SSD Installation Instructions 

Published Date: 2019.08.20

INSTALLATION INSTRUCTIONS

These general instructions apply to all applications.

Worker Safety

For worker safety during installation, it is recommended that 

the user obtain certain equipment; namely a pair of electrically 

insulated gloves, a shorting cable approximately 3 ft (0.91 m) 

long with insulated clamps on each end, and a multi-meter 

to measure AC voltage. (Of these items, Dairyland offers 

a suitable 3 ft long 1/0AWG shorting cable with insulated 

clamps, Model# BCL-1/0 for decouplers rated 10kA or higher 

or Model# BCL-2 for decouplers rated less than 10kA.) The 

following installation procedure assumes that these items are 

available. It is suggested that a grounding jumper be used 

as a safety precaution in the event the lead to the structure 

rises to an unsafe potential when it is disconnected during 

the installation process or if an electrical disturbance occurs 

while the decoupler is being installed. Be sure to remove the 

grounding jumper after the decoupler is completely installed. 

If the structure voltage is not at a safe touch potential 

(i.e.,>15VAC to ground per NACE SP0177), then insulating 

gloves should be used.

Mounting

Mount the SSD so that the total length of conductor to the 

connection points will be as short as possible if the SSD is going 

to be used to provide over-voltage protection from lightning. 

All conductors have inductance which will cause a significant 

voltage per unit of conductor length when subject to lightning 

surge current. To minimize the voltage developed between 

the connection points, install the SSD as close as practical to 

the required connection points and cut the conductor to the 

shortest possible length during installation. For most insulated 

joint applications the SSD can, and should, be installed with 

less than 8” (200 mm) of conductor. Conductors can develop 

1-3 kV/ft. (approx. 3-10 kV/meter) of length due to lightning; 

hence, for this reason, leads should be kept as short as 

possible in lightning applications. Conductor length is not 

critical for limiting voltage due to 50 Hz or 60 Hz current.

Mounting Accessories

Numerous mounting accessories are available from Dairyland 

to aid in the proper installation of the PCR. Full details and 

complete installation instructions are available on the Dairyland 

website here: 

Dairyland Accessories.

Specific Installation Guidance

The Dairyland website contains detailed information on 

the  installation  methods  specific  to  a  given  application. 

For wiring diagrams and/or application guidance, see 

Dairyland Applications.

Environmental Exposure

The SSD enclosure is rated IP68 and is suitable for indoor 

or outdoor use, in submersible and non-submersible 

applications. SSDs may be submersed in non-freezing 

conditions up to 6.5 ft. (2 m) depth for occasional prolonged 

periods, though not continuously.

The unit must be installed in environments with ambient 

temperatures of  -49ºF to +149ºF (-45ºC to +65ºC).

Polarity

If the SSD purchased has asymmetrical blocking characteristics 

and it is being connected between a cathodically  protected 

structure and ground, connect the negative terminal of the 

SSD to the cathodically protected structure and the positive 

terminal to ground. If being connected between two different 

cathodically protected systems, attach the negative terminal 

to the more negative structure and the positive terminal to the 

less negative structure. A label on the SSD housing shows the 

polarity of each terminal.

Enclosure

The standard enclosure is rated IP68 to 2 m depth (comparable 

to NEMA 6P). This enclosure is suitable for submersible 

applications.

Ambient Operating Temperature

-45ºC to +65ºC.

Field Testing

Before installation, the following measurements are suggested 

to  confirm  that  the  steady-state  conditions  imposed  on  the 

SSD will be within its ratings.

1.  Measure the open-circuit DC voltage between the SSD 

connection points with a multimeter. The open-circuit DC 

voltage measured should be within the DC blocking voltage 

rating of the model selected (i.e., normally -3.0 V/+1.0 V or 

+/-2.0 V, unless a custom version has been ordered).

WARNING:

During installation, the voltage on the structure may rise 

to an unsafe level (i.e., due to induced AC, AC fault or 

lightning on the structure). Sparking and current flow may 

occur when connecting or disconnecting decouplers or 

over-voltage protectors. Assure that this does not occur 

in hazardous locations where gases or vapors may be 

present. All necessary safety precautions must be taken 

by the user to avoid unsafe worker conditions, including 

arcing, in accordance with applicable industry and/or 

company-required practices. Dairyland provides suggested 

procedures for installing and operating this equipment 

(See the section on Worker Safety). But the user must be 

responsible for and approve the procedures to be used by its 

workers when installing the equipment because Dairyland 

cannot be familiar with each user’s safety guidelines.

CAUTION:

Note:  Explosion  Hazard  -  Substitution  of  any  component 

may impair suitability for Class I, Division 2.