Data sheet
AB-PM DN 40-100
6 | VD.HR.D1.02
© Danfoss | 2018.01
Fig. 6
Fig. 5
DN 40
Flow limitation on Δp factory setting
Factory
setting
∆p setting [kPa]
Δp
r
[kPa]
40%
50%
60%
70%
80%
90%
100%
/0 turns
5 turns 10 turns 15 turns 20 turns
Q [l/h]
10
4600
5520
6348
7084
7728
8280
9200
15
4000
4800
5520
6160
6720
7200
8000
20
3300
3960
4554
5082
5544
5940
6600
9200
25
2500
3000
3450
3850
4200
4500
5000
8000
10200
30
2070
2310
2520
2700
3000
6600
9200
11100
35
5000
8000
10200
11900
40
3000
6600
9200
11100
45
5000
8000
10200
50
3150
6600
9200
55
5000
8000
60
3150
6600
Table 1
Example 1
Given :
Design flow to zone
4200 l/h, pressure drop over
the zone at design flow 25 kPa.
Solution:
AB-PM DN 40 is
selected. Δp setting is kept
at factory setting and flow
limitation is changed to 80 %.
AB-PM will control differential
pressure of 25 kPa when
design flow is achieved and
the flow to the zone will be
limited to 4200 l/h
2000
3000
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
10
15
20
25
30
35
40
45
50
55
60
Q
[l/h
]
∆p
r
[kPa]
Example 1
40 %
50 %
60 %
70 %
80 %
90 %
100 %
5 turns
10 turns
15 turns
20 turns
0
5000
10000
15000
20000
25000
30000
35000
40000
45000
50000
55000
10
15
20
25
30
35
40
45
50
55
60
FL
OW
[L
/H
]
ΔP
r
[kPa ]
DN 100
DN 80
DN 65
DN 50
DN 40
AB-PM HP DN 10-32
1)
1)
See datasheet AB-PM
DN 10-32
DN 40
Sizing
Sizing graph - ΔP/ max. flow