14
Manual RS8GE202 © Danfoss 01-2016
AK-PC
560
Menu survey
SW: 1.0x
Fortsættes
Sequence
1.
o61
must
be set as the first parameter. This parameter determines which of the four operating interfaces (application mode) are
activated. This
must
be set via the display keys. It cannot be set via data communication. (Active functions are shown below in shaded
fields.)
2.
Quick- start
To get the system up and running quickly so that cooling can be commenced, start it by setting the following parameters (these pa-
rameters can only be set when the regulation is stopped, r12=0): r23, r28, c08, c16, c29, o06, o30, o75, o76
and finally r12=1
.
3.
Once the regulation is under way, you can go through the other parameters and adjust them in situ.
Function
Para-
meter
o61 =
Min.
Max.
Factory
setting
1
2
Normal display
Shows P0 in EKA 165 (display with buttons)
-
°C
P
°C / bar
Shows Pc in EKA 163
-
°C
P
°C / bar
P0 reference
Neutral zone
r01
0.1°C / 0.1 bar
20°C /5.0 bar
4.0°C / 0.4 bar
Correction of signal from P0 sensor
r04
-50°C /-5.0 bar
50°C / 5.0 bar
0.0
Select view; SI or US. 0=SI (bar /°C), 1=US (Psig /°F)
r05
0
1
0
Start/Stop of regulation
r12
OFF
ON
OFF
Reference offset for P0 (see also r27)
r13
-50°C / -5.0 bar
50°C / 5.0 bar
0.0
Set regulation set point for P0
r23
-99°C / -1 bar
30°C / 60.0 bar
0.0°C / 3.5 bar
Shows total P0 reference
( r23 + various displacements)
r24
°C / bar
Limitation: P0 reference max. value
(also applies to regulation with reference displacement)
r25
-99°C / -1.0 bar
30°C / 60.0 bar
30.0°C / 40.0 bar
Limitation: P0 reference min. value
(also applies to regulation with reference displacement)
r26
-99°C / -1.0 bar
30°C / 40.0 bar
-99.9°C / -1.0 bar
Displacement of P0 (ON=active “r13”)
r27
OFF
ON
OFF
Pc reference
Set regulation set point for Pc
r28
-25°C / 0.0 bar
75°C / 110.0 bar 35°C / 15.0 bar
Shows total Pc reference
r29
°C / bar
Limitation: Pc reference max. value
r30
-99.9°C / -0.0 bar 99.9°C/ 130.0bar 55.0°C / 60.0 bar
Limitation: Pc reference min. value
r31
-99.9°C / 0.0 bar 99.9°C / 60.0 bar -99.9°C / 0.0 bar
Correction of signal from Pc sensor
r32
-50°C / -5.0 bar
50°C / 5.0 bar
0.0
Pc reference variation. 1 and 2 are PI-regulation
1: Fixed reference. “r28” is used
2: Variable reference. Outdoor temperature (Sc3) included in the refer-
ence
3: As 1, but with P-regulation (Xp-band)
4: As 2, but with P-regulation (Xp-band)
r33
1
4
1
Reference offset for Pc
r34
-50°C / -5.0 bar
50°C / 5.0 bar
0.0
The mean temperature difference across the condenser at maximum
load (dim tm K)
r35
3.0
50.0
10.0
The mean temperature difference across the condenser at the lowest
relevant compressor capacity (min tm K)
r56
3.0
50.0
8.0
Capacity
Min. ON time for relays
c01
0 min
30 min.
0
Min. time period between cutins of same relay
c07
2 min.
60 min
2
Definition of regulation mode
1: Sequential (step mode / FILO)
2: Cyclic (step mode / FIFO)
c08
1
2
1
Definition of compressor connections.
See options on page 11.
c16
1
7
1
Definition of condenser:
1-8:
Total number of fan relays or voltage step on the voltage output
9:
Only via analog output and start of frequency converter
10:
Not used
11- 18:
Total number of fan relays which are to be connected with alter-
nating start-up.
c29
0/OFF
18
0
Cut in compressor capacity with manual control. See also “c32”
c31
0%
100%
0
Manual control of compressor capacity (when ON, the value in “c31” will
be used)
c32
OFF (0)
ON (1)
OFF (0)