Installation Guide

Danfoss District Energy 

VI.GP.R1.51 

DKDHR

English - GB 

If the household plumbing system includes hot water recirculation the water heater must be connected to the hot water recirculation 

system by using this circulation set. 

It is to be recommended to prepare the water heater for recirculation BEFORE mounting it on the wall.

The recirculation pipe in your household plumbing system must be connected to a nipple, mounted on the circulation pipe of the water 

heater. - 

See pages 2 to 5 for information about preparation of water heater for and connection to the DHW recirculation system.

Remember always to mount circulation pump and non-return valve on the circulation pipe and to mount safety valve on the DCW 

inlet. The pump must be installed so that the pump is pumping water towards the water heater.

If a time-controlled pump is used, it is to be recommended that the circulation water temperature is set to approx. 35 °C.

If the circulation pump (outside the water heater) is switched off for a longer period, it is to be recommended that the Danfoss bypass  

thermostat is closed during the same period. 

NOTE!

Please note that water heaters with Danfoss AVE expanion unit must not be used on systems with DHW recirculation.

Circulation set for water heaters
Cirkulationssæt for vandvarmere
Zirkulationsset für Warmwasserbereiter

Danish - DK 

Hvis der er cirkulation på anlægget skal der etableres cirkulationskobling på vandvarmeren ved hjælp af dette cirkulationssæt

.

 

Det anbefales at etablere cirkulation INDEN vandvarmeren hænges op på væggen.

Cirkulationsledningen fra den faste installation tilsluttes på brystniplen nederst i unitten. - 

Se hvordan man cirkulationskobler vandvar-

meren på side 2 til 5.

Der skal altid monteres pumpe og kontraventil på cirkulationsrøret med flowretning ind mod vandvarmeren.

Hvis der anvendes urstyret pumpe, anbefales det, at cirkulationsvandtemperaturen indstilles til ca. 35 °C.

Bemærk, hvis cirkulationspumpen (udenfor unitten) stoppes længerevarende, anbefales det, at by-pass termostaten lukkes i samme tidsrum. 

NB!

Vær opmærksom på, at vandvarmere udstyret med Danfoss AVE trykudligner ikke må bruges på anlæg med cirkulation.

German - DE 

Wenn eine Zirkulationsleitung in der Hausinstallation vorhanden ist, ist die Warmwasserbereiter an die Zirkulationsleitung anzuschließen, 

und eine Umrüstung von Bypassbetrieb auf TWW-Zirkulation ist mittels dieses Zirkulationssatzes vorzunehmen. 

Es wird empfohlen die Warmwasserbereiter für TWW-Zirkulation VOR der Montage auf der Wand vorzubereiten

Die Zirkulationsleitung der Hausinstallation ist an einen Messing-Nippel, den auf dem Zirkulationsschlauch des Warmwasserbereiters 

montieret ist, anzuschliessen. - Siehe Seiten 2-5 für weitere Informationen über Zirkulationsanschluss.

Bitte einbau von Umwälzpumpe und Rückschlagventil in der Zirkulationsleitung beachten, und Sicherheitsventil in der Kaltwas-

serzuleitung einzubauen.  Die Fleißrichtung der Pumpe ist in Richtung Warmwasserbereiter.

Wird die Umwälzpumpe über eine Schaltuhr gesteuert, empfehlen wir, dass die Zirkulationswassertemperatur auf ungefähr. 35 °C eingestellt 

wird.

Wenn die Umwälzpumpe (außerhalb der Warmwasserbereiter) für einen längeren Zeitraum abgeschaltet wird, wird es empfohlen, dass der 

Danfoss Bypass Thermostat im gleichen Zeitraum geschlossen wird.

BITTE BEMERKEN!

Der AVE Druckausgleichventil ist nicht auf Systemen mit TWW-Zirkulation zu verwenden.

Div.734 

    Code 

No. 

004U8442

Summary of Contents for 004U8442

Page 1: ...sluttes på brystniplen nederst i unitten Se hvordan man cirkulationskobler vandvar meren på side 2 til 5 Der skal altid monteres pumpe og kontraventil på cirkulationsrøret med flowretning ind mod vandvarmeren Hvis der anvendes urstyret pumpe anbefales det at cirkulationsvandtemperaturen indstilles til ca 35 C Bemærk hvis cirkulationspumpen udenfor unitten stoppes længerevarende anbefales det at by...

Page 2: ... Fig 4 GB Unscrew the 3 screws on locking rail DK Løsn de 3 skruer på låseskinnen DE Die 3 Schrauben der Verschlussschiene abschrauben Fig 5 GB Demount locking rail DK Afmontér låseskinnen DE Die Verschlussschiene abmontieren Fig 6 GB Demount support rail as shown DK Afmontér fikseringsskinnen som vist DE Die Festhalteschiene wie gezeigt herausnehmen Fig 7 GB Place bracket C on support rail as sho...

Page 3: ...ngle end wrench DK Montér nyt kapillarrør G på nippelmuffe A ved hjælp af omløber og skærering H Fastspænd med skruenøgle DE Neues Kapillarrohr G in Messingnippel A mittels Überwurfmutter und Schneidring H einbauen Mit Schraubenschlüssel festspannen Fig 15 UK Fit the other end of the capillary tube G on bypass thermostat by means of union nut and cutting ring H Tighten with single end wrench DK Mo...

Page 4: ...er einbauen Fig 4 GB Prepare bracket C for mounting on mounting plate by making a 90 degree bend on one end using a pair of pliers This applies only to Akva Vita II and Akva Les For Akva Lux II GW it is not necessary to bend the bracket before mounting it on the mounting plate DK Forbered beslag C for montage på bagpladen ved at bukke beslaget 90 grader i den ene ende Dette gælder kun for Akva Vit...

Page 5: ...fra by pass termostaten DE Das Kapillarrohr vom Bypass Thermostat abbauen Fig 10 GB Mount M8 x 1 screw plug F in the brass angle piece DK Afprop med M8 x 1 konisk prop F i messingvinklen DE M8 x 1Propfen F in Winkelstück einbauen Fig 11 GB Fit new capillary tube G on nipple A by means of union nut and cutting ring H Tighten with single end wrench DK Montér nyt kapillarrør G på nippelmuffe A ved hj...

Page 6: ...rkulationswassers wird unabhängig von dem eingestellten Warmwassertemperatur einreguliert Es wird emp fohlen den Thermostat auf max Pos 3 einzustellen GB This picture shows the Akva Les II water heater ready mounted with circulation set and ready for connection to the recirculation system of the household piping DK Dette foto viser en Akva Lux II vandvarmer med cirkulationssæt fær digmonteret og k...

Page 7: ...n Warmwassertemperatur einreguliert Es wird emp fohlen den Thermostat auf max Pos 3 einzustellen GB This picture shows the Akva Lux II GW water heater ready mounted with circulation set and ready for connection to the recirculation system of the household piping DK Dette foto viser en Akva Lux II GW vandvarmer med cirkulationssæt fær digmonteret og klar til tilslutning på varmtvandsanlæg med brugs...

Page 8: ...VI GP R1 51 Produced by Danfoss Redan A S 11 2012 ...