background image

 

 

 

MAN# 650264:B

 

Operation 

The electric cooling fan controller provides a way to run up to two electric engine cooling fans or one two speed cooling 
fan. (A second relay, sold separately, is required for two speed or dual fan operation). The controller monitors the engine 
temperature using a dedicated sender, or a gauge and its sender. When the engine temperature goes above a user 
adjustable set point, the fan is turned on with a relay. When the engine has cooled below a user selectable off 
temperature, the fan is shut off. Separate on and off temperatures can be set for the high and low fan outputs. The 
controller will also run the fan when the air conditioner requires, by detecting when the air conditioning clutch is engaged. 

 

The unit can be set to keep the fan running (if the engine is hot enough) after the key is turned off. Several delay times are 
available from no delay to five minutes. The display will countdown the seconds left before the fan is turned off. If the 
battery voltage drops too low, the fan will be turned off and a “Lo bAt” message will display for the remainder of the time.  

 

Settings for several gauge systems are included to make installation with a gauge easier. The included gauges are 
Stewart Warner, Classic Instruments, VDO, and Autometer. If the gauge being used isn’t included, a custom calibration 
option allows the system to be calibrated to any gauge with clear numerical temp markings. This is accomplished by 
setting the controller to match the marks on the gauge with a few steps described in detail in the installation instructions.  

 

IMPORTANT NOTE!!!: If using a gauge with this unit, always ensure that your gauge is working properly. If the gauge is not reading 
correctly, the fan control unit will not have correct temperature information and cannot be guaranteed to properly control the fan, 
possibly leading to overheating and engine damage.   

If the gauge uses a two-wire temperature sender (such as Autometer full sweep) use of a dedicated Dakota Digital sender is 

required.   
 

If a gauge is not used, ONLY a Dakota Digital 300ºF sender should be used. Other senders may not give a correct reading to 

the control unit. 
 

Custom gauge calibration requires numerical marks, stock “C-NORMAL-H” type gauges cannot be accurately calibrated to. 

 

Required components for installation: 

The PAC-2700 is shipped with necessary components for use with a single fan on a gauged system. These parts include: 
 

PAC-2700 module 

 

RLY-3 relay with wiring harness 

 

Instruction manual 

For some options of the PAC-2700, additional components are required. These are listed below. 

- Second RLY-3 assembly (needed for dual fan or two speed fan operation) 
- 300ºF sender Dakota Digital temp sender (for operation without a gauge) 

 

Installation 
Note: Mount ONLY in vehicle cabin. Controller is not designed for engine compartment mounting. 

The terminal strip on this unit has 6 connections: 
1. Fan high relay  

Connect to the white wire on the high fan relay assembly 

 

 

 

 

(for single fan applications leave unconnected) 

2. Fan low relay  

Connect to the white wire on the low fan relay assembly 

3. Ground 

 

Connect to a good chassis ground 

4. Power 

 

Connect to a fused 12V battery  

5. Sender 

 

Connect to the engine temperature sender wire. 

6. A/C clutch 

 

Connect to the cycle switch on systems with air conditioning 

 

 

 

 

(on systems without air conditioning leave unconnected) 

7. Ignition 

 

Connect to a circuit which has +12V only with the ignition key ON. (switched power) 

 
Relay wiring: 
White   

 

Connect to control unit 

Green   

 

Connect to fused 12V battery circuit that can run cooling fan 

Red 

 

 

Connect to fused 12V battery 

Black   

 

Connect to cooling fan 

 

Factory Presets 

This controller comes preset to use a dedicated sender as follows: 
  

Dakota Digital Sender only (no gauge, see above for 300ºF sender options) 

 

One single speed fan 

 

205ºF on temperature 

 

200ºF off temperature  

 

30 sec Fan off delay 

 
If the factory settings don’t fit your application, you will need to go through the setup procedure on the following page. At 
anytime during the setup procedure, the key may be turned off and the settings up to that point will be saved. 

Summary of Contents for PAC-2700

Page 1: ... application 12V with key ON A C clutch cycle switch Fused battery 12V Choose option below SENDER GAUGE single fan two separate fans dual speed fan Fan High Fan High Fan Low Fan Low 12V NOT CONNECTED FAN Fan Low Fan High 12v trigger 12V Fan PWR 12V Fan PWR 12V IMPORTANT NOTE The 12V for the controller should NOT be taken from the same circuit as the Fan Power 12V as this can cause the fan to cycle...

Page 2: ...er full sweep use of a dedicated Dakota Digital sender is required If a gauge is not used ONLY a Dakota Digital 300ºF sender should be used Other senders may not give a correct reading to the control unit Custom gauge calibration requires numerical marks stock C NORMAL H type gauges cannot be accurately calibrated to Required components for installation The PAC 2700 is shipped with necessary compo...

Page 3: ...45 seconds after key is turned off If fan was running at key off it will continue to run for 1 minute after key is turned off If fan was running at key off it will continue to run for 2 minutes after key is turned off If fan was running at key off it will continue to run for 3 minutes after key is turned off If fan was running at key off it will continue to run for 5 minutes after key is turned of...

Page 4: ...will return the device to the original factory presets and clear custom calibration settings NOTE Calibration data for the custom gauge setup will be lost when reset to factory presets 1 Turn key off 2 Press and hold SW1 and SW2 and turn key on 3 Display will read for reset 4 Display will flash to indicate unit is reset Factory reset values are listed at the beginning of the setup portion of this ...

Page 5: ... Shorten fan delay time to prevent excessive battery drain Fan turns on late or not at all Unit has no power Broken shorted wire to sender Wrong gauge is selected gauge setup Wrong sender used for no gauge setup On temperature in setup is too high Fan not connected properly Alternator overcharging Analog gauge applications only With key on hold SW1 if the display doesn t show a temperature after a...

Page 6: ...ame and address street address preferred and a telephone number where you can be reached during the day Any returns for warranty work must include a copy of the dated sales receipt from your place of purchase Send no money We will bill you after repair Dakota Digital 24 Month Warranty DAKOTA DIGITAL warrants to the ORIGINAL PURCHASER of this product that should it under normal use and condition be...

Reviews: