OMM WCT
Centrifugal Chillers
D-EOMWC01302-16EN - 32/84
Table 11, WATER Setpoint Settings
Description
Default
Range
Pass-
word
Comments
Cool LWT
44. 0
F
35.0 to 80.0
F
M
Evaporator LWT setpoint in COOL mode
Ice LWT
25. 0
F
15.0 to 35.0
F
M
Evaporator LWT setpoint in the ICE mode
Heat LWT
135. 0
F
100.0 to 150.0
F
M
Condenser LWT setpoint in HEAT (Templifier) mode
Shutdown Delta T
3.0
F
0.0 to 3.0
F
M
Degrees below setpoint for compressor to stop.
Startup Delta T
3.0
F
0.0 to 10.0
F
M
Degrees above setpoint for compressor to start.
Stage Delta T
1ºF
0.5 to 5
F
M
Sets the temperature the leaving water must be below
setpoint for next compressor to start.
LWT Reset Type
NONE
NONE, RETURN,
4-20mA
M
Select reset type, NONE for none, RETURN for
reseting chilled water based on the entering water, or
4-20 mA for external analog signal
Start Reset Delta T
10. 0
F
0.0 to 20.0
F
M
Sets the evap delta-T above which Return reset
begins.
Max Reset Delta T
0.0
F
0.0 to 20.0
F
M
Set the maximum reset that can occur, in °F if LWT
reset is selected or max reset at 20 mA input if 4-20
mA is selected in SP7
MODES Setpoints
Figure 20, MODES Setpoint Screen