6
Manual RS8GE202 © Danfoss 01-2016
AK-PC
560
Actuel zone state:
0=off. 2=-zone. 3=Neutral zone.
4=+zone.
Condenser capacity
Definition of condenser and number of fans
Here you set the number of fan steps with which regulation has to be carried out (but
max. eight).
1-8:
All fans are cut in and out with relays. The first vacant relay number is assigned to
fan 1, the next to number 2, etc. Steps after DO8 must be executed through connec-
tion of a relay module type EKC 331 to the analog output. Cf. drawing on page 12.
9:
All fans controlled via the analog output and a frequency converter.
10:
Not used
11-18:
Total number of fan relays (as 1-8), but here the starting sequence is altered
after each time all fans are stopped.
c29
Fan mode
Read temperature at sensor Sc3
u44
Sc3 temp
Read temperature at sensor Sc4
(sensor is only used for monitoring)
u45
Sc4 temp
-
- - - Fan Cap %
Read cut-in condenser capacity
Regulation parameters for the condenser regulation
Proportional band xp (P = 100/Xp)
If the Xp value is increased, the regulation becomes steadier
n04
Xp K / Xp b
I: Integration time Tn
If the Tn value is increased, the regulation becomes steadier
n05
Tn s
Manual control of condenser capacity
This sets the capacity that is to be cut in when switching to manual control.
n52
FanManCap%
Manual control
Manual control of the condenser capacity is enabled here.
When set to ON, the capacity that is specified in “n52” is cut in.
n53
FanManCap
Speed control start value
Speed control will only be activated when the capacity requirement reaches this
value.
n54
StartSpeed
Speed control stop value
Speed control will be stopped when the capacity requirement falls below this value.
n55
MinSpeed
Alarm
Alarm settings
The controller can give alarm in different situations. When there is an alarm the light-
emitting diodes (LED) will flash on the display and the alarm relay will cut in.
(In AK-PC 560 the alarm relay may be used for a fan, if required).
P0 min.
(Alarm and safety function, see also page 20.)
Here you set when the alarm at too low suction pressure is to enter into effect. The
value is set as an absolute value.
A11
Min. P0.°C / Min. P0. b
Alarm delay P0 alarm
The time delay is set in minutes. At min. setting the alarm is cancelled.
A44
P0AlrmDelay
Pc max.
(Alarm and safety function, see also page 20.)
Here you set when the alarm at too high condensing pressure is to enter into effect.
The value is set as an absolute value.
A30
Max. Pc.°C / Max. Pc. b
Alarm delay Pc alarm
The time delay is set in minutes. At min. setting the alarm is cancelled.
A45
PcAlrmDelay
Alarm delay DI1 (an interrupted input will give alarm).
The time delay is set in minutes. At max. setting the alarm is cancelled.
A27
DI1AlrmDelay
Alarm delay DI2
(an interrupted input will give alarm).
The time delay is set in minutes. At max. setting the alarm is cancelled.
A28
DI2AlrmDelay
Alarm delay DI3
(an interrupted input will give alarm).
The time delay is set in minutes. At max. setting the alarm is cancelled.
A29
DI3AlrmDelay
Alarm limit for high temperature of the “Saux1” sensor
If an alarm is generated the digital scroll stops. With setting = Off the alarm has been
opted out.
A32
Saux Al Lim
Alarm delay from "Saux1" (A32)
If the limit value is exceeded, a timer function will commence. The alarm will not be-
come active until the set time delay has been passed. The time delay is set in minutes.
A03
Alarm delay
Give the top button a brief push to zeroset the alarm and to have the message shown
on the display.
Reset alarm
The function zerosets all alarms when
set in pos. ON.