AFD 2 / VFG 2 (21) DN 15-250, VFG 22 (221) DN 65-250

ENGLISH

Safety Notes

Prior to assembly and commissioning 
to avoid injury of persons and damages 
of the devices, it is absolutely necessary 

to carefully read and observe these instructions.

Necessary assembly, start-up, and maintenance 
work must be performed only by qualified, 
trained and authorized personnel.

Prior to assembly and maintenance work on the 
controller, the system must be:

- depressurized,
-  cooled down,
-  emptied and
- cleaned.

Please comply with the instructions of the 
system manufacturer or system operator.

Disposal instructions

 This product should be dismantled 
and its components sorted, if possible, 
in various groups before recycling or 

disposal.
Always follow the local disposal regulations.

Definition of Application

The controller is used for pressure reduction of 
water and water glycol mixtures for heating, 
district heating and cooling systems.

The technical data on the label plates determine 
the use.

Scope of Delivery 

*)  Impulse tube AF, accessory

Assembly

Admissible Installation Positions 

  media temperatures up to 150 °C: 

Can be installed in any positi on.

  media temperatures > 150 °C. 

Installation permitted only in horizontal 
pipelines with the actuator oriented 
downwards.

Installation Location and Installation 
Scheme 

 The valve is open without pressure and 
is closing on rising pressure.
System must be protected behind the 

pressure reducer by a safety monitoring unit 

.

Valve Installation 

1.  Install strainer 

 before the controller.

2.  Rinse system prior to installing the valve.
3.  Observe flow direction 

 on valve body.

 Flanges 

 in the pipeline must be in 

parallel position and sealing surfaces 
must be clean and without any damage.

4.  Install valve.
5.  Tighten screws crosswise in 3 steps up to the 

max. torque.

Actuator Installation 

 The actuator stem must be screwed 
into the valve stem. Spring on the 
pressure actuator is factory adjusted 
(released) for proper installation.

1.  Remove the spindle protection cup and 

release the valve spindle by removing the 
nut, washer and cardboard tube.

2.  Align the actuator stem with the valve stem, 

connect both stems and turn gently the whole 
pressure actuator clockwise with both hands, 
until the stems are fully connected (valve stem 
fully screwed into the actuator stem). 

3.  Release the uninon nut by pulling out the 

blocking spring.

4.  Tight the union nut
5.  Release the pressure actuator by turning it 

counter clockwise for approximately half a turn.

6.  Observe the position of impulse tubes 

connection to the valve and align the 
actuator accordingly.

7.  Hold the actuator in the position and tight 

the union nut to the valve with 100- 120 Nm 
torque.

Impulse Tube mounting 

•  Which impulse tubes to use?
 

The impulse tube set AF (2×) 

❻①

 can be 

used: Order No.: 

003G1391

 

or use the following pipes: 

Stainless steel

Ø 10×0.8  DIN 17458, DIN 2391

Steel

Ø 10×1

DIN 2391

Copper

Ø 10×1

DIN 1754

• 

The impulse tube 

③ 

can be connected

 

directly to the valve

 

 or 

to the pipeline

 

.

 ⑥

 ventilation socket, do not connect 

impulse tube.

Connection to the valve 

1.  Remove plug 

 at the valve.

2.  Screw in threaded joint G 1/4 

 with copper 

seal, Torque 40 Nm.

- or -

Connection to the Pipeline 

❽①

No connection downwards/upwards 

, could

bring dirt/air into an impulse tube.
1.  Cut pipe in rectangular sections 

 and deburr.

2.  For copper pipe: 

insert sockets 

 on both sides.

3.  Verify the correct position of the cutting 

ring 

.

4.  Press impulse tube 

 into the threaded joint 

up to its stop.

5.  Tighten union nut 

 Torque 40 Nm.

 When installing seal pots 

❽⑧

, please 

observe the Installati on Instructions 
for the seal pots.

Insulation 

For media temperatures up to 120 °C the 
pressure actua tor may be insulated 

.

Dismounting 

 

Danger

Danger of injury by hot water

Prior to dismounting depres surize system or 
use shut off valves on the impulse tubes! 

Carry out dismounting in following steps: 

1.   Fasten pressure actuator with the safety 

bands to the fixed points in surroundings 

2.  Before releasing the actuator, fully release 

the union nut

3.   Hold the pressure actuator with both 

hands, and release it by turning it counter 
clockwise ~30 turns. During turning, control 
the actuator weight all the time to prevent 
unexpected fall of detached actuator.

