Installation Manual
Installation of Outdoor Units
9
3. Installation Manual
3.1
RXYQ-TYDN, RXYQ-TTJU
3P362438-1B
3P362438-1B English
i
Safety considerations
Read these Safety considerations for Installation carefully be-
fore installing an air conditioner or heat pump. After complet-
ing the installation, make sure that the unit operates properly
during the startup operation.
Instruct the customer on how to operate and maintain the
unit.
Inform customers that they should store this Installation
Manual with the Operation Manual for future reference.
Always use a licensed installer or contractor to install this
product.
Improper installation can result in water or refrigerant leak-
CIGGNGEVTKECNUJQEMƂTGQTGZRNQUKQP
Meanings of
DANGER
,
WARNING
,
CAUTION
, and
NOTE
Symbols:
DANGER . . . . . . . .
Indicates an imminently hazardous
situation which, if not avoided, will
result in death or serious injury.
WARNING . . . . . . .
Indicates a potentially hazardous
situation which, if not avoided,
could result in death or serious
injury.
CAUTION . . . . . . . .
Indicates a potentially hazardous
situation which, if not avoided,
may result in minor or moderate
injury. It may also be used to alert
against unsafe practices.
NOTE . . . . . . . . . . .
Indicates situations that may result
in equipment or property-damage
accidents only.
INFORMATION . . .
6JKUU[ODQNKFGPVKƂGUWUGHWNVKRU
or additional information.
DANGER
r 4GHTKIGTCPVICUKUJGCXKGTVJCPCKTCPFTGRNCEGUQZ[IGP#
OCUUKXGNGCMYKNNTGUWNVKPQZ[IGPFGRNGVKQPGURGEKCNN[KP
DCUGOGPVUCPFCPCURJ[ZKCVKQPJC\CTFYKNNTGUWNVKPUGTK
-
ous injury or death.
r
Do not ground units to water pipes, gas pipes, telephone
wires, or lightning rods as incomplete grounding will result
a severe shock hazard resulting in severe injury or death.
Additionally, grounding to gas pipes will result a gas leak
CPFRQVGPVKCNGZRNQUKQPTGUWNVKPIKPUGXGTGKPLWT[QTFGCVJ
r
If refrigerant gas leaks during installation, ventilate the
area immediately. Refrigerant gas will result in producing
VQZKEICUKHKVEQOGUKPVQEQPVCEVYKVJƂTG'ZRQUWTGVQVJKU
gas will result in severe injury or death.
r
After completing the installation work, check that the re-
frigerant gas does not leak throughout the system.
r &QPQVKPUVCNNWPKVKPCPCTGCYJGTGƃCOOCDNGOCVGTKCNU
CTGRTGUGPVFWGVQTKUMQHGZRNQUKQPUVJCVYKNNTGUWNVKPUGTK
-
ous injury or death.
r
Safely dispose all packing and transportation materials
in accordance with federal/state/local laws or ordinances.
Packing materials such as nails and other metal or wood
parts, including plastic packing materials used for trans-
portation will result in injuries or death by suffocation.
WARNING
r 1PN[SWCNKƂGFRGTUQPPGNOWUVECTT[QWVVJGKPUVCNNCVKQP
work. Installation must be done in accordance with this
installation manual. Improper installation could result in
YCVGTNGCMCIGGNGEVTKEUJQEMQTƂTG
r
When installing the unit in a small room, take measures to
MGGRVJGTGHTKIGTCPVEQPEGPVTCVKQPHTQOGZEGGFKPICNNQY
-
CDNGUCHGV[NKOKVU'ZEGUUKXGTGHTKIGTCPVNGCMUKPVJGGXGPV
of an accident in a closed ambient space, could result in
QZ[IGPFGƂEKGPE[
r 7UGQPN[URGEKƂGFCEEGUUQTKGUCPFRCTVUHQTKPUVCNNCVKQP
YQTM(CKNWTGVQWUGURGEKƂGFRCTVUEQWNFTGUWNVKPYCVGT
NGCMCIGGNGEVTKEUJQEMUƂTGQTVJGWPKVHCNNKPI
r
Install the air conditioner or heat pump on a foundation
strong enough that it can withstand the weight of the unit.
#HQWPFCVKQPQHKPUWHƂEKGPVUVTGPIVJEQWNFTGUWNVKPVJGWPKV
falling and causing injuries.
r
Take into account strong winds, typhoons, or earthquakes
when installing. Improper installation could result in the
unit falling and causing accidents.
r
Make sure that a separate power supply circuit is pro-
vided for this unit and that all electrical work is carried
QWVD[SWCNKƂGFRGTUQPPGNCEEQTFKPIVQNQECNUVCVGCPF
PCVKQPCNTGIWNCVKQPU#PKPUWHƂEKGPVRQYGTUWRRN[ECRCEKV[
or improper electrical construction could result in electric
UJQEMUQTƂTG
r /CMGUWTGVJCVCNNYKTKPIKUUGEWTGFVJCVURGEKƂGFYKTGU
CTGWUGFCPFVJCVPQGZVGTPCNHQTEGUCEVQPVJGVGTOKPCN
connections or wires. Improper connections or installation
EQWNFTGUWNVKPƂTG
r 9JGPYKTKPIRQUKVKQPVJGYKTGUUQVJCVVJGEQPVTQNDQZ
cover can be securely fastened. Improper positioning of
VJGEQPVTQNDQZEQXGTEQWNFTGUWNVKPGNGEVTKEUJQEMUƂTGQT
the terminals overheating.
r
Before touching electrical parts, turn off the unit.
r
This equipment can be installed with a Ground-Fault Cir-
cuit Breaker (GFCI). Although this is a recognized mea-
sure for additional protection, with the grounding system in
North America, a dedicated GFCI is not necessary.
r
Securely fasten the unit terminal cover (panel). If the
terminal cover/panel is not installed properly, dust or
YCVGTOC[GPVGTVJGQWVFQQTWPKVCPFEQWNFTGUWNVKPƂTGQT
electric shock.
r
When installing or relocating the system, keep the refriger-
CPVEKTEWKVHTGGHTQOUWDUVCPEGUQVJGTVJCPVJGURGEKƂGF
refrigerant (R410A) such as air. Any presence of air or oth-
er foreign substance in the refrigerant circuit could result
in abnormal pressure rise or rupture, resulting in injury.
r
Do not change the setting of the protection devices. If the
pressure switch, thermal switch, or other protection device
is shorted and operated forcibly, or parts other than those
URGEKƂGFD[&CKMKPCTGWUGFƂTGQTGZRNQUKQPEQWNFTGUWNV
Summary of Contents for VRV IV RXYQ TYDN Series
Page 1: ...EDUS341411 N Installation...
Page 62: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 63 3P161697D...
Page 66: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 67 C 3P113151C 7 8 1 1 1 8...
Page 67: ...REFNET Joint and Header EDUS341411 N 68 Installation of Outdoor Units KHRP26M73HU 3P185500...
Page 68: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 69 3P185500...
Page 70: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 71 1P218719...
Page 71: ...REFNET Joint and Header EDUS341411 N 72 Installation of Outdoor Units 1P218719...
Page 72: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 73 1P218720...
Page 73: ...REFNET Joint and Header EDUS341411 N 74 Installation of Outdoor Units 1P218720...
Page 75: ...REFNET Joint and Header EDUS341411 N 76 Installation of Outdoor Units 1P280278A...
Page 76: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 77 1P280278A...
Page 77: ...REFNET Joint and Header EDUS341411 N 78 Installation of Outdoor Units 1P280279...
Page 79: ...Caution Label EDUS341411 N 80 Installation of Outdoor Units 2P361359C...
Page 80: ...EDUS341411 N Caution Label Installation of Outdoor Units 81 3P357947A...
Page 81: ...Caution Label EDUS341411 N 82 Installation of Outdoor Units 3P357947A...
Page 83: ...Caution Label EDUS341411 N 84 Installation of Outdoor Units 1P361833B...
Page 84: ...EDUS341411 N Caution Label Installation of Outdoor Units 85 1P361833B...
Page 85: ...Caution Label EDUS341411 N 86 Installation of Outdoor Units 1P361833B...
Page 86: ...EDUS341411 N Caution Label Installation of Outdoor Units 87 1P361833B...
Page 87: ...Caution Label EDUS341411 N 88 Installation of Outdoor Units 1P361833B...
Page 88: ...EDUS341411 N Caution Label Installation of Outdoor Units 89 1P361833B...
Page 89: ...Caution Label EDUS341411 N 90 Installation of Outdoor Units 3P357946A...
Page 90: ...EDUS341411 N Caution Label Installation of Outdoor Units 91 3P357946A...