Electrical Installation
4-2
Refer to the schematic drawings listed above and to the table in
to
determine circuit specifications and power requirements for individual displays.
Grounding
Reference Drawing:
Schematic; Gen III Outdoor LED,
16 Column Drvr.....................................................
Displays MUST be grounded according to the provisions outlined in Article 250 of
the National Electrical Code and according to the specifications in this manual.
Daktronics recommends a resistance-to-ground of 10 ohms or less.
The contractor performing the electrical installation can verify ground resistance.
Daktronics Sales and Service personnel can also provide this service.
The display system
must
be connected to an earth electrode installed at the display.
Proper grounding is necessary for reliable equipment operation. It also protects the
equipment from damaging electrical disturbances and lightning.
Note:
The display must be properly grounded, or the warranty will be void.
Refer to the schematic,
Drawing A-177931
,
for information on connecting the
grounding wire. The connection is illustrated in the "Pwr In" detail of the
Master
Configuration
portion of the schematic.
The material for an earth-ground electrode differs from region to region and may
vary according to conditions present at the site. Consult the National Electrical Code
and any local electrical codes that may apply. The support structure of the display
cannot be used as an earth-ground electrode. The support is generally embedded in
concrete, and if it is in earth, the steel is usually primed or it corrodes, making it a
poor ground in either case.
Power Installation
There are two considerations for power installation: installation with ground and
neutral conductors provided, and installation with only a neutral conductor provided.
These two power installations differ slightly, as described in the following
paragraphs:
Installation with Ground and Neutral Conductors Provided
For this type of installation, the power circuit
must
contain an isolated earth-ground
conductor. Under this circumstance,
do not
connect neutral to ground at the
disconnect or at the display.
Note:
Connecting the neutral to ground at the disconnect would violate electrical
codes and void the warranty.
Summary of Contents for TN-2011
Page 14: ......
Page 24: ......
Page 34: ......
Page 46: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ...Eyebolts B 1 Appendix B Eyebolts Eyebolts ED7244...
Page 88: ......
Page 91: ...Appendix C C 1 Appendix C Daktronics Warranty and Limitations of Liability...
Page 92: ......