Danfoss AK-CC 460 Instructions Manual Download Page 2

Instructions RI8SE202 © Danfoss 07/2017 

 

 AK-CC 

460

DI1
Digital input signal.  
The defined function is active when the input is short-circuited/
opened. The function is defined in o02. 

DI2
Digital input signal.  
The defined function is active when the input is short-circuited/
opened. The function is defined in o37. 

S7, S3, S4, S5, S6 
Pt 1000 ohm

S7, brine sensor, placed in the cold inlet before the heat exchanger 
S3, air sensor, placed in the warm air before the evaporator
S4, air sensor, placed in the cold air after the evaporator

(the need for either S3 or S4 can be deselected in the 
configuration) 

S5, defrost sensor, placed on the evaporator
S6, product sensor 

EKA Display
If there is be external reading/operation of the controller, display 
type EKA 163B or EKA 164B can be connected. 

RS485 (terminal 51, 52, 53)
For data communication, but only if a data communication 
module is inserted in the controller. The module can be a LON 
RS485, DANBUSS or a MODBUS.
Terminal 51 = screen
Terminal 52 = A (A+)
Terminal 53 = B (B-)
(For LON RS485 and gateway type AKA 245 the gateway must be 
version 6.20 or higher.)

RJ45
For data communication, but only if a TCP/IP module is inserted in 
the controller. (OEM)

MODBUS
For data communication.
Terminal 56 = screen
Terminal 57 = A+
Terminal 58 = B-
(Alternatively the terminals can be connected to an external 
display type EKA 163A or 164A, but then they cannot be used 
for data communication. Any data communication must then be 
carried out by one of the other methods.)

Supply voltage
230 V a.c., 50/60 Hz

DO1

Compressor 1 

Connection of relay. The coil must be a 230 V a.c. coil.

DO2

Alarm

There is a connection between terminal 7 and 8 in alarm 
situations and when the controller is without power.

DO3

Compressor 2

There is connection between terminal 10 and 11 when the 
compressor is on.

DO4

Defrost

There is connection between terminal 12 and 14 when 
defrosting takes place.

DO5

Fan

There is connection between terminal 15 and 16 when the fan 
is on.

Connections

Overview of outputs and applications.

Application

DO1

DO2

DO3

DO4

DO5

DO6

DO7 DI1 DI2 DI3 AI1 AI2 AI3 AI4 AI5 AI6

1

• • •

S7

S3

S4

S5

S6

See also electrical diagrams earlier in the instruction.

DI1 DI2

DI3

DO1 

DO2  DO3 DO4 DO5 DO6  

DO7 

Solid state 
output

DO1
(for coil)

Max. 240 V a.c. , Min. 28 V a.c.
Max. 0.5 A
Leak < 1 mA
Max. 1 pcs. coil

Relays

CE 
(250 V a.c.)
IBExU approved

DO3, DO4 4 (3) A
DO2, DO5, 
DO6, DO7

4 (3) A

Summary of Contents for AK-CC 460

Page 1: ...Principle Dimensions Instructions AK CC 460 RI8SE202 07 2017 Identification 084B8016 1...

Page 2: ...her RJ45 For data communication but only if a TCP IP module is inserted in the controller OEM MODBUS For data communication Terminal 56 screen Terminal 57 A Terminal 58 B Alternatively the terminals c...

Page 3: ...ectly See separate literature No RC8AC Electric noise Cables for sensors DI inputs and data communication must be kept separate from other electric cables Use separate cable trays Keep a distance betw...

Page 4: ...ion 6 20 AK SM Data communication Display EKA 163 164 L 15 m L 15 m Important All connections to the data communication MODBUS RS 485 and DANBUSS must comply with the requirements for data communicati...

Page 5: ...arameter value is shown 4 Push the upper or the lower button and select the new value 5 Push the middle button again to set the value Cutout alarm relay receipt alarm see alarm code A short press of t...

Page 6: ...Delay for temperature alarm after defrost A12 1 0 min 240 min 90 High alarm limit for thermostat 1 A13 1 50 C 50 C 8 Low alarm limit for thermostat 1 A14 1 50 C 50 C 30 High alarm limit for thermostat...

Page 7: ...d changeover activate r21 8 alarm function when closed 9 alarm function when open 10 case cleaning pulse signal 12 night cover 15 appliance shutdown o02 1 0 15 0 Network address 0 off o03 1 0 240 0 On...

Page 8: ...1 Temperature measured with S3 sensor u12 1 Status on night operation on or off 1 on u13 1 Temperature measured with S4 sensor u16 1 Thermostat temperature u17 1 Run time of thermostat cooling time in...

Page 9: ...nations Settings from System manager AK SM Settings from AKM AKM destination Send via Network High 1 X Middle 2 X Low 3 X Log only Disabled Operating status Measure ment The controller goes through so...

Reviews: