• VRV Systems • Network Solution
8
4
Accessories
4 - 2 DEC102A51 - Digital input / output
4 - 2 - 2 External connection diagram
DEC102A51
3D047624
No.
❈
Wiring procedure
➀
<F1/F2> wiring between this equipment and centralized control equipment is required.
➁
The connection to the facility equipment and setting of various switches are required.
See the “Wiring with Facility equipment” paragraph.
➂
Connect the power supply and earth.
See the “Power Supply & Earth wiring” paragraph.
➂
For the wiring connection and clamping method, refer to the “Wiring lead-in” paragraph.
Power Supply
(1~200-240V)
switch
L
N
Fuse (10A)
DEC102A51
facility equipment
(4 numbers max.)
centralized
control
equipment
F1, F2
Wiring with Facility Equipment
<Caution> The length of wiring between this equipment and facility equipment is 100m max.
Operation output
It is possible to select continuous 1 output (4 points) or instantaneous 2 output (ON/OFF pair - 2 points).
• Wiring at Continuous Output (Up to 4 facility equipments can be connected.)
• Wiring at instantaneous Output (Up to 2 facility equipments can be connected.)
Operation input
When the contact is “Closed”, “Run” is to be input. Input SPEC: No-voltage “a” contact (When the applied voltage is 20 to 30V DC and the contact is “Closed”, the welding current is approx. 10mA.) For
input, use a contact for micro current. (12V DC, 1mA max.)
Abnormal input
When the contact is “Open” or “Closed”, “Error” is produced. Input specifications: No-voltage “a” contact (The welding current is approx. 10mA when the applied voltage is 20 to 30V DC and the contact
is “Closed”.) For input, use the contact for micro current. (12V DC, 1mA max.)
Terminal used in case where the switch was set to “Continuous Output” (Con.) or “Instantaneous Output” (Ins.)
Power Supply & Earth Wiring
For power supply, 1~200-240V is used. The wiring to the power terminal block (L/N) is required. The electric wire used should be 1.25 to 2.0mm
2
. After checking tht power supply specifications, make
correct connections.
Connect the earth wiring to the “
” terminal. Use a 2.0 mm
2
wire.
(Terminal size: M3.5)
Operation
command
Facility equipment operation circuit example
Remote
Local
Facility
equipment
protecting
device
Facility equipment
protecting device
Local
operation
Local
stop
DEC102A51
CD
K1R
K1R
K5R
K5R K3R
K4R
Q1M
Q1M
Q1M
S3S
S2S
S1S
D1~4
1~200-240V
1~200-240V
Output SPEC: No-voltage “a” contact
Voltage SPEC
Maximum current
Minimum current
200-240V
1.5A (Resistive Load)
10mA
DC5~24V
2A (Resistive Load)
10mA
(Terminal size: M3.5)
Operation
command
Stop command
Facility equipment operation circuit example
Remote
Local
Facility equipment
protecting device
Facility
equipment
protecting
device
Local
operation
Local
stop
DEC102A51
Output wiring for facility equipment 2
K1R
K2R
K1R
K5R
K5R
K2R
K5R K3R
K4R
Q1M
Q1M
S3S
S2S
S1S
D4
D3
CD
1~200-240V
(Terminal size: M3.5)
Operation
command
Stop command
DEC102A51
Output wiring for facility equipment 1
K1R
K2R
D2
D1
CD
1~200-240V
1~200-240V
Output SPEC: No-voltage “a” contact
Voltage SPEC
Maximum current
Minimum current
200-240V
1.5A (Resistive Load)
10mA
DC5~24V
2A (Resistive Load)
10mA
CM
K3R
M1~4
CA
K4R
A1~4
DEC102A51
DEC102A51
Facility equipment operating status input wiring
Facility equipment
operating status
Facility equipment
error status
Facility equipment error status input wiring
When the switch was set to “Ins.” (Instantaneous Output), the operation
input terminals M3, M4 and abnormal input terminals A3, A4 ar not used.
Facility equipment
(Up to 4 units can be connected to
single DEC102A51.)
Terminal used in the case of setting to “Continuous Output”
Run/Stop output
terminal
Operation input
terminal
Abnormal input
terminal
1st equipment
CD
D1
CM
M1
CA
A1
2nd equipment
CD
D2
CM
M2
CA
A2
3rd equipment
CD
D3
CM
M3
CA
A3
4th equipment
CD
D4
CM
M4
CA
A4
When the switch was set to “Ins.” (Instantaneous Output), the operation input terminals M3, M4
and abnormal input terminals A3, A4 are not used.
Facility equipment
(Up to 2 units can be connected to
single DEC102A51.)
Terminal used in the case or setting to “Instantaneous Output”
Operation
output terminal
Stop output
terminal
Operation input
terminal
Stop input
terminal
1st equipment
CD
D1
CD
C2
CM
M1
CA
A1
2nd equipment
CD
D2
CD
C4
CM
M2
CA
A2