EDUS341411-N
Installation Manual
Installation of Outdoor Units
41
3P362438-1B
31
3P362438-1B English
Perform the test procedure as described in 15.4.2. Test operation on
RCIG|
INFORMATION
r
When a malfunction is detected during the procedure (e.g., in case
of closed stop valve), a malfunction code will be displayed. In that
ECUGTGHGTVQ/CNHWPEVKQPEQFGNKUVQPRCIG|CPFUQNXG
the malfunction accordingly. Resetting the malfunction can be done
by pushing BS3. The procedure can be restarted from 6B).
r
Aborting the manual refrigerant charge is possible by pushing BS3.
The unit will stop and return to idle condition.
Information which may occur during additional refrigerant charging
procedures:
P8: Indoor unit freeze up prevention
Action:
Close valve A immediately. Reset malfunction by pushing
BS1. Retry auto charge procedure.
P2: Abnormal low pressure drop
Action:
Close valve A immediately. Reset malfunction by pushing
BS1. Check following items before retry auto charge procedure:
- Check if the gas side stop valve is opened correctly.
- Check if the valve of the refrigerant cylinder is opened.
- Check if the air inlet and outlet of the indoor units are not ob-
structed.
E-2
:
Indoor temperature is out of range.
E-3
:
Outdoor temperature is out of range.
E-5
: An indoor unit which is not compatible with automatic refrigerant
charge functionality is installed (e.g., Mini-split indoor unit, etc.)
1VJGTOCNHWPEVKQPEQFGENQUGXCNXG#KOOGFKCVGN[%QPƂTOVJGOCN
-
function code and take corresponding action, 15.5. Malfunction code
NKUVQPRCIG|
14.3.3.
Final charge adjustment
+VKUPQVPGEGUUCT[VQFQVJKUƂPCNCFLWUVOGPVPQTOCNN[DWVRGTHQTOVJG
following operation only when if the most adequate refrigerant for the
best performance is required.
The outdoor temperature must be between 60°F (16°C) and 97°F
|%
Purge gauge lines. Connect service gauge manifold to the service
port between the compressor and the reversing valve in each outdoor
unit. Run the system for 30 minutes in cooling by the forced operation
WUKPIVJGƂGNFUGVVKPIOQFG=?XCNWG1((104GHGTVQ
/QPKVQTKPIHWPEVKQPCPFƂGNFUGVVKPIUVQCNNQYRTGUUWTGUVQUVCDKNK\G
then check subcooling as detailed in the following sections.
Subcooling = Sat. Liquid Temp. – Liquid Line Temp.
1
Temporarily install a thermometer on the liquid line between the
EQKNCPFVJG'8KPGCEJQWVFQQTWPKV'PUWTGVJGVJGTOQOGVGT
makes adequate contact and is insulated for best possible read-
ings. Use liquid line temperature to determine sub cooling.
2
Check subcooling for each outdoor unit and calculate the average
subcooling of the outdoor unit. Systems should have a subcooling
of 11±3°F (6±2°C).
a. If average subcooling is low, add charge to raise subcooling to
(%6JGOCZKOWOCFFKVKQPCNEJCTIGKU|NDU
(2kg))
b.
If average subcooling is high, remove charge to lower the sub-
cooling to 11±3°F (6±2°C)
14.3.4. Checks after adding refrigerant
r
Are the stop valves for liquid and gas open?
r
Is the amount of refrigerant, that has been added, recorded on the
refrigerant charge label?
NOTE
Make sure to open all stop valves after (pre-) charging the refrigerant.
Operating with the stop valves closed will damage the compressor.
15.
5VCTVWRCPFEQPƂIWTCVKQP
INFORMATION
It is important that all information in this chapter is read sequentially by
VJGKPUVCNNGTCPFVJCVVJGU[UVGOKUEQPƂIWTGFCUCRRNKECDNG
DANGER: ELECTRICAL SHOCK
5GG5CHGV[EQPUKFGTCVKQPUQPRCIG|K
15.1. Checks before initial start up
#HVGTVJGKPUVCNNCVKQPQHVJGWPKVƂTUVEJGEMVJGHQNNQYKPIKVGOU1PEGCNN
DGNQYEJGEMUCTGHWNƂNNGFVJGWPKVOWUVDGENQUGFQPN[VJGPECPVJG
unit be powered up.
1
Installation
Check that the unit is properly installed, to avoid abnormal noises
and vibrations when starting up the unit.
Summary of Contents for VRV IV RXYQ TYDN Series
Page 1: ...EDUS341411 N Installation...
Page 62: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 63 3P161697D...
Page 66: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 67 C 3P113151C 7 8 1 1 1 8...
Page 67: ...REFNET Joint and Header EDUS341411 N 68 Installation of Outdoor Units KHRP26M73HU 3P185500...
Page 68: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 69 3P185500...
Page 70: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 71 1P218719...
Page 71: ...REFNET Joint and Header EDUS341411 N 72 Installation of Outdoor Units 1P218719...
Page 72: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 73 1P218720...
Page 73: ...REFNET Joint and Header EDUS341411 N 74 Installation of Outdoor Units 1P218720...
Page 75: ...REFNET Joint and Header EDUS341411 N 76 Installation of Outdoor Units 1P280278A...
Page 76: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 77 1P280278A...
Page 77: ...REFNET Joint and Header EDUS341411 N 78 Installation of Outdoor Units 1P280279...
Page 79: ...Caution Label EDUS341411 N 80 Installation of Outdoor Units 2P361359C...
Page 80: ...EDUS341411 N Caution Label Installation of Outdoor Units 81 3P357947A...
Page 81: ...Caution Label EDUS341411 N 82 Installation of Outdoor Units 3P357947A...
Page 83: ...Caution Label EDUS341411 N 84 Installation of Outdoor Units 1P361833B...
Page 84: ...EDUS341411 N Caution Label Installation of Outdoor Units 85 1P361833B...
Page 85: ...Caution Label EDUS341411 N 86 Installation of Outdoor Units 1P361833B...
Page 86: ...EDUS341411 N Caution Label Installation of Outdoor Units 87 1P361833B...
Page 87: ...Caution Label EDUS341411 N 88 Installation of Outdoor Units 1P361833B...
Page 88: ...EDUS341411 N Caution Label Installation of Outdoor Units 89 1P361833B...
Page 89: ...Caution Label EDUS341411 N 90 Installation of Outdoor Units 3P357946A...
Page 90: ...EDUS341411 N Caution Label Installation of Outdoor Units 91 3P357946A...