Maintenance Schedule
Maintenance Check List Item
Daily
W
ee
kl
y
Mon
th
ly
Q
u
ar
ter
ly
An
n
u
all
y
5
-Yr
As Req’d
I. Unit
· Operational Log
O
· Analyze Operational Log
O
· Refrigerant Leak Test Chiller
O
· Test Relief Valves or Replace
X
II. Compressor
· Vibration Test Compressor
X
A. Motor
· Meg. Windings (Note 2)
X
· Ampere Balance (within 10% at RLA)
O
· Terminal Check (Infrared temperature measurement)
X
· Motor Cooling Filter Drier Pressure Drop
X
B. Lubrication System
· Lubricant Appearance (clear color, quantity)
O
- Lubricant Filter Pressure Drop
O
· Lubricant Analysis (Note 6)
X
· Lubricant change if indicated by lubricant analysis
X
III. Controls
A. Operating Controls
· Calibrate Temperature Transducers
X
· Calibrate Pressure Transducers
X
· Check Vane Control Setting and Operation
X
· Verify Motor Load Limit Control
X
· Verify Load Balance Operation
X
· Check Lubricant Pump Contactor
X
B. Protective Controls
· Test Operation of:
Alarm Relay
X
Pump Interlocks
X
Guardistor and Surgeguard Operation
X
High and Low Pressure Cutouts
X
Lubricant Pump Pressure Differential Cutout
X
Lubricant Pump Time Delay
X