41
3P362438-5N English
Malfunction code
Contents
Solution
Main
code
Sub code
Master/sub 1/sub 2
F3
01/02/03
Reverse connection of high/low pressure gas pipe and
suction gas pipe of Branch Selector unit.
Check connection of high/low pressure gas pipe and
suction gas pipe.
01/03/05
Discharge temperature too high (R2T/R21T/R22T):
•
Stop valves are closed.
•
Refrigerant shortage.
•
Open stop valves.
•
Check refrigerant amount and recharge.
20/21/22
Compressor casing temperature too high (R14T):
•
Stop valves are closed.
•
Refrigerant shortage.
•
Open stop valves.
•
Check refrigerant amount and recharge.
F6
02
•
Stop valves are closed.
•
Refrigerant overcharge.
•
Open stop valves.
•
Check refrigerant amount and recharge.
F9
01
Electronic expansion valve malfunction (Branch Selec
-
tor units).
Check connection on printed circuit board or actuator.
02
05
H9
01/02/03
Temperature sensor malfunction
(R1T)-A1P (X18A)
Check connection on printed circuit board or actuator.
J3
16/22/28
Temperature sensor malfunction
(R2T, R21T)-A1P (X19A)
Check connection on printed circuit board or actuator.
17/23/29
Temperature sensor malfunction
(R2T, R21T)-A1P (X19A)
Check connection on printed circuit board or actuator.
18/24/30
Temperature sensor malfunction
(R22T)-A1P (X19A)
Check connection on printed circuit board or actuator.
19/25/31
Temperature sensor malfunction
(R22T)-A1P (X19A)
Check connection on printed circuit board or actuator.
47/49/51
Temperature sensor malfunction
(R14T)-A1P (X19A)
Check connection on printed circuit board or actuator.
48/50/52
Temperature sensor malfunction
(R14T)-A1P (X19A)
Check connection on printed circuit board or actuator.
J5
01/03/05
Temperature sensor malfunction
(R12T)-A8P (X15A)
Check connection on printed circuit board or actuator.
18/19/20
Temperature sensor malfunction
(R10T)-A1P (X29A)
Check connection on printed circuit board or actuator.
J6
01/02/03
Temperature sensor malfunction
(R11T)-A8P (X15A)
Check connection on printed circuit board or actuator.
08/09/10
Temperature sensor malfunction
(R8T)-A1P (X29A)
Check connection on printed circuit board or actuator.
11/12/13
Temperature sensor malfunction
(R9T)-A1P (X29A)
Check connection on printed circuit board or actuator.
J7
01/02/03
Temperature sensor malfunction
(R3T)-A1P (X30A)
Check connection on printed circuit board or actuator.
06/07/08
Temperature sensor malfunction
(R7T)-A1P (X30A)
Check connection on printed circuit board or actuator.
J8
01/02/03
Temperature sensor malfunction
(R4T)-A1P (X30A)
Check connection on printed circuit board or actuator.
08/09/10
Temperature sensor malfunction
(R5T)-A1P (X30A)
Check connection on printed circuit board or actuator.
11/12/13
Temperature sensor malfunction
(R15T)-A8P (X15A)
Check connection on printed circuit board or actuator.
J9
01/02/03
Temperature sensor malfunction
(R6T)-A1P (X30A)
Check connection on printed circuit board or actuator.
11/12/13
Temperature sensor malfunction
(R13T)-A8P (X17A)
Check connection on printed circuit board or actuator.
JA
06/08/10
High pressure sensor malfunction: open circuit
(S1NPH)-A1P (X32A)
Check connection on printed circuit board or actuator.
07/09/11
High pressure sensor malfunction: short circuit
(S1NPH)-A1P (X32A)
Check connection on printed circuit board or actuator.
01_EN_3P362438-5N.indb 41
12/11/2019 11:24:25 AM