Daikin VRVWII RWEYQ10MY1 Operation Manual Download Page 12

7

English

5-4 PROGRAMMING START AND STOP OF 

THE SYSTEM WITH TIMER 
(Refer to figure 9)

• The timer is operated in the following two ways. 

Programming the stop time “

”. The sys-

tem stops operating after the set time has 
elapsed.
Programming the start time “

”. The sys-

tem starts operating after the set time has 
elapsed.

• The timer can be programmed for a maxi-

mum of 72 hours.

• The start and the stop time can be simulta-

neously programmed.

Press the timer mode start/stop button several 
times and select the mode on the display.
The display flashes.

• For setting the timer stop “

• For setting the timer start “

Press the programming time button and set 
the time for stopping or starting the system.

Each time this button is pressed, the 
time advances or goes backward by 
1 hour.

Press the timer on/off button.
The timer setting procedure ends. The display 

” or “

” changes from flashing 

light to constant light.

NOTE

• When setting the timer off and on at the 

same time, repeat the above procedure 
(from “

” to “

”) once again.

• After the timer is programmed, the display 

shows the remaining time.

• Press the timer on/off button once again to 

cancel programming. The display vanishes.

For example: (Refer to figure 11)

When the timer is programmed to stop the sys-
tem after 3 hours and start the system after 
4 hours, the system will stop after 3 hours and 
start 1 hour later.

5-5 SETTING THE MASTER REMOTE CON-

TROLLER (Refer to figure 10)

• When one outside unit or BS unit is connected 

with several indoor units as shown in figure 14, it 
is necessary to designate one of the remote con-
trollers as the master remote controller.

• Only the master remote controller can select 

heating, automatic or cooling operation.

• The displays of slave remote controllers show 

” (changeover under control) and they 

automatically follow the operation mode directed 
by the master remote controller.
However, it is possible to changeover to program 
dry with slave remote controllers if the system is in 
cooling operation by setting on the master remote 
controller and to changeover to fan only opera-
tion.

How to designate the master remote controller

Press the operation mode selector button of 
the current master remote controller for 4 sec-
onds.
The display showing “

” (changeover 

under control) of all slave remote controllers 
connected to the same outside unit flashes.

Press the operation mode selector button of 
the controller that you wish to designate as the 
master remote controller. Then designation is 
completed. This remote controller is desig-
nated as the master remote controller and the 
display showing “

” (changeover 

under control) vanishes.
The displays of other remote controllers show 

” (changeover under control).

5-6 PRECAUTIONS FOR GROUP CON-

TROL SYSTEM OR TWO REMOTE CON-
TROLLER CONTROL SYSTEM

This system provides two other control systems 
beside individual control (one remote controller con-
trols one indoor unit) system. Confirm about your sys-
tem to Daikin dealer.

Group control system

One remote controller controls up to 16 indoor 
units. All indoor units are equally set.

Two remote controllers control system

Two remote controllers control one indoor unit (in 
case of group control system, one group of indoor 
units). The unit is individually operated.

NOTE

• Contact your Daikin dealer in case of chang-

ing the combination or setting of group con-
trol and two remote controller control 
systems.

1

2

3

1

3

1

2

01_EN_3P153897-1.fm  Page 7  Wednesday, March 2, 2005  3:32 PM

Summary of Contents for VRVWII RWEYQ10MY1

Page 1: ...riebsanweisung VRVWII System Klimaanlage Manuel d utilisation Conditionneur d air VRVWII System Manual de operaci n Sistema de acondicionador de aire VRVWII Manuale d uso Condizionatore d aria a siste...

Page 2: ...lo desea puede consultar detalles sobre la unidad interior en el manual de funcionamiento pro vistoconlamisma Guardeel manualdefuncionamientoconlaunidad interior y con este manual en un lugar seguro C...

Page 3: ...2 1 4 2 NOT AVAILABLE 3 5 00_CV_3P153897 1 fm Page 3 Friday March 4 2005 1 41 PM...

Page 4: ...5 6 8 7 1 7 2 7 3 9 00_CV_3P153897 1 fm Page 4 Friday March 4 2005 1 41 PM...

Page 5: ...10 11 13 12 Double flow Ceiling Suspended Wall Mounted Multi flow Corner 14 Heat pump system Heat recovery system 00_CV_3P153897 1 fm Page 5 Friday March 4 2005 1 41 PM...

Page 6: ...er leakage electric shock and fire Do not put a finger a rod or other objects into the air inlet or outlet As the fan is rotating at high speed it will cause injury Never touch the air outlet or the h...

Page 7: ...ing conductor or telephone earth wire Arrange the drain hose to ensure smooth drainage Incomplete drainage may cause wet ting of the building furniture etc Do not let children play on and around the o...

Page 8: ...during operation 3 Display changeover under control It is impossible to changeover heat cool with the remote controller which display this icon 4 Display air flow flap Refer to the chapter Operation p...

Page 9: ...g conditions the safety device may be activated and the unit becomes not operational or condensed water drops from an indoor unit This value shows a quantity of water per one outside unit NOTE To avoi...

Page 10: ...ediately after the unit stops The system needs at least 5 minutes for residual operation of drain pump device Turning off the power immediately will cause water leak or trouble EXPLANATION OF HEATING...

Page 11: ...only for FXC FXF FXH FXK FXA Press the air flow direction button to select the air direction The air flow flap display swings as shown right and the air flow direction continuously varies Automatic s...

Page 12: ...ontroller can select heating automatic or cooling operation The displays of slave remote controllers show changeover under control and they automatically follow the operation mode directed by the mast...

Page 13: ...parallel during cooling or dry operation and set it downwards during heat ing operation Do not let the air blow directly to a person Make sure that the inlet and outlet of the indoor unit are not clog...

Page 14: ...nd stops but then restarts after a few minutes This is because the remote control is intercepting noise from electrical appliances other than the air conditioner and this prevents communication betwee...

Page 15: ...at the start or immediately after stopping operation This is the noise of refrigerant gas caused by flow stop or flow change 8 9 DUST COMES OUT OF THE UNIT When the unit is used after stopping for a...

Page 16: ...estored If power failure occurs during operation the system automati cally restarts immediately after the power supply is recovered Check if no fuse has blown Turn off the power supply Check if the br...

Page 17: ...tc it will cause toxic gas to be generated When a refrigerant leakage failure has been repaired confirm a service person that the leakage point has been corrected surely before restarting operation Do...

Page 18: ...f maintenance cycle and replacement cycle needs to be considered in the following cases 1 When used in hot humid locations or locations where temperature and humidity fluctuate greatly 2 When used in...

Page 19: ...sales service etc consult with your dealer Warranty period This product includes a warranty card The warranty card is given to a customer after dealer staff fills out necessary items in the card The c...

Page 20: ...3P153897 1A EM04A065 0503 HT 00_CV_3P153897 1 fm Page 6 Friday March 4 2005 1 41 PM...

Reviews: