I
AHF,N
ordering number
max fuse rating
ordering number
max fuse rating
[Amp]
AHF 005
[Amp]
AHF 010
[Amp]
43
130B2328
63
130B2293
63
72
130B2330
125
130B2295
125
101
130B2331
160
130B2296
160
144
130B2333
250
130B2298
250
180
130B2334
315
130B2299
315
217
130B2335
315
130B2300
315
289
130B2301
500
324
130B2302
500
370
130B2304
630
Table 4.5: AHF005 and AHF010, 690V, 50Hz
4.1.6 Over temperature contactor
The Danfoss harmonic filter AHF 005 and AHF 010 is equipped with a galvanic isolated contactor that is closed under normal operating conditions
and open if the filter is overheated. A controlled ramp down within 30 s is allowed with overheat damage of filter. This contactor must be used to
prevent damage to the filter caused by over temperature as shown in the following example.
Example: Connect terminal A of the harmonic filter to terminal 12 or13
(voltage supply digital input, 24V) of the Danfoss frequency converter and
terminal B to terminal 27 (digital input “Coast Inverse”) the frequency
converter will let go of the motor (coasting) and thereby unload the filter
if an over temperature is detected.
NB!
The maximum rating of the over temperature contactor is 250V AC and 10A.
4.1.7 Power wiring size
Enclosure
Max. cable size mm
2
AWG
Type
Nom. Fix Torque
B
16
6
Connector
2 Nm
C and D
50
1
Connector
6 Nm
E, F, G and H
*
*
Bus Bars
25 Nm
Table 4.6: Power wiring size
Enclosure
Max. cable size mm
2
AWG
Type
Nom. Fix Torque
4
Connector
0.6 Nm
Table 4.7: Overheat contactor (copper)
Enclosure
Max. cable size mm
2
AWG
Type
Nom. Fix Torque
B
4
10
Connector
0.6 Nm
C and D
16
6
Connector
2 Nm
E, F, G and H
50
1
Connector
6 Nm
Table 4.8: Capacitor disconnect (copper)
*Power wiring used for connection of the filter AHF 005 and AHF 010 in enclosure size E, F and G must be terminated with cable lugs that can be attached
to the input and output bus bars terminals. This type of termination imposes no specifications of the minimum and maximum cable size suitable for
connection. Power terminal details regarding the bus bars can be found in the figures below.
AHF 005/010 Operating Instructions
4 Installation
MG.80.C1.02 - VLT
®
is a registered Danfoss trademark
23