WARNINGS  

 
 

 

 

BEFORE the installation, maintenance or repair of the detector, check that there 
is  no  explosive  gas  or  explosive  vapour  in  the  atmosphere.  Never  open  the 
detector  when  an  explosion  risk  is  present.  To  reduce  the  risk  of  electrostatic 
discharge, always use a damp cloth to clean the detector. 

  

 

 

The INSTALLATION, COMMISSIONNING and MAINTENANCE must be performed 
exclusively by DALEMANS or by an approved service centre and in all cases by 
qualified  personnel  having  received  appropriate  training.  The  gas  detection 
equipment must be calibrated at least once a year to compensate for any loss of 
sensitivity of the sensors. 

 

The guarantee offered by DALEMANS will be void if this equipment is not installed, used and 
maintained in strict compliance with these instructions, warnings and limits of use.  

 

By following these instructions, you guarantee the proper functioning of the equipment. Please 
contact  DALEMANS  for  any  information  on  the  installation,  use  or  maintenance  of  this 
equipment.  

 

Always follow the following instructions to prevent premature wear to the sensor and guarantee 
its proper functioning. These recommendations are general guidelines.  

 

Always refer to current regulations and standards before proceeding with the installation (e.g. 
standards IEC 60079-14 and IEC 60079-29-2). These take pre

cedence over the manufacturer’s 

recommendations.  

 

Maintenance must be carried out according to the procedures given by DALEMANS or its local 
representative. Any repair  or maintenance performed without respecting these instructions or 
without  help  from  DALEMANS  may  prevent  the  equipment  from  working  correctly  and,  as  a 
result, prevent guaranteeing the safety of the occupants of the installations being monitored.  

 

The  modification,  disassembly  and  total  or  partial  destruction  of  this  equipment  may  lead  to 
invalidity of the essential safety requirements of the installations as a whole.  

 

Only  use  original  DALEMANS  spare  parts.  Using  unoriginal  spare  parts  may  invalidate  the 
certification and the guarantee covering this equipment.  

  

LIMITATIONS  

 

The sensors may be sensitive to several gases. Consult DALEMANS for more information.  

 

The catalytic sensors can lose sensitivity in the presence of inhibitors and pollutants such as 
silicone,  halogen  and  heavy  metals.  When  these  inhibitors  are  permanently  present, 
DALEMANS recommends the use of gas detectors equipped with infra-red sensors immune to 
these pollutants and inhibitors.  

 

The catalytic sensors are not suitable for use in atmospheres with variable oxygen levels, at 
over  21%  oxygen  or  less  than  15%  oxygen.  Prolonged  exposure  to  explosive  gas 
concentrations greater than 100% of the Lower Explosive Limit (LEL) may significantly reduce 
its useful life.  

 

During  construction,  repackaging  or  maintenance  works  concerning  the  installations,  gas 
detectors must be installed as late as possible but nevertheless before any risk of the presence 
of gas or gas vapours. This is to avoid any damage to the sensor resulting from works such as 
welding or painting. If they are already installed, the detectors must be protected using a sealed 
cover for the duration of the work and be clearly marked as being non-operational.  

 

The  gas  detectors  must  be  protected  against  any  direct  exposure  to  solar  rays,  against 
vibrations and risks of mechanical impacts. 

 

 

  

EX 

Summary of Contents for D-TEX3F+

Page 1: ......

Page 2: ...hibited Warning All information contained in this document is non contractual and subject to change without notice We also encourage you to regularly check the availability of a new version on our web...

Page 3: ...ALITY ASSURANCE 7 1 INTRODUCTION 8 1 1 Certification 8 2 DESCRIPTION 9 2 1 Overview 9 2 2 Dimensions 10 3 INSTALLATION 11 3 1 Positioning of the detectors 11 3 2 Assembly 12 3 3 Wiring 13 3 4 Electric...

Page 4: ...without help from DALEMANS may prevent the equipment from working correctly and as a result prevent guaranteeing the safety of the occupants of the installations being monitored The modification disa...

Page 5: ...e gases are typically 20 LEL for the first alarm level A1 and 40 LEL for the second level A2 The choice of alarm levels must consider the possible effects of local climatic conditions Temperature The...

Page 6: ...h a normal degree of safety 2 Gas groups Group Reference gas Definition I Methane Equipment intended for mines on the surface or under the surface IIA Propane Equipment intended for surface industries...

Page 7: ...cerning the collection and recycling of Waste Electrical and Electronic Waste WEEE These provisions aim to preserve the natural resources used to produce this product and to avoid the dispersal of sub...

Page 8: ...nce of this marking label the detector is not certified for use in danger zones Figure 1 identification and certification label Compliance Definition see Directive 2034 14 EU for more information II E...

Page 9: ...astic flame retardant box a certified cable gland a detection head with a flameproof enclosure and a connection terminal mounted on a circuit board The detection head and the D BASE 3F card are design...

Page 10: ...www dalemans com 10 2 2 Dimensions Figure 3 D TEX3F dimensions in mm D TEX3F...

Page 11: ...sources must be considered Consider possible combinations of gas sources and dissemination effects The detector must be protected against risks related to the operation of the installations The detec...

Page 12: ...rews and pins Make sure that dust deposits do not obstruct the sensor and that water does not enter the detector The D TEX3F may be mounted horizontally or vertically For vertical assembly the box s c...

Page 13: ...requirements of the D TEX3F detector are compatible with the characteristics of the measurement panel see Specifications Connections to the D TEX3F detector are via the 24V GND OUT terminal present o...

Page 14: ...s of sensitivity of the sensors This calibration must be carried out according to the procedure given by DALEMANS or by its local representative and in any case by qualified personnel having received...

Page 15: ...ilter Fault signal active on the panel Wiring or connection defective Sensor disconnected or defective Voltage in the detector between the 24V and GND terminals outside of limits 4 3 Spare parts and a...

Page 16: ...rent 18 mA 2 Secured 12V Box Material Flame retardant and UV stable plastic UL 94V0 Dimensions H xW x D 147 x 119 x 51 mm Weight 285 g IP protection index IP 65 Reversibility YES Standard fixing 4 scr...

Page 17: ...www dalemans com 17 Notes...

Page 18: ......

Reviews: