background image

• VRV

®

 Systems • Installation procedure

9

• Installation procedure

1

Installation of outdoor

1 - 6 Handling of the plate type heat exchanger

C

AUTION

The brazing plate type heat exchanger (the plate type heat exchanger) is used for this outside unit. Because its structure is different from a 
conventional type heat exchanger, it must be handled in a different manner.

1 - 6 - 1

When designing the equipment

1

Install a strainer (an optional accessory) at the water inlet side adjacent to the outside unit in order to prevent any foreign materials such as dust, 
sand, etc. from entering.

2

Depending on the water quality, scale may stick to the plate type heat exchanger. In order to remove this scale, it is necessary to clean it at a 
regular interval using chemicals. To this end, install a gate valve in the water piping. Set up a piping connection port on the piping between this 
gate valve and the outside unit for cleaning by chemicals.

3

For the purpose of cleaning and water drain off from the outside unit (water draining during a long period of nonuse in winter, draining upon starting 
of season-off), install an “air discharge plug” and a “water draining plug” at the inlet/outlet ports of water piping. In addition, install an “automatic 
air discharging valve” at the top of riser piping or at the top of a portion where air tends to stay.

4

Independent of the piping inlet of the outside unit, install a cleanable strainer at a portion close to the pump piping inlet.

5

Carry out complete cooling/thermal insulation of water piping and outdoor dehumidification. If complete cooling or thermal insulation has not been 
carried out, any damage may be caused during severe winter due to freezing, in addition to thermal loss.

6

When you stop operation during night or winter, it is necessary to take measures to prevent water related circuits from natural freezing in the area 
the ambient temperature drops below 0°C (by water drain off, keeping the circulation pump running, warming up by a heater, etc.) Freezing of 
water related circuits may result in any damage to the plate type heat exchanger. Therefore, please take appropriate measures depending on the 
circumstances of use.

Example of piping

Water inlet piping

Strainer (sold separately as an accessory)

Air discharge plug (for joint use with cleaning port)

Cleaning device

Strainer for pump

Automatic air discharge valve

Water outlet piping

Joint use with water draining plug

Plate type heat exchanger

Outside unit

1 - 6 - 2

Before starting a test run

1

Before starting a test run, please make sure that the piping work has been carried out in a proper manner.
Especially, make sure that the strainer, air discharge valve, automatic water supply valve, expansion tank and cistern are positioned at their places correctly.

2

After water has been completely filled in, first run the pump only, and then make sure that no air has been caught in the water circulation system 
and the water flow rate is correct. If any air has been caught or the flow rate is not enough, the plate type heat exchanger may freeze. Measure 
any water pressure loss before and after the outside unit and make sure that the flow rate is as designed. In case of any abnormal, stop the test 
run immediately and carry out trouble shooting to resolve the trouble.

3

Following the installation manual, carry out a test run of the outside unit.

4

After the test run has been completed, inspect the strainer at the inlet piping of the outside unit. Clean it if it is dirty.

Summary of Contents for VRV-WII FXYCP30MY1

Page 1: ...technical data InstallationProcedure air conditioning systems EEDEN08 201 2b...

Page 2: ...n procedure 1 Installation of outdoor 2 Introduction 3 Selection of location 5 Inspecting and handling the unit 6 Unpacking and placing the unit 7 Water piping work 8 Handling of the plate type heat e...

Page 3: ...ing copper pipes or soldered parts may result in refrigerant leakage c near machinery emitting electromagnetic waves Electromagnetic waves may disturb the operation of the control system and result in...

Page 4: ...tible with R410A refer to the product catalogs Total capacity quantity of indoor units Outside unit Total capacity index of indoor units Total quantity of indoor units RWEYQ10MY1 125 325 16 units RWEY...

Page 5: ...0 x 2 1000 x 780 x 550 x 3 Mass kg 150 150 x 2 150 x 3 Connections Refrigerant liquid pipe inch 3 8 5 8 3 4 mm 9 5 28 6 19 1 Refrigerant gas pipe inch 7 8 1 1 8 1 3 8 mm 22 2 28 6 34 9 Refrigerant dis...

Page 6: ...tween the outside unit and the indoor unit may not exceed the allowable piping length 10 9 Refrigerant piping 5 Locations where the noise of the unit operating will not disturb nearby houses etc 6 Loc...

Page 7: ...caused by the corrosion of metal materials and clogging of the heat exchanger 5 The refrigerant R410A itself is nontoxic nonflammable and is safe If the refrigerant should leak however its concentrat...

Page 8: ...vailable M12 type foundation bolts nuts and washers The foundation bolts should be inserted 20 mm Fix 4 foundation bolts Support the unit with the foundation which is larger than the hatched area show...

Page 9: ...t any clogging by dust Do not connect the drain outlet to the water outlet Install a strainer an optional accessory in the inlet of water piping within a distance of 1 5 m from the outside unit If san...

Page 10: ...be caused during severe winter due to freezing in addition to thermal loss 6 When you stop operation during night or winter it is necessary to take measures to prevent water related circuits from natu...

Page 11: ...6 NOTES 1 The circle marks in the columns for corrosion or scale to develop 2 Corrosion has a tendency to occur when water temperature is high 40 C or higher and if metals with no protective coating...

Page 12: ...d nitric acid etc because they have strong corrosive features Make sure that a valve has been reserved for each before the inlet connection port and after the outlet connection port Connect the piping...

Page 13: ...e product in reversed phase may break the compressor and other parts Attach the power wire securely Introducing power with a missing N phase or with a mistaken N phase will break the equipment 1 7 1 O...

Page 14: ...gas pipes sewage pipes lightning rods or telephone ground wires Gas pipes can explode or catch fire if there is a gas leak Sewage pipes no grounding effect is possible if hard plastic piping is used...

Page 15: ...g should be secured as described in Field line connection transmission wiring and COOL HEAT selector 5 Secure the wiring with the accessory clamps so that it does not touch the piping 6 Make sure the...

Page 16: ...re no polarity Terminal board field supply Indoor unit Never connect the power wire BS unit A BS unit B Last BS unit Cool only unit In case of RWEYQ20 30MY1 Unit A Master unit Unit B Unit C TO IN D UN...

Page 17: ...eration circuit shall be set between terminals 1 and 2 Contact specification 220 VAC 3mA 0 5A PC board A1P Mount an insulation sleeve Connection of interlock circuit Do not forget to connect an interl...

Page 18: ...sheathed vinyl cords with 0 75 to 1 25 mm2 or cables 2 core wires 3 core wire are allowable for the COOL HEAT selector only All transmission wire is field supply If the following limits should be exc...

Page 19: ...leakage breaker Attach insulation sleeves Power supply terminal block Grounding terminal Retain the ground wires along with the power wires using the accessory clamp A Grounding wire When wiring do n...

Page 20: ...ng and ground jumper wiring Retain the power supply wiring pump operation output high voltage and ground wiring with the accessory clamp B to prevent them from touching with the stop valve for dischar...

Page 21: ...oned in the table below refer to the equipment design materials and service manual CAUTION A separate adapter sold separately as an accessory for external control of an outside unit becomes necessary...

Page 22: ...the system while the pump is not working 3Use a vacuum pump which can evacuate to 100 7 kPa 5Torr 755mmHg 1 8 1 Selection of piping material 1 Foreign materials inside pipes including oils for fabric...

Page 23: ...on nameplate Horizontal line Ground Straight part of 500mm or more Local pipe 120mm length or more Precautions when selecting branch piping If the equivalent length of piping between the outside units...

Page 24: ...autions when connecting pipes See the following table for flare part machining dimensions When connecting the flare nuts apply refrigerant oil to the inside and outside of the flares and screw them in...

Page 25: ...f the hatched area and use it as a cover for the drilled Hatched area Accessory pipe for discharge gas Accessory pipe for suction gas Guideline for pipe machining Accessory pipe for suction gas 2 Braz...

Page 26: ...ing causing any damage to the outside unit 3 If the piping length between the outside unit connecting pipe kit or between the outside units exceeds 2 m create a rise of 200 mm or more in the gas line...

Page 27: ...to 100 7kPa within 2 hours repeat the operation of vacuum break and vacuum drying Then after leaving the system in vacuum for 1 hour confirm that the vacuum gauge does not rise 1 8 6 Pipe insulation...

Page 28: ...front cover NOTE Refer to the example of connection for the amount to be added Additional refrigerant charge procedure 1 normally Charge the refrigerant to the liquid pipe in its liquid state Since R4...

Page 29: ...arging additional refrigerant Pressure reducing valve Nitrogen Refrigerant tank With a siphon Measuring instrument Vacuum pump Val ve A Val ve B Charge hose Outside unit Gas side Liquid side Discharge...

Page 30: ...then open the valve by turning 180 Start the additional refrigerant charge operation See Service precautions Label for detail If it is difficult to charge the refrigerant additionally decrease the wat...

Page 31: ...to the shutoff valve Doing so may break the valve body as the valve is not a backseat type Always use the hexagon wrench 3 Make sure to tighten the cap securely Closing shutoff valve 1 Remove the cap...

Page 32: ...turns as the initial tightening 7 Do not forget to open the stop valve before starting operation Remove the cap and turn the valve counter clockwise with the hexagon wrenches until it stops Discharge...

Page 33: ...not be operated at a temperature outside the operation range 6 Check the LED on the PC board A1P in the outside unit to see if the data transmission is performed normally The master unit is the outsid...

Page 34: ...toff valve of an outside unit is left closed Open the shutoff valve U1 The phases of the power to the outside units are reversed Exchange two of the three phases L1 L2 L3 to make a positive phase conn...

Page 35: ...ted therein Specifications are subject to change without prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage In the broadest sense arising from or related...

Reviews: