AK-PI 200 

Manual  RS8EX202  ©  Danfoss  02-2009 

3

Number of controllers

Up to 60 controllers can be connected to a single AK-PI 200. If 
there are more than 60 controllers, two AK-PI 200 units should be 
used. 

Up to two AK-PI 200 units can be connected to a single system 
manager, in other words up to 120 controllers on the DANBUSS 
communication. If there are two AK-PI 200 units, the connection 
to the system manager is led via a router or a switch.

Addresses

In principle there are three types of addresses:

IP addresses

Both the system manager and the AK-PI 200 must have an IP 
address set.
The address can be either dynamic or static – the desired value is 
selected with a setting. If static is chosen, an address must also be 
set.
If the system can be accessed externally, the setting in the 
system manager AK-SM 720 must always be set to static so that 
the external connection always recognises the address and can 
communicate with the unit.
(The IP address is set in a menu).

Network addresses

There must always be one and only one master system manager 
on a network. This is defined with the address setting = 1. This 
system manager controls the communication to all the other 
controllers on the network. The PI unit is perceived as a controller 
on the network and its address can be viewed in the IP list. (Up to 
two PI units can be connected to the system manager, which is 
master - i.e. has address =1)
(You set the network address on the front of the system units and 
on the front of the PI units.) 
Set the system manager to address 1.
If there are several system managers (slave network), set these to 
addresses 2 to 10.
Each PI unit is set with a separate address. Select 12 or higher, e.g. 
21. 

Interconnection
When setting the system manager, a menu must also be set 
in which the relevant AK-PI 200 chooses the network. The 
system manager then knows the way to the different DANBUSS 
controllers. The system manager must be version 1.20 or later.

Controller addresses

All controllers on the same network must have different addresses. 
In other words, all controllers that are connected to a system 
manager on either:

• the LON communication
• the MODBUS communication or
• the DANBUSS communication.

Start with the addresses on DANBUSS. They must be set with a DIP 
switch and cannot be set to higher than 120. 
The addresses on the LON and MOD buses can be set higher.
No more than 200 controllers can be connected to a system 
manager.

DANBUSS communication:   Address options 1 to 120
LON communication:  

Address options 1 to 999

MODBUS communication:   Address options 1 to 247

Max. number of controllers:   200

Summary of Contents for AK-PI 200

Page 1: ...REFRIGERATION AND AIR CONDITIONING Protocol interface AK PI 200 Manual ...

Page 2: ...ware interface Or it can be used on new systems where the majority might be controllers with LON communication and other individual controls can be AKC controllers Principle The link between the system manager and the AK PI 200 is via a TCP IP In this very simple connection the two units can be connected to each other via a crossed cable This is where the IP addresses are set to static addresses O...

Page 3: ...e network The PI unit is perceived as a controller on the network and its address can be viewed in the IP list Up to two PI units can be connected to the system manager which is master i e has address 1 You set the network address on the front of the system units and on the front of the PI units Set the system manager to address 1 If there are several system managers slave network set these to add...

Page 4: ...the two units must be a crossed cable A static IP address is always used here b Cables from the units are connected to a router or to a switch A dynamic or static IP address is used here 2 Setting a Router Dynamic There are no settings in the router Static A static address range must be set in the router b AK SM 720 Select static if the connection between the system unit and the AK PI 200 is with ...

Page 5: ...ion 1 1x it must be set to 1 5 You can activate the Service PIN function at this point If you do this means you do not have to start the scan function in the next point Perform the first scan 1 Start the scan function in the system manager wait for the results the controllers on the LON and MODBUS communication will now be located and visible in the network overview 2 Go to the next page of the ne...

Page 6: ...networks and addresses that can occur 11 001 is the master system manager 11 002 to 11 010 are slave networks controlled by 11 001 the figure 11 keeps track of the networks and cannot be changed 11 012 to 11 999 are addresses for units on the network The units can be AK PI 200 units or wireless units or they can be controllers in which the data communication takes place via TCP IP 1 xxx will be co...

Page 7: ... manager that AK PI 200 is connected to The status of the alarm transmission Date and time The quality of the DANBUSS communication signal The configuration display gives access to the following The configuration lock is only used if a static IP address is to be set Under System setup you can give the unit a name IP settings can be entered ...

Page 8: ...AK PS 075 18 VA Supply 080Z0053 Type Function Application Language Code no AK PI 200 Protocol interface Intermediary link between system manager and controllers with DANBUSS data communication English German French Italian Dutch Spanish Portuguese Danish Swedish and Finnish 080Z8521 Data Supply voltage 24 V a c 20 Power consumption AK PI 200 12 VA Ambient temperature During transport 40 to 70 C Du...

Reviews: