SK2019 FCSD(H)-V/P-ECM-001
Sleep Mode
a)
The sleep mode can only be set when the unit is in cool mode or heat mode.
b)
If the sleep mode is activated when the unit is in cool mode, then the indoor fan will run at low speed and Ts will
increase by 2ºC over 2 hours.
c)
If the sleep mode is activated when the unit is in heat mode, then the indoor fan will run at set speed and Ts will
decrease by 2ºC over 2 hours.
d)
Changing the mode of operation will cancel the sleep mode.
The cool mode sleep profile is:
The heat mode sleep profile is:
Auto Fan Speed
COOL MODE
HEAT MODE
Fan speed cannot change until it has run for more than 30
seconds.
Fan speed is regulated according to the profile below.
Fan speed cannot change until it has run for more than 30
seconds.
Fan speed is regulated according to the profile below.
After 30 seconds the fan speed is modulated according to the difference between the room temperature and the set
temperature. The controller adjusts the motor signal input from 0 to 5VDC by PID calculation every 10 seconds. The air flow is
adjusted from 15% to100%.
Modulating Valve Control Under Energy Saving Mode
If the modulating valve is used, the water flow is adjusted from Modbus 310015 setting to 100% according to the room
temperature and set temperature. The controller adjusts the modulating valve signal input from Modbus 310015 setting to
10VDC by PID calculation every Modbus 310007 setting.
Louver
For remote handset.
Whenever the indoor fan is running, the louver can swing or stop at the desired position.
Louver angle: 0~100 º, opens clockwise with widest angle at 100 º.
Swing angle: 35~100 º, opens clockwise to 68º. Below are the 4 fixed positions which can be set from wireless LCD handset.
Position
Angle against vertical
1
35 º
2
57 º
3
83 º
4
100 º
Hour
Sleep on
0.5
1.0
2.0
Sleep off
Set temperature
Ts
Ts+0.5
Ts+1.0
Ts+2.0
Hour
Sleep on
0.5
1.0
2.0
Sleep off
Set temperature
Ts
Ts-2.0
Ts-1.0
Ts-0.5
Summary of Contents for L/M-STAT AMV Series
Page 1: ...SK2018 GLOBAL FDLA V P AC 001 FDLA V P AC MOTOR...
Page 27: ...Page 26 of 51 SK2018 GLOBAL FDLA V P AC 001 Configuration Settings...
Page 53: ...FDHD V P AC MOTOR...
Page 69: ...B 1 4 4 Electrical connections T Configuration standard version...
Page 74: ...Wiring Diagram D 2 SK NCPDWH 001b S Configuration Full Control PCB...
Page 76: ...Configuration Settings D 3...
Page 111: ......
Page 112: ...SK2019 FCSD H V P ECM 001 FCSD H V P ECM MOTOR...
Page 190: ...SK2019 FCSD H V P ECM 001...
Page 191: ...Page 1 of 59 SK2015 FMCD V EC 001 FMCD ECM MOTOR...
Page 210: ...Page 20 of 59 SK2015 SWC V EC 001 D 1 3 Wiring Diagram SK NCSWC 001...
Page 233: ...Page 43 of 59 SK2015 SWC V EC 001 D 4 2 Wiring diagram SK NCSWC 002...
Page 248: ...Page 58 of 59 SK2015 SWC V EC 001 Troubleshooting Guide E 4...
Page 249: ...Page 59 of 59 SK2015 SWC V EC 001...
Page 250: ...FSTD C V P ECM MOTOR...
Page 256: ...Page 7 of 73 SK2015 FSTDC V P ECM 001 A 2 Unit Appearance FSTDC VAR FSTDC HAR FSTD...