20
|
Configuration
Installer and user reference guide
103
RXYSQ4~6T8V/YB
VRV IV-S system air conditioner
4P482277-1B – 2020.10
#
Action
Button/display
2
Check the status of LED H6P.
H6P OFF: Unit is currently not
operating under low noise
restrictions.
H6P ON: Unit is currently operating
under low noise restrictions.
Example: 7‑LEDs display – Mode 1
You can read out setting [1‑5] (= the total number of connected indoor units) as
follows:
#
Action
Button/display
1
Start from the default situation.
2
Select mode 1.
BS1 [1×]
3
Select setting 5.
("X×" depends on the setting that
you want to select.)
BS2 [X×]
(= binary 5)
4
Display the value of setting 5.
(there are 8 indoor units
connected)
BS3 [1×]
(= binary 8)
5
Quit mode 1.
BS1 [1×]
20.2.6 To use mode 2
In mode 2 you can make field settings to configure the system.
Example: 7‑LEDs display – Mode 2
You can change the value of setting [2‑8] (= T
e
target temperature during cooling
operation) to 4 (= 8°C) as follows:
#
Action
Button/display
1
Start from the default situation.
2
Select mode 2.
BS1 [5 s]
3
Select setting 8.
("X×" depends on the setting that
you want to select.)
BS2 [X×]
(= binary 8)