Danfoss AB-PM DN 40 Datasheet Download Page 5

Data sheet 

AB-PM DN 40-100

VD.HR.D1.02 | 5

© Danfoss | 2018.01

Δp

v

Δp

r

=P

0

-P

1

Δp

a

=P

0

-P

3

003L8151  

Flow verification /trouble 

shooting

To verify that an installation functions per the 

design specifications the AB-PM (DN 40-100) has 

test plugs that allow measuring of the pressure 

difference Δp

r

 or Δp

cv

 across the valve.  In this 

way the pressure difference and flow can be 

verified for handover or troubleshooting.
At handover of the base building when the HVAC 

design conditions are specified but components 

are not yet installed in the zone, the differential 

pressure and flow for the valve and loop can 

only be verified by installing a bypass with the 

same dp as specified for the zone. For quick hand 

over, without flow verification, the calculated dp 

can be pre-set on the valve for the dp and flow 

demand of the loop.
In the 2

nd

 stage of commissioning when the 

HVAC system has been installed in the zone, the 

differential pressure and flow can be verified for 

handover and troubleshooting. 
The differential pressure can be measured using 

the following methods:

DPCV: Measure differential pressure from AB-PM 

to installed partner valve (Δp

r

  =p

0

 − p

1

).   

PIBCV: Measure the differential pressure across 

the control valve (ΔP

cv

  =p

1

 − p

2

).

To calculate the flow below formulas are used:
DPCV:

Δp

r

=p

0

 − p

1

Q=kv

cv

 × √∆p

r

PIBCV:

Δp

Cv

=P

1

 − P

2

Q=kv

cv

 × √∆p

cv

 

For kv

cv

 values see datasheet “AB-QM flow 

checker DN 40-250”
For trouble shooting the available pressure can 

be verified, Closing the AB-PM valve fully and 

measuring p

0

 – p

2

.

Verifying the pressure and flow can be done 

by using Danfoss PFM or other dp measuring 

devices (select valve type: AB-QM)

Q = needed design flow for the loop 
Δp

r

 = needed differential pressure for the loop 

Δp

v

 = differential pressure on AB-PM

Δp

a

 = min. needed differential pressure over  

   

both AB-PM and loop  

Δp

a

 = Δp

v

 + Δp

r

Δp

V

 = 

p

1

 − p

3

 

Δp

r

 = 

p

0

 − p

1

 (as DPCV) 

Δp

cv

 = 

p

1

 − p

2

 (as PIBCV for flow validation)

  

Δp

a

 = p

0

 − p

3

P

1

-P

3

P

1

-P

2

P

0

-P

1

P

0

P

2

P

3

P

1

Flow 

direction

Differential pressure legend

Sizing

AB-PM is to be sized based on the needed flow 

(Q) and the needed differential pressure drop for 

the zone (∆p

r

). 

Max flow /Δp

r

 for all sizes are presented in the 

sizing guide in fig. 5.

When pipe dimension has been selected, specific 

sizing, selection and setting can be identified 

based on Q and Δp

r

  in fig. 6-10.

Alternatively table 1-5 can be used for AB-PM 

sizing as well.

For needed flow and differential pressure 

outside specified in graphs and tables, setting 

can be calculated by linear distribution of 

setting.

For minimum needed available differential 

pressure (Δp

a

 ) at Q nominal see table 6.

Fig. 4 Differential pressure legend

Summary of Contents for AB-PM DN 40

Page 1: ...oor designed executed user installations Unoccupied zones do not impact other users Flow verification and easy troubleshooting Description Ordering AB PM valve including 2 5 m impulse tube G 1 16 A br...

Page 2: ...pr 25 kPa l h 5000 6500 16800 19600 21000 Min differential pressure pa Factory setting 1 kPa 42 60 Setting range 2 3 Flow 40 100 p setting 0 20 turns 0 40 turns Nominal maximal pressure bar 16 PN16 Ma...

Page 3: ...with adapter 003Z0691 In that case the AB PM will function as a pressure independent control valve with 100 authority 1 For information on partner valve see ASV and MSV F2 datasheet Service and troub...

Page 4: ...lation of backbone piping without terminal units AB PM is used as DPCV with flow limitation ensuring the specified design pressure and flow to each zone The 2nd stage is then the installation of termi...

Page 5: ...ross the control valve Pcv p1 p2 To calculate the flow below formulas are used DPCV pr p0 p1 Q kvcv pr PIBCV pCv P1 P2 Q kvcv pcv For kvcv values see datasheet AB QM flow checker DN 40 250 For trouble...

Page 6: ...1 Example 1 Given Design flow to zone 4200 l h pressure drop over the zone at design flow 25 kPa Solution AB PM DN 40 is selected p setting is kept at factory setting and flow limitation is changed t...

Page 7: ...1400 14155 45 6305 9880 12825 50 3977 8075 11400 55 6175 9880 60 3895 8075 Table 2 Fig 8 DN 65 Flow limitation on p factory setting Factory setting p setting kPa pr kPa 40 50 60 70 80 90 100 0 turns 1...

Page 8: ...0 40600 48000 40 14000 27000 36600 44400 45 21000 32200 40600 50 14000 27000 36600 55 21000 32200 60 14000 27000 Table 5 Sizing Fig 9 DN 80 Flow limitation on p factory setting Factory setting p setti...

Page 9: ...increases the setting turning it counter clockwise reduces the setting If the setting is not known turn the spindle fully clockwise With this the setting on AB PM is at maximum value within setting ra...

Page 10: ...ing it full authority Higher pressure acts on the lower side of the control membrane 3 via an impulse tube 12 while the lower pressure in the return pipe acts on the upper side of the membrane use eit...

Page 11: ...AME 435 QM Dimensions Type L1 H1 H2 H3 a EN 1092 2 Weight kg mm DN 65 290 218 388 330 185 41 DN 80 310 223 393 335 200 46 DN 100 350 239 451 350 220 64 H 1 L1 b H 2 AB PM DN 40 50 H 3 AB PM AME 435 QM...

Page 12: ...have possibility to mount actuator without effecting presetting Valve should have variable setting Setting value should allow to set a combination of needed differential pressure and flow for zone Set...

Reviews: