Daikin VRVWII RWEYQ10MY1 Operation Manual Download Page 14

9

English

7-3 AT THE END OF THE SEASON

On a clear day, use fan operation for around half a 
day to thoroughly dry out the interior of the unit.

• Refer to page 5 for details on fan only operation.

Turn off the power.

• When the power is shut off, the characters in the 

remote controller display disappear.

• When the power is on, the unit consumes up to 

several dozen Watts of power.
Turn off the power to conserve energy.

Clean the air filter and exterior.

• After cleaning the air filter, be sure to put it back in 

the same position.
See the operation manual included with the 
indoor unit for details on how to clean it.

• If the water piping may freeze, keep operating the 

heat source water pump operating even during 
the unit stops.

• Remove all the water from the unit and the water 

piping if the pump is not used for a long time in 
winter.

8. FOLLOWING SYMPTOMS ARE NOT 

AIR CONDITIONER TROUBLES

8-1 THE SYSTEM DOES NOT OPERATE

The air conditioner does not start immediately 
when restarting the operation after stoping 
the operation or when putting the temperature 
back after changing the temperature setting 
with the temperature adjust button.

If the operation lamp lights, the system is in nor-
mal condition.
To prevent overloading of the unit, the air condi-
tioner starts 5 minutes after it is turned ON again 
in case it was turned OFF just before.

If “Centralized Control” is displayed on the 
remote controller and pressing the operation 
button causes the display to blink for a few 
seconds.

This indicates that the central device is controlling 
the unit.
The blinking display indicates that the remote 
control cannot be used.

The system does not start immediately after 
the power supply is turned on.

Wait one minute until the micro computer is pre-
pared for operation.

8-2 IT STOPS SOMETIMES

The remote controller display reads “U4” or 
“U5” and stops but then restarts after a few 
minutes.

This is because the remote control is intercepting 
noise from electrical appliances other than the air 

conditioner, and this prevents communication 
between the units, causing them to stop.
Operation automatically restarts when the noise 
goes away.

8-3 COOL/HEAT CANNOT BE CHANGED 

OVER

When the display shows 

 

(changeover under control).

It shows that this is a slave remote controller.
Refer to “Setting the master remote controller”.

When the cool/heat selector switch is 
installed and the display shows 

 

(changeover under control).

This is because cool/heat changeover is con-
trolled by the cool/heat selector. Ask your Daikin 
dealer where the remote control switch is installed.

8-4 FAN OPERATION IS POSSIBLE, BUT 

COOLING AND HEATING DO NOT 
WORK

Immediately after the power is turned on.

The micro computer is getting ready to operate.
Wait 10 minutes.

Only fan operation is possible.

This is because the interlock contact point is not 
turned on. (Check that the water pump is operat-
ing.)
This is because the inlet temperature (*1) of the 
heat source water is beyond the operating condi-
tions (refer to page 4). (Check that it is in the 
range of the operating conditions.)

8-5 THE FAN SPEED DOES NOT CORRE-

SPOND TO THE SETTING

The fan speed does no change even if the fan 
strength adjustment button in pressed.

• When the room temperature reaches the set tem-

perature during heating operation (extremely low 
fan speed operation).

• When operation is changed to fan operation while 

another indoor unit is in heating operation 
(extremely low fan speed operation).

• When the remote controller displays “

” 

(stoppage).

• When the remote controller displays “

” (auto-

matic operation).

8-6 THE AIR FLOW DIRECTION DOES NOT 

CORRESPOND TO THE SETTING

The air flow direction does not correspond to 
the remote control display.
The air flow direction does not swing.

This is because the unit is being controlled by the 
microcomputer. Refer to “Adjusting the air flow 
direction”.

01_EN_3P153897-1.fm  Page 9  Wednesday, March 2, 2005  3:32 PM

Summary of Contents for VRVWII RWEYQ10MY1

Page 1: ...riebsanweisung VRVWII System Klimaanlage Manuel d utilisation Conditionneur d air VRVWII System Manual de operaci n Sistema de acondicionador de aire VRVWII Manuale d uso Condizionatore d aria a siste...

Page 2: ...lo desea puede consultar detalles sobre la unidad interior en el manual de funcionamiento pro vistoconlamisma Guardeel manualdefuncionamientoconlaunidad interior y con este manual en un lugar seguro C...

Page 3: ...2 1 4 2 NOT AVAILABLE 3 5 00_CV_3P153897 1 fm Page 3 Friday March 4 2005 1 41 PM...

Page 4: ...5 6 8 7 1 7 2 7 3 9 00_CV_3P153897 1 fm Page 4 Friday March 4 2005 1 41 PM...

Page 5: ...10 11 13 12 Double flow Ceiling Suspended Wall Mounted Multi flow Corner 14 Heat pump system Heat recovery system 00_CV_3P153897 1 fm Page 5 Friday March 4 2005 1 41 PM...

Page 6: ...er leakage electric shock and fire Do not put a finger a rod or other objects into the air inlet or outlet As the fan is rotating at high speed it will cause injury Never touch the air outlet or the h...

Page 7: ...ing conductor or telephone earth wire Arrange the drain hose to ensure smooth drainage Incomplete drainage may cause wet ting of the building furniture etc Do not let children play on and around the o...

Page 8: ...during operation 3 Display changeover under control It is impossible to changeover heat cool with the remote controller which display this icon 4 Display air flow flap Refer to the chapter Operation p...

Page 9: ...g conditions the safety device may be activated and the unit becomes not operational or condensed water drops from an indoor unit This value shows a quantity of water per one outside unit NOTE To avoi...

Page 10: ...ediately after the unit stops The system needs at least 5 minutes for residual operation of drain pump device Turning off the power immediately will cause water leak or trouble EXPLANATION OF HEATING...

Page 11: ...only for FXC FXF FXH FXK FXA Press the air flow direction button to select the air direction The air flow flap display swings as shown right and the air flow direction continuously varies Automatic s...

Page 12: ...ontroller can select heating automatic or cooling operation The displays of slave remote controllers show changeover under control and they automatically follow the operation mode directed by the mast...

Page 13: ...parallel during cooling or dry operation and set it downwards during heat ing operation Do not let the air blow directly to a person Make sure that the inlet and outlet of the indoor unit are not clog...

Page 14: ...nd stops but then restarts after a few minutes This is because the remote control is intercepting noise from electrical appliances other than the air conditioner and this prevents communication betwee...

Page 15: ...at the start or immediately after stopping operation This is the noise of refrigerant gas caused by flow stop or flow change 8 9 DUST COMES OUT OF THE UNIT When the unit is used after stopping for a...

Page 16: ...estored If power failure occurs during operation the system automati cally restarts immediately after the power supply is recovered Check if no fuse has blown Turn off the power supply Check if the br...

Page 17: ...tc it will cause toxic gas to be generated When a refrigerant leakage failure has been repaired confirm a service person that the leakage point has been corrected surely before restarting operation Do...

Page 18: ...f maintenance cycle and replacement cycle needs to be considered in the following cases 1 When used in hot humid locations or locations where temperature and humidity fluctuate greatly 2 When used in...

Page 19: ...sales service etc consult with your dealer Warranty period This product includes a warranty card The warranty card is given to a customer after dealer staff fills out necessary items in the card The c...

Page 20: ...3P153897 1A EM04A065 0503 HT 00_CV_3P153897 1 fm Page 6 Friday March 4 2005 1 41 PM...

Reviews: