VRV IV+ heat pump
4P546228-1A – 2019.10
If
Then
"
", "
", or "
" appears
Push BS1 to finish the automatic charging
function procedure. The ambient conditions are
favourable to execute the test run.
"
", or "
" appears
The ambient conditions are NOT favourable to
execute the test run. Push BS1 to finish the
automatic charging procedure.
INFORMATION
In case a malfunction code occurred during this automatic charging procedure, the
unit will stop and indicate "
" flashing. Push BS2 to restart the procedure.
Cooling (middle 7‑segment display indicates " ")
Automatic charging will continue, the 7‑segment display indication shows the
current low pressure value and the status indication "
" intermittent.
If the 7‑segment display indication/user interface of indoor unit shows "
" code,
charging is almost finished. When the unit stops operating, close valve A
immediately and check whether the 7‑segment display indication/user interface of
indoor unit shows "
". This indicates the automatic charging in cooling program
was finished successfully.
INFORMATION
When the charging amount is little, the "
" code may not be displayed, but instead
the "
" code will be displayed immediately.
When the required (calculated) additional refrigerant amount is already charged
before "
" or "
" indication appears, close valve A and wait till "
" is displayed.
If during the cooling operation for the automatic refrigerant charge the ambient
conditions go beyond the allowable for this operation mode, the unit will indicate
on the 7‑segment display "
" in case indoor temperature is out of range or "
"
in case the outdoor temperature is out of range. In this case, when the additional
refrigerant charging was not finished, step
"6.7.6 Step 6a: To automatically charge
INFORMATION
▪
When a malfunction is detected during the procedure (e.g, in case of closed stop
valve), a malfunction code will be displayed. In that case, refer to
problems based on error codes"
116] and solve the malfunction accordingly.
Resetting the malfunction can be done by pushing BS1. The procedure can be
restarted from
"6.7.6 Step 6a: To automatically charge refrigerant"
72].
▪
Aborting the automatic refrigerant charge is possible by pushing BS1. The unit will
stop and return to idle condition.
Perform the test procedure as described in
108].
6.7.7 Step 6b: To manually charge refrigerant
The remaining additional refrigerant charge can be charged by operating the
outdoor unit by means of the manual refrigerant charge operation mode:
1
Take all the precautions mentioned in
84] and
2
Turn on the power of the indoor units and outdoor unit.