Data sheet 

AB-PM DN 40-100

AB-PM DN 40-100 is a combined differential pressure controller for dynamic hydronic balance.

•  The valve should be able to ensure hydronic balance for each zone with one or more terminal units.

•  Valve shall have flexible functionality as either DPCV or PIBCV.

•  The valve can be connected to either flow or return pipe via impulse tube

•  With impulse tube connected to flow, the valve should keep differential pressure across the 

branch by membrane driven controller. 

•  With impulse tube connected to the return, the valve should control the flow on every terminal unit

•  Valve should have shut-off function. 

•  Valve should have possibility to mount actuator without effecting presetting.

•  Valve should have variable setting. Setting value should allow to set a combination of needed 

differential pressure and flow for zone. 

•  Setting should be lockable to prevent unauthorized change. 

•  Control valve should have metal to metal sealing to ensure sufficient performance of differential 

pressure control at low flows. 

•  Shut-off service function should be possible to do with hand or a tool. The Dp controller should 

have soft sealing to ensure suficient closing in case of zero flow

•  Valve should be delivered with min. 2.5 m impulse tube. Diameter of impulse tube should not be 

bigger than 1.2 mm. 

•  Valve should be delivered in reliable packaging for safe transport and handling.

Product characteristics:

a) Pressure class: PN16

b) Max. pressure drop across AB-PM: 4 bar

c) Temperature range: –10 … 120 °C

d) Connections size: DN 40-100

e) Connection type: External tread ISO 228/1 (DN 40, DN50 ), Flange EN1092-2 (DN 65-100)

f) Installation: in return pipe with connection via impulse tube to flow or return pipe

g) Setting range: Flow: 40-100%, Δp setting : 0-20 turns (DN40, DN50), 0-40 turns (DN65-DN100)

h) Nom. flow at  factory setting (Δpr 25 kPa): 5000l/h (DN40), 6500 l/h (DN50), 16800 l/h (DN65), 

19600 (DN80), 21000 (DN100)

i)  Minimum differential pressure across valve and zone at factory setting 45 kPa (DN40, DN50), 

60 kPa (DN65-100)

Tender text

Summary of Contents for AB-PM DN 40

Page 1: ...oor designed executed user installations Unoccupied zones do not impact other users Flow verification and easy troubleshooting Description Ordering AB PM valve including 2 5 m impulse tube G 1 16 A br...

Page 2: ...pr 25 kPa l h 5000 6500 16800 19600 21000 Min differential pressure pa Factory setting 1 kPa 42 60 Setting range 2 3 Flow 40 100 p setting 0 20 turns 0 40 turns Nominal maximal pressure bar 16 PN16 Ma...

Page 3: ...with adapter 003Z0691 In that case the AB PM will function as a pressure independent control valve with 100 authority 1 For information on partner valve see ASV and MSV F2 datasheet Service and troub...

Page 4: ...lation of backbone piping without terminal units AB PM is used as DPCV with flow limitation ensuring the specified design pressure and flow to each zone The 2nd stage is then the installation of termi...

Page 5: ...ross the control valve Pcv p1 p2 To calculate the flow below formulas are used DPCV pr p0 p1 Q kvcv pr PIBCV pCv P1 P2 Q kvcv pcv For kvcv values see datasheet AB QM flow checker DN 40 250 For trouble...

Page 6: ...1 Example 1 Given Design flow to zone 4200 l h pressure drop over the zone at design flow 25 kPa Solution AB PM DN 40 is selected p setting is kept at factory setting and flow limitation is changed t...

Page 7: ...1400 14155 45 6305 9880 12825 50 3977 8075 11400 55 6175 9880 60 3895 8075 Table 2 Fig 8 DN 65 Flow limitation on p factory setting Factory setting p setting kPa pr kPa 40 50 60 70 80 90 100 0 turns 1...

Page 8: ...0 40600 48000 40 14000 27000 36600 44400 45 21000 32200 40600 50 14000 27000 36600 55 21000 32200 60 14000 27000 Table 5 Sizing Fig 9 DN 80 Flow limitation on p factory setting Factory setting p setti...

Page 9: ...increases the setting turning it counter clockwise reduces the setting If the setting is not known turn the spindle fully clockwise With this the setting on AB PM is at maximum value within setting ra...

Page 10: ...ing it full authority Higher pressure acts on the lower side of the control membrane 3 via an impulse tube 12 while the lower pressure in the return pipe acts on the upper side of the membrane use eit...

Page 11: ...AME 435 QM Dimensions Type L1 H1 H2 H3 a EN 1092 2 Weight kg mm DN 65 290 218 388 330 185 41 DN 80 310 223 393 335 200 46 DN 100 350 239 451 350 220 64 H 1 L1 b H 2 AB PM DN 40 50 H 3 AB PM AME 435 QM...

Page 12: ...have possibility to mount actuator without effecting presetting Valve should have variable setting Setting value should allow to set a combination of needed differential pressure and flow for zone Set...

Reviews: