Unit Controller
www.DaikinApplied.com 31
IOM 1322-1 • WATER-COOLED SCROLL COMPRESSOR
Table 23: Digital Inputs
The following parameters are digital inputs to this controller.
C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit, *n = Refrigerant Dependent
#
Description
Type
Signal
Signal
1
Unit OFF Switch
UT
0 VAC (Stop)
24 VAC (Auto)
2
Pump Down Switch #1
C1
0 VAC (Stop)
24 VAC (Start)
3
Evaporator Water Flow Switch
UT
0 VAC (No Flow)
24 VAC (Flow)
*4
Motor Protection #1
C1
0 VAC (Fault)
24 VAC (No Fault)
*4
Open
5
Open
6
Pump Down Switch #2
C2
0 VAC (Stop)
24 VAC (Start)
*7
Motor Protection #2
C2
0 VAC (Fault)
24 VAC (No Fault)
*7
Open
*8
Open
*8
Condenser Water Flow Switch
(R134a,R410A)
UT
0 VAC (No Flow)
24 VAC (Flow)
9
Phase Voltage Fault #1 (See Note 1 Below)
C1
0 VAC (Fault)
24 VAC (No Fault)
10
Phase Voltage Fault #2 (See Note 1 Below)
C2
0 VAC (Fault)
24 VAC (No Fault)
11
Ground Fault Prot. #1 (See Note 2 Below)
C1
0 VAC (Fault)
24 VAC (No Fault)
12
Ground Fault Prot. #2 (See Note 2 Below)
C2
0 VAC (Fault)
24 VAC (No Fault)
13
Remote Start/Stop
UT
0 VAC (Stop)
24 VAC (Start)
*14
Condenser Water Flow Switch
UT
0 VAC (No Flow)
24 VAC (Flow)
*14
Open
*15
Open
*15
Motor Protection #1
(R134a,R410A)
C1
0 VAC (Fault)
24 VAC (No Fault)
*16
Open
*16
Motor Protection #2
(R134a,R410A)
C2
0 VAC (Fault)
24 VAC (No Fault)
17
Ice Mode Switch
UT
0 VAC (Normal)
24 VAC (Ice)
18
Heat Mode Switch
UT
0 VAC (Normal)
24 VAC (Heat)
NOTE:
1. Units with single point electrical connection will have one PVM with Inputs 9 and 10 wired together. Units with multiple
point connection will have two PVM’s with Input 9 for Electrical Circuit #1 and Input 10 for Electrical Circuit #2.
NOTE:
2. Units with single point electrical connection will have one GFP with Inputs 11 and 12 wired together. Units with multiple
point connection will have two GFP’s with Input 11 for Electrical Circuit #1 and Input 12 for Electrical Circuit #2.
Table 24: Digital Outputs
The following parameters are digital outputs from this controller.
C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit, *n = Refrigerant Dependent
#
Description
Type
Load
Output OFF
Output ON
1
Alarm
C1,C2,UT Alarm Indicator
Alarm OFF
Alarm ON
2
Evaporator Water Pump
UT
Pump Contactor
Pump OFF
Pump ON
3
Condenser Water Pump – Water Cooled = Y
C1/UT
Pump Contactor
Fan OFF
Fan ON
4
Motor Control Relay #1 = Compr#1
C1
Starter
Compressor OFF
Compressor ON
5
Motor Control Relay #3 = Compr#3
C1
Starter
Compressor OFF
Compressor ON
*6
Tower Fan #2-Water Cooled=Y
C1/UT
Fan Contactor
Fan OFF
Fan ON
*6
Motor Control Relay #5 = Compr#5
(R134a, R410A)
C1
Starter
Compressor OFF
Compressor ON
Summary of Contents for WGZ030DW
Page 4: ......
Page 57: ...Unit Controller Operation www DaikinApplied com 57 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 71: ...Unit Maintenance www DaikinApplied com 71 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 74: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 74 www DaikinApplied com Troubleshooting Chart...
Page 75: ...Troubleshooting Chart www DaikinApplied com 75 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 76: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 76 www DaikinApplied com Troubleshooting Chart...
Page 77: ...Troubleshooting Chart www DaikinApplied com 77 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 78: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 78 www DaikinApplied com Troubleshooting Chart...