• The installation of the data communication must be carried out 

as specified in the guide to the RC8AC.

• The terminations must be in order.

• Language options in an AKC controller

When data is retrieved and sent to the AK-PI 200 and then on to 
the system manager and operation software, it will appear in the 
language selected in the controller. 
If the wrong language is displayed, the AK-PI 200 must be 
restored to factory settings and an associated file on the PC must 
be deleted. 
(C:Program files\ADAP-KOOL\Service tool\Data\Cashe\Code no).
The whole process must then be repeated, but this time with a 
different language selected.

• Network addresses

Here is a small summary of the networks and addresses that can 
occur:
11:001 is the master system manager
11:002 to 11:010 are slave networks controlled by 11:001
(the figure “11” keeps track of the networks and cannot be 
changed).
11:012 to 11:999 are addresses for units on the network. The 
units can be AK-PI 200 units or wireless units, or they can be 
controllers in which the data communication takes place via 
TCP/IP.
1: xxx will be controllers that are registered under the master 
system manager.
2: xxx will be controllers that are registered under slave network 
number 2.

Requirements and terms

Principle

• Up to 60 AKC controllers can be connected to a single AK-PI 200.

• Up to two AK-PI 200 units can be connected to a single system 

manager.

• Up to 20 different types of AKC controller can be connected.

• There must not be a gateway or an AKA 21 connected to the 

DANBUSS communication – it is the AK-PI 200 that controls 
the communication to the controllers. 

Summary of Contents for AK-PI 200

Page 1: ...REFRIGERATION AND AIR CONDITIONING Protocol interface AK PI 200 Manual ...

Page 2: ...ware interface Or it can be used on new systems where the majority might be controllers with LON communication and other individual controls can be AKC controllers Principle The link between the system manager and the AK PI 200 is via a TCP IP In this very simple connection the two units can be connected to each other via a crossed cable This is where the IP addresses are set to static addresses O...

Page 3: ...e network The PI unit is perceived as a controller on the network and its address can be viewed in the IP list Up to two PI units can be connected to the system manager which is master i e has address 1 You set the network address on the front of the system units and on the front of the PI units Set the system manager to address 1 If there are several system managers slave network set these to add...

Page 4: ...the two units must be a crossed cable A static IP address is always used here b Cables from the units are connected to a router or to a switch A dynamic or static IP address is used here 2 Setting a Router Dynamic There are no settings in the router Static A static address range must be set in the router b AK SM 720 Select static if the connection between the system unit and the AK PI 200 is with ...

Page 5: ...ion 1 1x it must be set to 1 5 You can activate the Service PIN function at this point If you do this means you do not have to start the scan function in the next point Perform the first scan 1 Start the scan function in the system manager wait for the results the controllers on the LON and MODBUS communication will now be located and visible in the network overview 2 Go to the next page of the ne...

Page 6: ...networks and addresses that can occur 11 001 is the master system manager 11 002 to 11 010 are slave networks controlled by 11 001 the figure 11 keeps track of the networks and cannot be changed 11 012 to 11 999 are addresses for units on the network The units can be AK PI 200 units or wireless units or they can be controllers in which the data communication takes place via TCP IP 1 xxx will be co...

Page 7: ... manager that AK PI 200 is connected to The status of the alarm transmission Date and time The quality of the DANBUSS communication signal The configuration display gives access to the following The configuration lock is only used if a static IP address is to be set Under System setup you can give the unit a name IP settings can be entered ...

Page 8: ...AK PS 075 18 VA Supply 080Z0053 Type Function Application Language Code no AK PI 200 Protocol interface Intermediary link between system manager and controllers with DANBUSS data communication English German French Italian Dutch Spanish Portuguese Danish Swedish and Finnish 080Z8521 Data Supply voltage 24 V a c 20 Power consumption AK PI 200 12 VA Ambient temperature During transport 40 to 70 C Du...

Reviews: