IOM 1322-1 • WATER-COOLED SCROLL COMPRESSOR 62 www.DaikinApplied.com
Startup and Shutdown Procedures
returned to the Daikin Applied service through your sales
representative.
Weekend or Temporary Shutdown
Move pumpdown switches PS1 and PS2 to the “manual
pumpdown” position. After the compressors have pumped
down, turn off the chilled water pump. Note: With the unit in this
condition, it will not restart until these switches are turned back
on. The unit has one-time pumpdown. It is important that the
compressors pump down before the water flow to the unit is
interrupted to avoid freeze-up in the evaporator.
Leave S1 on and power to the unit so that the crankcase
heaters will remain energized.
Start-up after Temporary Shutdown
1. Start the water pumps.
2. With the control system switch S1 in the “on”
position,move the pumpdown switches PS1 and PS2 to
the “auto pumpdown” position.
3. Observe the unit operation for a short time, noting
unusual sounds or possible cycling of compressors.
4. Check compressor crankcase heaters.
Extended Shutdown
1.
Close the manual liquid line shutoff valves.
2.
After the compressors have pumped down, turn off the
water pumps.
3.
Turn off all power to the unit.
4.
Move the control service switch S1 to the “off” position.
5.
Close the discharge shutoff valves on the compressor(s)
and the liquid outlet valves at the condenser.
6. Tag all opened disconnect switches to warn against
startup before opening the compressor suction and
discharge valves.
7. Drain all water from the unit evaporator, condenser, and
chilled water piping if the unit is to be shut down during
the winter and exposed to below freezing temperatures.
Do not leave the vessels or piping open to the
atmosphere over the shutdown period.
Start-up after Extended Shutdown
1. Inspect all equipment to see that it is in satisfactory
operating condition.
2. Remove all debris that has collected on the surface of
the cooling tower.
3. Open the compressor discharge valves until backseated.
Always replace valve seal caps.
4.
Open the manual liquid line shutoff valves.
5.
5 Check circuit breakers. They must be in the “off”
position.
6. Check to see that the pumpdown switches PS1 and PS2
are in the “manual shutdown” position and the control
system switch S1 is in the “off” position.
7. Put the main power and control circuit disconnects to the
“on” position.
8. Leak test the unit.
9. Allow the crankcase heaters to operate for at least 12
hours prior to start-up.
10. Start the chilled water pump and purge the water piping
as well as the evaporator in the unit.
11. Start the system auxiliary equipment for the installation
by turning on the time clock, ambient thermostat and/or
remote on/off switch.
12. Check that the MicroTech II controller is set to the
desired chilled water temperature.
13. Check resets of all equipment protection controls.
14. Switch the unit circuit breakers to “on.”
15. Start the system by setting the system switch S1 to “on.”
CAUTION
Most relays and terminals in the control center are powered when S1 is
closed and the control circuit disconnect is on. Therefore, do not close S1
until ready for start-up or serious equipment damage can occur.
16. Set pumpdown switches PS1 and PS2 to the “auto
pumpdown” position for restart and normal operation.
17. After running the unit for a short time, check the oil level
in the compressor oil sight glass or in the compressor’s
equalizing lines for flashing indicating possible refrigerant
in the oil (see System Maintenance section beginning on
).
Summary of Contents for WGZ030DW
Page 4: ......
Page 57: ...Unit Controller Operation www DaikinApplied com 57 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 71: ...Unit Maintenance www DaikinApplied com 71 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 74: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 74 www DaikinApplied com Troubleshooting Chart...
Page 75: ...Troubleshooting Chart www DaikinApplied com 75 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 76: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 76 www DaikinApplied com Troubleshooting Chart...
Page 77: ...Troubleshooting Chart www DaikinApplied com 77 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 78: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 78 www DaikinApplied com Troubleshooting Chart...