Danfoss AK-CC 460 Instructions Manual Download Page 7

 

AK-CC 

460 

Instructions RI8SE202 © Danfoss 07/2017 

7

Drip off time

d06

1

0 min.

60 min.

0

Delay for fan start after defrost

d07

1

0 min.

60 min.

0

Fan start temperature

d08

1

-50 °C

0 °C

-5

Fan cutin during defrost
0: stopped
1 & 2: Running

d09

1

0

2

1

Defrost sensor:

 0 =Stop on time, 1=S5, 2=S4, 3=S5 and S6

d10

1

0

3

0

Pump down delay

d16

1

0 min.

60 min.

0

Max. aggregate refrigeration time between two defrosts

d18

1

0 hrs

48 hrs

0/OFF

Rail heat during defrost
0: off
1: on
2: Pulsing

d27

1

0

2

2

Max. duration of -d- in display

d40

1

5 min.

240 min.

30 min.

Fan

Fan stop temperature (S5)

F04

1

-50°C

50°C

50

Pulse operation on fans:  0=No pulse operation,  1=At thermostat cuts out only,  2= 
Only at thermostat cut outs during night operation

F05

1

0

2

0

Period time for fan pulsation (on-time + off-time)

F06

1

1 min.

30 min.

5

On-time in % of period time

F07

1

0 %

100 %

100

Real time clock

Six start times for defrost. 
Setting of hours. 
0=OFF

t01 - 
t06

1

0 hrs

23 hrs

0

Six start times for defrost.
Setting of minutes.
0=OFF

t11 - 
t16

1

0 min.

59 min.

0

Clock - Setting of hours

t07

1

0 hrs

23 hrs

0

Clock - Setting of minute

t08

1

0 min.

59 min.

0

Clock - Setting of date

t45

1

1 day

31 day

1

Clock - Setting of month

t46

1

1 mon.

12 mon.

1

Clock - Setting of year

t47

1

0 year

99 year

0

Miscellaneous

Delay of output signals after start-up

o01

1

0 sec

600 sec

5

Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm 
when open. 4=defrost start (pulse-signal).  5=ext.main switch. 6=night operation 
7=thermostat band changeover (activate r21). 8=alarm function when closed. 9=alarm 
function when open. 10=case cleaning (pulse signal). 12=night cover. 15=appliance 
shutdown

o02

1

0

15

0

Network address (0= off)

o03

1

0

240

0

On/Off switch (Service Pin message)
IMPORTANT! o61 must be set prior to o04

(used at LON 485 only)

o04

1

0/Off

1/On

0/Off

Access code 1 (all settings)

o05

1

0

100

0

Software Version 

o08

1

Max hold time after coordinated defrost

o16

1

0 min.

360 min.

20

Select signal for display view.  S4% (100%=S4, 0%=S3)

o17

1

0 %

100 %

100

Input signal on DI2. Function: 
0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm 
when open. 4=defrost start (pulse-signal).  5=ext. main switch 6=night operation 
7=thermostat band changeover (activate r21). 8=alarm function when closed. 9=alarm 
function when open. 10=case cleaning (pulse signal). 12=night cover, 13=coordinated 
defrost. 15=appliance shutdown

o37

1

0

15

0

Configuration of light function

: 1=Light follows day /night operation,  2=Light 

control via data communication via ‘o39’,  3=Light control with a DI-input,  4=As "2", 
but light switch on and night cover will open if the network cut out for more than 
15 minutes.

o38

1

1

4

1

Activation of light relay (only if o38=2)

  On=light

o39

1

0/Off

1/On

0/Off

Rail heat On time during day operations

o41

1

0 %

100 %

100

Rail heat On time during night operations

o42

1

0 %

100 %

100

Rail heat period time (On time + Off time)

o43

1

6 min.

60 min.

10

Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output Off.

***

o46

1

0

2

0

Selection of  EL diagram. See overview page 1

*

o61

1

1

1

1

Access code 2 (partial access)

***

o64

1

0

100

0

Replace the controllers factory settings with the present settings

o67

1

0/Off

1/On

0/Off

Continued

code

 1

Min.

Max.

Fac.

Actual

Summary of Contents for AK-CC 460

Page 1: ...Principle Dimensions Instructions AK CC 460 RI8SE202 07 2017 Identification 084B8016 1...

Page 2: ...her RJ45 For data communication but only if a TCP IP module is inserted in the controller OEM MODBUS For data communication Terminal 56 screen Terminal 57 A Terminal 58 B Alternatively the terminals c...

Page 3: ...ectly See separate literature No RC8AC Electric noise Cables for sensors DI inputs and data communication must be kept separate from other electric cables Use separate cable trays Keep a distance betw...

Page 4: ...ion 6 20 AK SM Data communication Display EKA 163 164 L 15 m L 15 m Important All connections to the data communication MODBUS RS 485 and DANBUSS must comply with the requirements for data communicati...

Page 5: ...arameter value is shown 4 Push the upper or the lower button and select the new value 5 Push the middle button again to set the value Cutout alarm relay receipt alarm see alarm code A short press of t...

Page 6: ...Delay for temperature alarm after defrost A12 1 0 min 240 min 90 High alarm limit for thermostat 1 A13 1 50 C 50 C 8 Low alarm limit for thermostat 1 A14 1 50 C 50 C 30 High alarm limit for thermostat...

Page 7: ...d changeover activate r21 8 alarm function when closed 9 alarm function when open 10 case cleaning pulse signal 12 night cover 15 appliance shutdown o02 1 0 15 0 Network address 0 off o03 1 0 240 0 On...

Page 8: ...1 Temperature measured with S3 sensor u12 1 Status on night operation on or off 1 on u13 1 Temperature measured with S4 sensor u16 1 Thermostat temperature u17 1 Run time of thermostat cooling time in...

Page 9: ...nations Settings from System manager AK SM Settings from AKM AKM destination Send via Network High 1 X Middle 2 X Low 3 X Log only Disabled Operating status Measure ment The controller goes through so...

Reviews: