TECHNICAL NOTE 

INSTALLATION 

 

CAUTION: The product may only be connected and installed by a qualified electrician. All applicable regulations, legislation, and 
building  codes  must  be  observed.  Incorrect  installation  of  the  product  can  cause  irreparable  damage  to  the  product  and  the 
connected LEDs.  

 

Maintenance must be performed only by a qualified electrician in compliance with current regulations. 
Pay attention when connecting the LEDs: polarity reversal results in no light output and often damages the LEDs. 

 

The  product  is  designed  and  intended  to  operate  LED  loads  only.  Powering  non-LED  loads  may  push  the  product  outside  its 
specified design limits and is, therefore, not covered by any warranty. 
Operating conditions of the product may never exceed the specifications as per the product datasheet. 

 

The product must be installed inside a switchgear/controlgear cabinet and/or junction box protection against overvoltage. 

 

The  product  must  be  installed  in  a  vertical  or  horizontal  position  with  the  label/top  cover  facing  upwards  or  vertically.  Other 
positions are not permitted. The bottom position is not permitted (label/top cover facing down). 

 

Keep separated 230Vac (LV) circuits and not SELV circuit from safety extra low voltage (SELV) circuit and from any connection 
with this product. It is absolutely forbitten to connect, for any reason whatsoever, directly or indirectly, the 230Vac mains voltage 
to the product (terminal block of BUS included). 

 

The product must be dissipated correctly. 

 

The use of the product in harsh environments could limit the output power. 

 

For  built-in  components  inside  luminaires,  the  ta  ambient  temperature  range  is  a  guideline  given  for  the  optimum  operating 
environment. However, integrator must always ensure proper thermal management (i.e. correct mounting of the device, air flow 
etc.) so that the tc point temperature does not exceed the tc maximum limit in any circumstance. Reliable operation and lifetime 
is only guaranteed if the maximum tc point temperature is not exceeded under the conditions of use. 

 

POWER SUPPLY 

 

Only  use  SELV  power  supplies  with  limited  current  for  device  power  supply,  short  circuit  protection  and  the  power  must  be 
dimensioned correctly. 
In the case of power supplies equipped with ground terminals, it is mandatory to connect ALL protective ground points (PE= 
Protection Earth) to a properly and certified protection earth. 

 

The connection cables between the very low voltage power source and the product must be properly dimensioned and must be 
insulated from any wiring or part at non-SELV voltage. Use double insulated cables. 

 

Dimension the power of the power supply in relation to the load connected to the device. In case the power supply is oversized 
compared to the maximum absorbed current, insert a protection against over-current between the power supply and the device. 

 

COMMAND 

 

The length of the cables connecting between the local commands (N.O. Push button or other) and the product must be less than 
10m. The cables must be properly dimensioned and must be insulated from any non-SELV wiring or voltage. It is recommended 
to use double insulated cables, if deemed appropriate also shielded. 

 

ALL  device  and  control  signal  connected  to  the  local  command  “N.O.  Push  button”  with 

symbol, they must not supply 

any type of voltage. 

 

OUTPUTS 

 

It is recommended a length of the connecting cables between the product and the LED module less than 10m. The cables must 
be properly dimensioned and must be insulated from any wiring or circuits at voltage not SELV. It is recommended to use double 
insulated cables. In case you want to use connecting cables between the product and the LED module greater than 10m, the 
installer  must  guarantee  the  correct  operation  of the  system.  In  any  case,  the  connection  between  the  product  and the  LED 
module must not exceed 30m. 

 

ONLY CASAMBI/BLUETTOTH PRODUCT 

 

WARNING: For optimal functionality of the Casambi signal, do not put the device into metal or aluminium boxes and do not shield 
the device. As any other Casambi product, should not be placed in a metal enclosure or next to large metal structures. Metal will 
effectively block all radio signals which are crucial to the operation of the product. 

WARNINGS 

 

To  guarantee the  best  performances  and the  full use  of functions,  make sure  to download  on  your  device the  last  release of 
CASAMBI APP. 

 

Whenever CASAMBI APP requires an upgrade of the profile installed in the LED Dimmers, follow the instruction to do it. This allows 
you to stay always up to date and benefit of new functions released. 

 

Functionality test are done on all dimmers to ensure the 

right working. In case the device is still paired to “Dalcnet network”, you 

are asked to unpair it by following the instructions on CASAMBI APP and in paragrap

“UNPAIR DEVICE FROM THE CASAMBI 

NETWORK”.

 

Summary of Contents for CBU-DALI-GATEWAY

Page 1: ...ceives the command signal from the Casambi APP and depending on the fixture set sends the signal in a predetermined sequence of DALI addresses See pag 7 for the DALI Addresses map With the CBU DALI GATEWAY profile the device receives commands from an external DALI Master and sends control signals to the Casambi lamps of the network to which it is associated Each Casambi lamp has a DALI address In ...

Page 2: ...s WWWW AUTOMATIC 25139 Fixture for checking 4 DALI addresses TW AUTOMATIC 2700 6000K 25140 Mixer hot cold color with two channels RGB AUTOMATIC 25141 Fixture RGB DT6 RGB W AUTOMATIC 25142 Fixture RGBW DT6 RGB TW AUTOMATIC 25137 Fixture RGB Tunable White DT6 WWWW GROUP 25138 Fixture for control of 4 DALI groups 8XW GROUP 25291 Fixture for control of 8 DALI groups DALI DT8 BC RGB 11121 Fixture RGB D...

Page 3: ... TECHNICAL SPECIFICATIONS CBU DALI GATEWAY Supply voltage min 10 8 Vdc max 52 8 Vdc Nominal Power4 Min Max 12V 61 mW 115 mW 24V 120 mW 176 mW 48V 230 mW 296 mW Power loss in standby mode 500mW Operating frequency5 2402 2480 MHz Maximum output power5 7dBm Storage temperature min 40 max 60 C Ambient temperature4 min 10 max 40 C IP protection class IP10 Wiring 2 5mm 2 solid 2 5mm2 stranded 30 12 AWG ...

Page 4: ...e symbol Be sure not to connect live parts to the INPUT terminals Connect the constant voltage SELV power supply to the DC IN terminal with the and symbols Make sure you are not using a power supply with a constant current output and check that the polarity of the cables is correct Connect the DALI BUS on the DALI OUT terminals Like any other product with Bluetooth control be sure not to place the...

Page 5: ...ld to adjust luminaire brightness Controls an element Click Long press 1s Tap to turn a device element on or off hold to adjust the element value Control a group Click Long press 1s Tap to turn a group on or off hold to adjust brightness For all other functions consult the CASAMBI APP documentation at https support casambi com support home UNPAIRING THE DEVICE FROM THE CASAMBI NETWORK If the devic...

Page 6: ...AY Device Manual Made in Italy DALCNET S r l 36077 Altavilla Vicentina VI Italy Via Lake Garda 22 Tel 39 0444 1836680 www dalcnet com info dalcnet com REv 25 01 2023 Pag 6 11 MECHANICAL DIMENSIONS Excluding terminals ...

Page 7: ...TIC fixtures of the CBU DALI GATEWAY automatically direct the UNADDRESSED devices connected to the DALI BUS CBU DALI GATEWAY Casambi Slider None The device appears in the Gateway section of the Casambi app DALI2 BROADCAST Casambi Slider Dimmer 0 Address Command BROADCAST Dimmer ALL W AUTOMATIC Casambi Slider Dimmer 0 Address Command A0 Dimmer 0 WWWW AUTOMATIC Casambi Slider Dimmer 0 Dimmer 1 Dimme...

Page 8: ...ture Address Command A0 Warm white A1 Cold white RGB AUTOMATIC Casambi Slider Dimmer Color Saturation Map Address Command A0 R Red A1 G Green A2 B Blue RGBW AUTOMATIC Casambi Slider Dimmer White Color Color Saturation Map Address Command A0 R Red A1 G Green A2 B Blue A3 W White RGB TW AUTOMATIC Casambi Slider Dimmer Color temperature White Color Color Saturation Map Address Command A0 R Red A1 G G...

Page 9: ...I GATEWAY send group commands The DALI devices must be previously addressed and assigned to the desired group through an external DALI master WWWW GROUP Casambi Slider Group 0 Group 1 Group 2 Group 3 Address Command G0 Group 0 G1 Group 1 G2 Group 2 G3 Group 3 8W GROUP Casambi Slider Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Address Command G0 Group 0 G1 Group 1 G2 Group 2 G3 ...

Page 10: ... BC fixtures of the CBU DALI GATEWAY send broadcast commands to devices compliant withIEC 62386 209 Device Type 8 DALI DT8 BC TW Sliderr Casambi Dimmer Color temperature Address Command Broadcast DT8 Dimming CCT DALI DT8 BC RGB Casambi Slider Dimmer Color Saturation Map Address Command Broadcast DT8 Dimming RGB DALI DT8 BC RGBW Casambi Slider Dimmer White Color Color Saturation Map Address Command...

Page 11: ...n the case of power supplies equipped with ground terminals it is mandatory to connect ALL protective ground points PE Protection Earth to a properly and certified protection earth The connection cables between the very low voltage power source and the product must be properly dimensioned and must be insulated from any wiring or part at non SELV voltage Use double insulated cables Dimension the po...

Reviews: