User Guide 

|

 Optyma™ control AK-RC 111 single phase

8 | BC309238530328en-000101

© Danfoss | DCS (vt) | 2020.03

4.4 General

4.5  Key to symbols

4.6  Setting and displaying the 

set points

4.7  Level 1 programming

 

(user level)

4.8  List of Level 1 variables

 

(user level)

To enhance safety and simplify the operator’s work, the AK-RC 111 has two programming levels; the 

first level (Level 1) is used to configure the frequently-modified SETPOINT parameters. The second 

programming level (Level 2) is for general parameter programming of the various controller work 

modes.
It is not possible to access the Level 2 programming directly from Level 1: you must exit the 

programming mode first.

For purposes of practicality the following symbols are used:
(

) the UP key 

 is used to increase values and mute the alarm.

(

) the DOWN key 

 is used to decrease values and force defrosting.

1.  Press the 

SET key

 to display the current 

SETPOINT

 (temperature).

2.  Hold down the 

SET key

 and press the (

) or (

) keys to modify the 

SETPOINT

.

  Release the 

SET key

 to return to cold room temperature display: the new setting will be saved 

automatically.

To gain access to the Level 1 configuration menu proceed as follows:
1.  Press the (

) and (

) keys simultaneously and keep them pressed for a few seconds until the first 

programming variable appears on the display.

2.  Release the (

) and (

) keys.

3.  Select the variable to be modified using the (

) or (

) key.

4.  When the variable has been selected it is possible:

•  to display the setting by pressing SET key.
•  to modify the setting by pressing the SET key together with the (

) or (

) key.

 When configuration values have been set you can exit the menu by pressing the (

) or (

) keys 

simultaneously for a few seconds until the cold room temperature reappears.

5.  The new settings are saved automatically when you exit the configuration menu.

Variables Meaning

Value

Default

r0

Temperature difference

 compared to main SETPOINT

0.2 – 10 °C

2 °C

d0

Defrost interval

 (hours)

If 

d0

 = 0 cyclical defrosts Off

0 – 24 hours

4 hours

d2

End-of-defrost setpoint

Defrost is not executed if the temperature read by the defrost 
sensor is greater than 

d2

.

(If the sensor is faulty defrost is stopped on time set by the d3 
parameter)

-35 – 45 °C

15 °C

d3

Max defrost duration

 (minutes)

1 – 240 min

25 min

d7

Drip duration

 (minutes)

At the end of defrost the compressor and fans remain at standstill 
for time 

d7

, the defrost LED on the front panel flashes.

0 – 10 min

0 min

F5

Fan pause 

after defrost (minutes)

Allows fans to be kept at standstill for a time 

F5

 after dripping. This 

time begins at the end of dripping. If no dripping has been set the 
fan pause starts directly at the end of defrost.

0 – 10 min

0 min

A1

Minimum temperature alarm

Allows user to define a minimum temperature for the room being 
refrigerated. Below value 

A1

 an alarm trips: the alarm LED flashes, 

displayed temperature flashes and the buzzer sounds to indicate 
the problem.

-45 – (A2-1) °C

-45 °C

A2

Maximum temperature alarm

Allows user to define a maximum temperature for the room being 
refrigerated. Above value 

A2

 an alarm trips: the alarm LED flashes, 

displayed temperature flashes and the buzzer sounds to indicate 
the problem.

(A1+1) – 99 °C

99 °C

tEu

Evaporator sensor temperature display

 

(displays nothing if 

dE =1

)

evaporator 

temperature

read only

Summary of Contents for AK-RC 111

Page 1: ...User Guide Optyma control AK RC 111 single phase...

Page 2: ...ing and displaying the set points 8 4 7 Level 1 programming user level 8 4 8 List of Level 1 variables user level 8 4 9 Level 2 programming installer level 9 4 10 List of Level 2 variables installer l...

Page 3: ...iliary relays with parameter configured Integrated RS 485 Modbus connection for Danfoss System Manager or standard Modbus RTU network Emergency operation in the event of a faulty probe environment Sma...

Page 4: ...n the electronics For the purposes of assembly and use the electronic AK RC 111 control unit comes with 3 seals to be fitted between the fixing screws and the box back panel 1 user s manual Fig 1 Rais...

Page 5: ...e panel and carry out thorough reading programming of all the parameters Note Make all the electrical connections as illustrated in the diagram for the corresponding model see relative table in append...

Page 6: ...nstalled relay Card output characterstics Note Compressor Relay 30A AC1 10 A 250 V AC3 2HP 100000 cicli The sum of contemporary absorptions of these outputs has not to exceed 16 A Defrost Relay 30A AC...

Page 7: ...Cold room temperature parameters 7 Up Mute buzzer alarm 2 Stand by flashes on stand by outputs are deactivated 8 Room light flashes if door switch activated 9 Cold indicates activation of compressor 1...

Page 8: ...T key together with the or key When configuration values have been set you can exit the menu by pressing the or keys simultaneously for a few seconds until the cold room temperature reappears 5 The ne...

Page 9: ...d working for the F6 time If activation time coincides with the defrosting time end of defrosting is awaited 0 240 min 0 function not activated 0 min F7 Evaporator fans duration for air recirculation...

Page 10: ...he temperature value read by the evaporator sensor is higher than this value 45 99 C 99 C Fd Fst differential 1 10 C 2 C LSE Minimum value attributable to setpoint 45 HSE 1 C 45 C HSE Maximum value at...

Page 11: ...econd level programming not permitted 3 PA Password see P1 for the type of protection 0 999 0 not active 0 reL Release software indicates software version 2 read only 4 11 Switching on the AK RC 111 e...

Page 12: ...must allow opening of the cycle inversion solenoid valve and closure of the liquid solenoid valve For capillary systems without thermostat valve it is only necessary to control the cycle inversion so...

Page 13: ...room alarm Reset the alarm input inside the cold room Ec Compressor protection tripped e g thermal protection or max pressure switch All outputs except the alarm one where applicable are deactivated...

Page 14: ...front opening hinge 5 Box closure screws 6 Board fixing screws 7 Magneto thermal cut out power breaker 8 CPU board 9 Polycarbonate screw cover 10 Terminal for earth connections N F d d 1 2 3 4 5 6 7...

Page 15: ...User Guide Optyma control AK RC 111 single phase Danfoss DCS vt 2020 03 BC309238530328en 000101 15 8 0 Ordering Type Code no OPTYMATM Control single phase 2 HP including two sensors 080Z3220...

Page 16: ...oss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady...

Reviews: