Manual  RS8EX202  ©  Danfoss  02-2009 

AK-PI 200

Installation

Preparing controllers on DANBUSS

In an existing system

If it is an existing system in which the controllers have 
previously been connected to a gateway, the pairing (network 
number) with the gateway is registered so it can be set in AK-PI 
200. 
1. Register the network number for the later setting.

In a new system

1. Set the address of the controller
2. Switch it on if it is not already on
3. Set the desired language in the controller (connect the AKA 

21 and set the language selection menu. Disconnect the 
AKA 21 after entering settings).

Preparing TCP/IP connection

The AK-PI 200 must have a connection to the system manager – 
both physically and with a software setting. This can take place in 
one of the following ways:
1. Connection

a) Direct connection (only used if there is not an external 

connection via a router).
The cable between the two units must be a crossed cable.
(A static IP address is always used here.)

b) Cables from the units are connected to a router or to a switch.

(A dynamic or static IP address is used here.)

2. Setting

a) Router

- Dynamic: There are no settings in the router
- Static: A static address range must be set in the router

b) AK-SM 720

- Select static if the connection between the system unit and 

the AK-PI 200 is with a crossed cable or there is an external 
connection to the system. Then set the IP address (an IP 
address must be obtained from the local IT manager).

- Select dynamic if it is a closed system and the two units are 

connected to a router or a switch. 

c) In the AK-PI 200 the IP address is set either to static or to 

dynamic.
- Select static if the connection between the system unit and 

the AK-PI 200 is with a crossed cable. Then set the IP address 
(an IP address must be obtained from the local IT manager).

- Select dynamic if it is a closed system and the two units are 

connected to a router or a switch. 

3. If a router or switch is connected, it must be turned on.

1a)

1b)

Crossed cable

Network number

Summary of Contents for AK-PI 200

Page 1: ...REFRIGERATION AND AIR CONDITIONING Protocol interface AK PI 200 Manual ...

Page 2: ...ware interface Or it can be used on new systems where the majority might be controllers with LON communication and other individual controls can be AKC controllers Principle The link between the system manager and the AK PI 200 is via a TCP IP In this very simple connection the two units can be connected to each other via a crossed cable This is where the IP addresses are set to static addresses O...

Page 3: ...e network The PI unit is perceived as a controller on the network and its address can be viewed in the IP list Up to two PI units can be connected to the system manager which is master i e has address 1 You set the network address on the front of the system units and on the front of the PI units Set the system manager to address 1 If there are several system managers slave network set these to add...

Page 4: ...the two units must be a crossed cable A static IP address is always used here b Cables from the units are connected to a router or to a switch A dynamic or static IP address is used here 2 Setting a Router Dynamic There are no settings in the router Static A static address range must be set in the router b AK SM 720 Select static if the connection between the system unit and the AK PI 200 is with ...

Page 5: ...ion 1 1x it must be set to 1 5 You can activate the Service PIN function at this point If you do this means you do not have to start the scan function in the next point Perform the first scan 1 Start the scan function in the system manager wait for the results the controllers on the LON and MODBUS communication will now be located and visible in the network overview 2 Go to the next page of the ne...

Page 6: ...networks and addresses that can occur 11 001 is the master system manager 11 002 to 11 010 are slave networks controlled by 11 001 the figure 11 keeps track of the networks and cannot be changed 11 012 to 11 999 are addresses for units on the network The units can be AK PI 200 units or wireless units or they can be controllers in which the data communication takes place via TCP IP 1 xxx will be co...

Page 7: ... manager that AK PI 200 is connected to The status of the alarm transmission Date and time The quality of the DANBUSS communication signal The configuration display gives access to the following The configuration lock is only used if a static IP address is to be set Under System setup you can give the unit a name IP settings can be entered ...

Page 8: ...AK PS 075 18 VA Supply 080Z0053 Type Function Application Language Code no AK PI 200 Protocol interface Intermediary link between system manager and controllers with DANBUSS data communication English German French Italian Dutch Spanish Portuguese Danish Swedish and Finnish 080Z8521 Data Supply voltage 24 V a c 20 Power consumption AK PI 200 12 VA Ambient temperature During transport 40 to 70 C Du...

Reviews: