17
|
Piping installation
Installer and user reference guide
93
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1A – 2020.10
Refrigerant bottle
Connected to the service port for refrigerant charge.
This charges to both circuits, and to the compressor
unit's internal refrigerant piping.
Stop valves
Open
Compressor
Operates
5
Connect as shown. Make sure valve A is closed.
p< p>
R410A
a
c
b
A
d
RDXYQ
a
Weighing scales
b
Refrigerant R410A tank (siphon system)
c
Vacuum pump
d
Refrigerant charge port
A
Valve A
NOTICE
The refrigerant charging port is connected to the piping inside the unit. The unit's
internal piping is already factory charged with refrigerant, so be careful when
connecting the charge hose.
6
Open all compressor unit stop valves. At this point, valve A must remain
closed!
7
Take all the precautions mentioned in
107] and
129] into account.
8
Turn on the power of the indoor units, compressor unit and heat exchanger
unit.
9
Activate setting [2‑20] to start the manual additional refrigerant charge mode.
For details, see
Result:
The unit will start operation.
INFORMATION
The manual refrigerant charge operation will automatically stop within 30 minutes. If
charging is not completed after 30 minutes, perform the additional refrigerant
charging operation again.
INFORMATION
▪
When a malfunction is detected during the procedure (e.g., in case of closed stop
valve), a malfunction code will be displayed. In that case, refer to
94] and solve the malfunction accordingly.
Resetting the malfunction can be done by pushing BS3. You can restart the
"Charging" instructions.
▪
Aborting the manual refrigerant charge is possible by pushing BS3. The unit will
stop and return to idle condition.
10
Open valve A.
11
Charge refrigerant until the remaining determined additional refrigerant
amount is added, and then close valve A.