background image

REYQ8~16P8Y1B
VRVIII System air conditioner
4PW39996-1A

Installation manual

17

1

Procedure for additional refrigerant charge

The automatic refrigerant charging has limits as described
below.
At out of limit, the system can not operate the automatic
refrigerant charging.

Pre-charging

To speed up the process of charging refrigerant for large systems, it
is recommended to first manually charge a portion of the refrigerant
first before performing automatic charging.

1

Calculate how much refrigerant to be added using the formula
explained in the chapter 

"How to calculate the additional

refrigerant to be charged" on page 8

.

2

The amount of pre-charging is 10 kg less than the calculated
amount.

3

Open valve B (the valves A and C, the liquid pipe, the suction
gas pipe and the high pressure/low pressure gas pipe stop
valves must be left closed) and charge the refrigerant in liquid
form via the liquid pipe stop valve service port.

(See figure 23)

4

If the calculated amount of pre-charging is reached, close
valve B.

5

After pre-charging, perform the refrigerant charge operation as
shown below and charge the remaining refrigerant of the
additional charging amount through valve A. 

(See figure 23)

1.

Start of automatic charging refrigerant
-

Open the liquid pipe, suction gas pipe and high pressure/low 
pressure gas pipe stop valves and the service port stop 
valve. (Valves A, B and C must be closed.)

-

Close all front panels except the electric component box front 
panel and turn the power ON.

-

Make sure all indoor units are connected, refer to 

"11.4. How 

to check how many units are connected" on page 16

.

-

If the H2P LED is not flashing (in 12 minutes time after 
turning on the power), make sure it is displayed as shown in 
the 

"2 Normal system display" on page 19

.

If the H2P LED is flashing, check the malfunction code on the
remote controller

 

"3 Remote controller malfunction code

display" on page 19

.

2.

Press the 

 button once if the LEDs combination is not

as in the figure below.

3.

Press the 

 button once.

4.

Hold the 

 button down for 5 seconds or more.

5.

Charging mode judgement
However, if the indoor temperature is 10°C DB or lower, in some
cases the unit will charge in heating mode to increase the indoor
temperature. 
The unit will automatically select the cooling mode or heating
mode for charging.

Outdoor temperature

: 0°C DB~43°C DB

Indoor temperature

: 10°C DB~32°C DB

Total indoor unit capacity

80%

1

Measuring instrument

2

Refrigerant tank (R410A, siphon system)

3

Charge hose

4

Refrigerant charge port 

5

High pressure/low pressure gas pipe stop valve

6

Suction gas pipe stop valve

7

Liquid pipe stop valve 

8

Valve A

9

Valve B

10

Valve C

11

Outdoor unit

12

To BS unit, indoor unit

13

Stop valve

14

Service port

15

Field piping

16

Refrigerant flow when pre-charging through the liquid stop valve 
service port (refer to step 

3 on page 17

)

17

Refrigerant flow when automatic charging through the charge port 
(refer to step 

5 on page 17

)

At least the unit should be charged with its original amount
of refrigerant (refer to the nameplate on the unit), before
starting the automatic charging.

NOTE

When the leak detection function is not required,
complete charging when using the previous described
method (unit is not operating) can be done.

If it is not possible to charge the entire quantity through
the service port of the liquid pipe stop valve with the
unit not operating, refer to 

"14. Additional  refrigerant

charging method" on page 25

.

NOTE

The refrigerant will be charged with ±30 kg in
1 hour time at an outdoor temperature of 30°C DB
or with ±12 kg at an outdoor temperature of
0°C DB.

During the automatic charging operation, you can
force the operation to a halt by pushing the

 button.

If you perform the refrigerant charging operation
within the refrigerant system with one or more
units with power OFF, the refrigerant charging
operation can not be accomplished properly.
For confirming the number of indoor units with
power ON, refer to 

"11.4. How to check how

many units are connected" on page 16

.

To  energize the crankcase heater, make sure to
turn the power ON at least 6 

hours before

starting operation.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

x

x w x

x

x

x

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w w w w w w w

When charging in cooling mode, the unit will stop
operating when the required amount of
refrigerant is charged.

During charging in heating mode, a person must
manually close valve A before complete charging
is finished. The required amount is the calculated
amount (see 

"6.6. Example of connection" on

page 7

), therefore, the weight must be monitored

constantly.

BS1  MODE

BS1  MODE

BS4  TEST

BS4  TEST

Summary of Contents for VRVIII REYQ-P8

Page 1: ...INSTALLATION MANUAL REYQ8P8Y1B REYQ10P8Y1B REYQ12P8Y1B REYQ14P8Y1B REYQ16P8Y1B System air conditioner...

Page 2: ...m e 100 mm f 500 mm 4 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm 1500 500 13 2 1 6 3 4 6 5 6 9 10 7 8 2 1 A B C 5 3 2 1 6 4 3 4 2 b a c d A C B D a e b d e A...

Page 3: ...jeidemme mukaisesti 14 za p edpokladu e jsou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m 15 u skladu sa slijede im standardom ima ili drugim normativni...

Page 4: ...ujam temperat ra TS TSmin Minim l temperat ra zem spiediena pus L C TSmax Pies tin t temperat ra saska ar maksim lo pie aujamo spiedienu PS M C Dzesin t js N Spiediena dro bas ier ces iestat ana P bar...

Page 5: ...ging from 25 0 to 50 0 kW For changing the refrigerant flow to indoor units the REYQ P system can be combined with BS units of the types BSVQ100P BSVQ160P and BSVQ250P only Other BS unit types will ca...

Page 6: ...he Engineering Data Book Outdoor unit Total capacity of indoor units REYQ8 100 260 REYQ10 125 325 REYQ12 150 390 REYQ14 175 455 REYQ16 200 520 NOTE If the total capacity of the connected indoor units...

Page 7: ...nt concentration from exceeding allowable safety limits in the event of a refrigerant leak 11 To prevent dripping water to form a puddle underneath the unit install a drain pan available as option kit...

Page 8: ...foundation dimension 7 Distance between foundation bolt holes X Not allowed O Allowed units mm Prepare a water drainage channel around the foundation to drain waste water from around the unit If the...

Page 9: ...the pipe size nearest to the required size use the suitable adapters for the change over from inch to mm pipes field supply 6 3 Pipe connection Be sure to perform a nitrogen blow when brazing and to r...

Page 10: ...the system Great caution is needed when passing copper tubes through walls Block all gaps in the holes for passing out piping and wiring using sealing material field supply The capacity of the unit wi...

Page 11: ...outdoor unit side choose from the following table in accordance with the capacity of the outdoor unit example refnet joint A How to select the refnet header Choose from the following table in accordan...

Page 12: ...igerant branch kit to indoor units is 40 m or less however it can be extended up to 90 m if all the following conditions are fulfilled Required conditions Example drawings It is necessary to increase...

Page 13: ...Valve B 13 Valve C 14 Outdoor unit 15 To BS unit or indoor unit 16 Stop valve 17 Service port 18 Field piping 19 Gas flow NOTE Make sure to perform leak test and vacuum drying using the service ports...

Page 14: ...2 liquid 2 H E liquid 2 R10 Resistor current sensor R31T R32T Thermistor discharge M1C M2C R50 R59 Resistor R90 Resistor current sensor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL...

Page 15: ...to leaked electrical current which will have to be discharged with the grounding Be sure to install an earth leakage breaker One that can handle high frequency electrical noise This unit uses an inve...

Page 16: ...of the transmission wiring terminals 1 Electric wiring diagram Printed on the back of the electric component box lid 2 Power wiring and ground wiring inside conduit When the wiring is routed out throu...

Page 17: ...iquid pipe 2 High pressure low pressure gas pipe 3 Finishing tape 4 Suction gas pipe 5 Transmission wiring 6 Insulation material 1 Power supply 380 415 V 3 N 50 Hz 2 Earth leakage breaker 3 Fuse 4 Gro...

Page 18: ...6 Refrigerant piping on page 4 The electrical work 1 Make sure there is no faulty power wiring or loose nuts See 8 Field wiring on page 9 2 Make sure there is no faulty transmission wiring or loose nu...

Page 19: ...t cannot be charged until all field wiring and field piping has been completed Refrigerant may only be charged after performing the leak test and the vacuum drying Charge the liquid refrigerant with t...

Page 20: ...tem charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect your eyes when charging refrigerant When the refrigerant charging procedure is done or when...

Page 21: ...indoor temperature The unit will automatically select the cooling mode or heating mode for charging Outdoor temperature 0 C DB 43 C DB Indoor temperature 10 C DB 32 C DB Total indoor unit capacity 80...

Page 22: ...and may cause overcharging 7 Ready Press the button once within 5 minutes If the button is not pushed within 5 minutes P2 will be displayed on the remote controller Refer to 3 Remote controller malfun...

Page 23: ...e valve A and remove the refrigerant tank immediately after finishing the refrigerant charge operation The refrigerant charge port of these units have electric expansion valves that will close automat...

Page 24: ...x w w 20 95 x 100 w x w x w x x 21 100 x w x w x w x w NOTE If you get confused in the middle of the input process press the button to return to setting mode 1 initial state The H1P LED is off x Resum...

Page 25: ...tons LED state Throughout the manual the state of the LEDs is indicated as follows Setting the push button switch BS1 5 Function of the push button switch which is located on the outdoor unit PCB A1P...

Page 26: ...ormal w abnormal c under preparation or under test operation 2 Indication of low noise operation state x standard operation factory setting w operation 3 Indication of power consumption limitation set...

Page 27: ...seconds The H1P LED is on w Perform following steps 1 Press the button 3 times 2 Press the button once to confirm 3 Press the button in order to change the LED display to the following display 4 Press...

Page 28: ...iping length and correct the refrigerant charge level by recovering any excessive refrigerant with a refrigerant recovery machine Insufficient refrigerant E4 F3 Check if the additional refrigerant cha...

Page 29: ...pipe stop valve service port with the unit not operating refer to Pre charging on page 17 make sure to charge the remaining charging quantity using the following procedure 1 Turn the power of the ind...

Page 30: ...as the following calculate the volume of A B as a single room or as the smallest room 3 Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above If the result o...

Page 31: ...N D UNIT TO OUT D UNIT TO IN D UNIT TO OUT D UNIT F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 8 7 7 6 6 3 5 6 13 12 1 1 2 3 4 5 3 4 7 8 2 9 6 4 1 2 5 7 7 8 1 9 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6...

Page 32: ...4PW39996 1A Copyright Daikin...

Reviews: