6
|
Installation
Installer and user reference guide
58
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10
d
Refrigerant R410A tank (siphon system)
e
Vacuum pump
f
Liquid line stop valve
g
Gas line stop valve
A
Valve A
B
Valve B
3
Recover gas and oil from the pinched piping by using a recovery unit.
CAUTION
Do not vent gases into the atmosphere.
4
When all gas and oil is recovered from the pinched piping, disconnect the
charge hose and close the service ports.
5
Cut off the lower part of the gas, liquid and equalising stop valve pipes along
the black line. Use an appropriate tool (e.g. a pipe cutter).
WARNING
Never remove the pinched piping by brazing.
Any gas or oil remaining inside the stop valve may blow off the pinched piping.
6
Wait until all oil has dripped out before continuing with the connection of the
field piping in case the recovery was not complete.