![Daitsu L/M-STAT AMV Series Installation, Operation & Service Manual Download Page 198](http://html1.mh-extra.com/html/daitsu/l-m-stat-amv-series/l-m-stat-amv-series_installation-operation-and-service-manual_3264310198.webp)
Page
8
of
59
SK2015
FMCD
‐
V
‐
EC
‐
001
Product
range
:
FMCD
‐
ECM
Hydronic
High
Wall
with
EC
Motor
FMCD
‐
[
Size
]
‐
V~
‐
ECM
18
20
24
30
Unit
Configuration
Configuration
2
‐
pipe
Number
Of
Fan
Blowers
Single
Power
Supply
(V/Ph/Hz)
230/1/50
220/1/60
Operation
Control
~S:
Complete
function
onboard
PCB
with
integrated
group
control
functionality,
incl.
1
pc
return
air
sensor
and
2
pcs
temperature
sensors.
~W:
Limited
function
onboard
PCB
with
drain
‐
pump,
louver
and
zone
control
functionality,
incl.
1
pc
coil
temperature
sensors.
Per
fo
rmanc
e
Data
Air
Air
Flow
H
m
3
/hr
788
980
1080
1240
M
740
760
980
1080
L
570
600
600
760
Cooling
Cooling
Capacity
e
H
kW
3.74
4.81
5.37
5.98
M
3.28
3.9
4.81
5.16
L
2.67
3.35
3.35
3.9
Sensible
Cooling
Capacity
e
H
2.74
3.46
3.88
4.34
M
2.4
2.8
3.46
3.73
L
1.94
2.38
2.38
2.8
FCEER
e
Rating
182.23
208.00
166.55
142.5
Class
B
A
B
B
Heating
Heating
Capacity
e
H
kW
4.77
5.97
6.7
7.5
M
4.17
4.82
5.97
6.43
L
3.37
4.12
4.12
4.82
Max.
Electric
Heater
Capacity
1.5
FCCOP
e
Rating
233.33
258.09
206.64
178.55
Class
B
B
B
C
Soun
d
Sound
PressureLevel(
Outlet
)
dB(A)
49/44/37
43/39/36
47/43/37
50/47/40
Sound
Power
Level
(
Outlet
)
e
58/53/46
52/48/45
56/52/46
59/56/49
Electrical
Fan
Motor
Power
e
H
W
30
30
40
50
M
26
20
30
40
L
13
15
19
25
Fan
Motor
Apparent
Power
@
H
60
60
80
100
Fan
Motor
Running
Current
@
H
A
0.261
0.261
0.347
0.434
Hydr
aulic
Cooling
Water
Flow
Rate
H
L/h
641
825
921
1025
M
562
669
825
885
L
458
574
574
669
Cooling
Pressure
Drop
e
H
kPa
50
43.5
52.5
63.3
M
40
30.5
43.5
49.3
L
28
23.5
23.5
30.5
Heating
Water
Flow
Rate
@H/M/L
L/h
Same
as
"Cooling
Water
Flow
Rate"
Heating
Pressure
Drop
e
H
kPa
45
39.2
47.3
57
M
36
27.5
39.2
44.4
L
25.2
21.2
21.2
27.5
Water
Content
L
0.192
0.252
0.252
0.252
Construc
tion
and
Pac
king
Data
Water
Connections
Type
Socket
(Threaded
Female)
In
mm
[in]
12.70
[1/2]
Out
Condensate
Drainage
Connection
16
[0.63]
Dimensions
L
mm
876
1063
W
228
240
H
300
310
Net
Weight
kg
14
16
16
16
1."
e
"
refers
to
technical
information
listed
on
the
Eurovent
website.
Eurovent
testing
conditions:
a.
Cooling
mode
(2
‐
pipe):
b.
Heating
mode
(2
‐
pipe):
‐
Return
air
temperature:
27C
DB/
19C
WB.
‐
Return
air
temperature:
20C.
‐
Inlet/
Outlet
water
temperature:
7C/
12C.
‐
Inlet
water
temperature:
50C.
‐
Water
flow
‐
rate:
same
as
2
‐
pipe
cooling.
Summary of Contents for L/M-STAT AMV Series
Page 1: ...SK2018 GLOBAL FDLA V P AC 001 FDLA V P AC MOTOR...
Page 27: ...Page 26 of 51 SK2018 GLOBAL FDLA V P AC 001 Configuration Settings...
Page 53: ...FDHD V P AC MOTOR...
Page 69: ...B 1 4 4 Electrical connections T Configuration standard version...
Page 74: ...Wiring Diagram D 2 SK NCPDWH 001b S Configuration Full Control PCB...
Page 76: ...Configuration Settings D 3...
Page 111: ......
Page 112: ...SK2019 FCSD H V P ECM 001 FCSD H V P ECM MOTOR...
Page 190: ...SK2019 FCSD H V P ECM 001...
Page 191: ...Page 1 of 59 SK2015 FMCD V EC 001 FMCD ECM MOTOR...
Page 210: ...Page 20 of 59 SK2015 SWC V EC 001 D 1 3 Wiring Diagram SK NCSWC 001...
Page 233: ...Page 43 of 59 SK2015 SWC V EC 001 D 4 2 Wiring diagram SK NCSWC 002...
Page 248: ...Page 58 of 59 SK2015 SWC V EC 001 Troubleshooting Guide E 4...
Page 249: ...Page 59 of 59 SK2015 SWC V EC 001...
Page 250: ...FSTD C V P ECM MOTOR...
Page 256: ...Page 7 of 73 SK2015 FSTDC V P ECM 001 A 2 Unit Appearance FSTDC VAR FSTDC HAR FSTD...