Danfoss AK-CC 460 Instructions Manual Download Page 5

 

AK-CC 

460 

Instructions RI8SE202 © Danfoss 07/2017 

5

Light-emitting diodes (LED) on front panel
The LED’s on the front panel will light up when the relevant relay 
is activated.

 = Refrigeration

 = Defrost
 = Fan running

The light-emitting diodes will flash when there is an alarm.
In this situation you can download the error code to the display 
and cancel/accept for the alarm by giving the top button a brief 
push.

The buttons
When you want to change a setting, the upper and the lower 
buttons will give you a higher or lower value depending on the 
button you are pushing. But before you change the value, you 
must have access to the menu. You obtain this by pushing the 
upper button for a couple of seconds - you will then enter the col-
umn with parameter codes. Find the parameter code you want to 
change and push the middle button until value for the parameter 
is shown. When you have changed the value, save the new value 
by once more pushing the middle button.

Examples

Set menu

1. Push the upper button until a parameter r01 is shown
2. Push the upper or the lower button and find that parameter you 

want to change

3. Push the middle button until the parameter value is shown
4. Push the upper or the lower button and select the new value
5. Push the middle button again to set the value.

Cutout alarm relay / receipt alarm/see alarm code 

• A short press of the upper button

If there are several alarm codes they are found in a rolling stack. 
Push the uppermost or lowermost button to scan the rolling 
stack.

Set temperature

1. Push the middle button until the temperature value is shown
2. Push the upper or the lower button and select the new value
3. Push the middle button again to conclude the setting.

Reading the temperature at defrost sensor (Or product sensor, if 
selected in o92.) 

• A short press of the lower button

Manual start or stop of a defrost

• Push the lower button for four seconds.

Controller/Display
The values will be shown with three digits, and with a setting you 
can determine whether the temperature is to be shown in °C or in 
°F.

Get a good start

With the following procedure you can start regulation very quick-
ly:

1 Open parameter r12 and start the regulation

2 Go through the survey of factory settings. Make any necessary 

changes in the respective parameters.

3 For network. Set the address in o03

4 Send address to system unit:

• MODBUS: Activate scan function in system unit
• If another data communication card is used in the controller:

- LON RS485: Activate the function o04

Operation

Summary of Contents for AK-CC 460

Page 1: ...Principle Dimensions Instructions AK CC 460 RI8SE202 07 2017 Identification 084B8016 1...

Page 2: ...her RJ45 For data communication but only if a TCP IP module is inserted in the controller OEM MODBUS For data communication Terminal 56 screen Terminal 57 A Terminal 58 B Alternatively the terminals c...

Page 3: ...ectly See separate literature No RC8AC Electric noise Cables for sensors DI inputs and data communication must be kept separate from other electric cables Use separate cable trays Keep a distance betw...

Page 4: ...ion 6 20 AK SM Data communication Display EKA 163 164 L 15 m L 15 m Important All connections to the data communication MODBUS RS 485 and DANBUSS must comply with the requirements for data communicati...

Page 5: ...arameter value is shown 4 Push the upper or the lower button and select the new value 5 Push the middle button again to set the value Cutout alarm relay receipt alarm see alarm code A short press of t...

Page 6: ...Delay for temperature alarm after defrost A12 1 0 min 240 min 90 High alarm limit for thermostat 1 A13 1 50 C 50 C 8 Low alarm limit for thermostat 1 A14 1 50 C 50 C 30 High alarm limit for thermostat...

Page 7: ...d changeover activate r21 8 alarm function when closed 9 alarm function when open 10 case cleaning pulse signal 12 night cover 15 appliance shutdown o02 1 0 15 0 Network address 0 off o03 1 0 240 0 On...

Page 8: ...1 Temperature measured with S3 sensor u12 1 Status on night operation on or off 1 on u13 1 Temperature measured with S4 sensor u16 1 Thermostat temperature u17 1 Run time of thermostat cooling time in...

Page 9: ...nations Settings from System manager AK SM Settings from AKM AKM destination Send via Network High 1 X Middle 2 X Low 3 X Log only Disabled Operating status Measure ment The controller goes through so...

Reviews: