Analogue Output Test
Navigation :
Service menu
→
Tests menu
→
Analog output test
This test allows the user to arbitrarily set a signal set point for the analogue output of the
device. This allows the user, for example, to verify the connections and ensure that the
receiver connected to this output is compatible with the unit.
The user can modify the simulated set point value using the
Up
and
Down
arrow keys.
The user can move from one digit to the next using the
Right
and
Left
arrow keys.
The user can end the simulation by pressing
ESC
.
Switching to the Battery
Navigation :
Service menu
→
Tests menu
→
Switch to battery
This test forces the U•V6 unit to switch to battery power, as if there were a mains power
outage.
The user can activate this function by pressing the
ENTER
key. The system then asks for
confirmation before switching the power source.
Switch to battery
Switch to battery ?
The user can confirm their request to switch power sources by pressing
ENTER
.
Switch to battery
Switched to battery
The U•V6 unit then reacts as if it were powered by the battery only:
Alarm management operates as per usual during a simulation. This means that, if the
simulated gas concentration exceeds an alarm threshold, the alarm is triggered and the
associated outputs are activated, along with the servos connected to them.
The signal that is actually produced at the device output depends on the interface
configuration chosen (0-20mA, 4-20mA, or 0-10 V). See Paragraph