AK-PC
560
Manual RS8GE202 © Danfoss 01-2016
17
The controller can give the following messages
E1
Error
message
Fault in controller
E2
Regulation is outside the range, or the control
signal is defective
A2
Alarm
message
Low P0
A11
Refrigerant not selected
A17
High Pc
A19
Compressor 1 error (29)
The actual compressors
safety circuit is
interrupted.
That is to say the signal
is missing on one of the
terminals 29-36
A20
Compressor 2 error (31)
A21
Compressor 3 error (32)
A22
Compressor 4 error (33)
A23
Compressor 5 error (34)
A24
Compressor 6 error (35)
A25
Compressor 7 error (36)
A27
Saux discharge gas temperature to high . Digital
scroll is stopped
A28
DI 1 alarm. Terminal 46 interrupted
A29
DI 2 alarm. Terminal 47 interrupted
A30
DI 3 alarm. Terminal 49 interrupted
A31
DI 4 alarm. Terminal 50 interrupted
A32
DI 5 alarm. Terminal 52 interrupted
A34
Fan alarm. There is no signal on DI1 input
A45
Regulation stopped
S0
Status
message
Regulation
S2
Wait for “c01”
S5
Wait for “c07”
S10
Refrigeration stopped by the internal or external
start/stop function
S25
Manual control of outputs
S34
Safety cutout.
Setting A30 is exceeded or all safety inputs (29-
36) are open
PS
Info
Access code is required before you have access to
the settings
Messages can be brought up on the display by briefly pressing
the uppermost key. If there is more than one alarm, they can be
scrolled through
Factory setting
If you need to return to the factory-set values, it can be done in
this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as
you reconnect the supply voltage