4.   Carefully remove the actuator from the valve.

Before installing actuator back to the valve, 
setting spring must be fully released again.

Leak and Pressure Test 

  Observe max.
permitted pressure, see below.

The pressure behind the valve

 ②

 must not 

exceed the pressure before the valve 

.

Observe nominal pressure

 ⑤ 

of the valve. 

Prior to pressure tests, it is absolutely necessary 
to remove the impulse tube at the valve 

.

Close connections with plugs G ¼ ISO 228.

Max. pressure [bar] with connected impulse 
tube:

AFD 2 (cm

2

)

32

80

160

320

640

bar

16

5

4

1,5

0,35

Max. test pressure [bar] with disconnected 
impulse tube must not exceed the plant testing 
pressure and must always be lower than 1.5 × PN. 

Non-compliance may cause damages at the 
controller 

.

Filling the System, Start-up 

The pressure 

 behind the valve must 

not exceed the pressure 

 before the

valve.

Non-compliance may cause damages at the 
controller 

.

1.  Open shut-off devices 

 that are possibly 

available at the impulse tubes.

2.  Slowly open valves in the system.
3.  Slowly open shut-off devices 

 in the supply 

flow.

4.  Slowly open shut-off devices 

 in the return 

flow.

Putting out of Operation

1.  Slowly close shut-off devices 

 in the supply 

flow.

2.  Slowly close shut-off devices 

 in the return 

flow.

Setpoint Adjustment 

Set-point range see rating plate 

1.  Start-up of system, see section 

.

2.  Set flow rate at the fitting 

 after the 

pressure reducer 

,to about 50 % of max. 

flow rate 

3.  Adjustment of the pressure behind the valve 

•  Observe pressure indica tors.
•  Turning to the right 

 increases the  set-

point (stressing the spring)

•  Turning to the left 

 redu ces the  

set-point (un-stressing the spring)

4.  The set-point adjuster 

 may be sealed.

5.  Release the not yet used pointer 

, move it 

to the set position and fix it with the screw

Dimensions 

Flanges: connection dimensi ons acc. to    
 

DIN 2501, seal form C

Summary of Contents for AFD 2 VFG 221

Page 1: ...VFG 2 21 DN 15 250 VFG 22 221 DN 65 250 Operating Guide ENGLISH AFD 2 VFG 2 21 DN 15 250 VFG 22 221 DN 65 250 www danfoss com Page 7 This document is included in the scope of delivery The latest docum...

Page 2: ...Tmax 150 C VFG 22 221 VFG 2 21 DN 15 50 Tmax 150 C MAINTENANCE FREE 3 mm SW13 19 36 46 AF 2 DN 15 50 Tmax 150 C Bellows VFG2 VFG21 AFD 2 adapter 003G1780 Piston VFG22 VFG221 DN 65 250 Tmax 150 C AFD...

Page 3: ...Danfoss 2020 11 3 AQ3525315322en 010101 AFD 2 VFG 2 21 DN 15 250 VFG 22 221 DN 65 250 SW46 Max 100 120 Nm 30 turns Pull out Hold Fix Release for turn Turn till and AFD 2 VFG 22 221 DN 65 250...

Page 4: ...AQ3525315322en 010101 4 Danfoss 2020 11 AFD 2 VFG 2 21 DN 15 250 VFG 22 221 DN 65 250 T 120 C T 120 C T 150 C SW 19 40 Nm SW 13 SW 19 40 Nm 30 Turns 30 Turns AFD 2 VFG 22 221 DN 65 250 G 1 4 AF...

Page 5: ...DN 15 250 VFG 22 221 DN 65 250 p 1 3 bar Type AFP 2 Code Nr 003G5650 p 1 3 bar Tmax 150 C Area cm2 80 Turn till end Hold Fix Release for turn Pull out SW46 Max 100 120 Nm 30 turns EN GJL 250 GG 25 PN...

Page 6: ...41 H 267 267 304 304 323 323 Size A HA Weight cm2 mm kg 32 175 485 8 5 80 175 485 8 5 160 228 505 12 320 295 505 20 5 630 300 630 36 Total installation height of the controller VFG 22 1 valve AFD 2 pr...

Page 7: ...connected directly to the valve or to the pipeline ventilation socket do not connect impulse tube Connection to the valve 1 Remove plug at the valve 2 Screw in threaded joint G 1 4 with copper seal T...

Page 8: ...73695620 AQ3525315322en 010101 8 Danfoss DHS SDBT SI 2020 11 AFD 2 VFG 2 21 DN 15 250 VFG 22 221 DN 65 250...