![background image](http://html1.mh-extra.com/html/daikin/vrv-iii-s/vrv-iii-s_technical-data-manual_3358789005.webp)
•
• VRV Systems • Network Solution
4
3
Specifications
Item
Comments
PC
Performance
CPU
Pentium 800MHz or above recommended
Memory
256Mb or above
HDD
4GB minimum, 8GB or above recommended
Network
100 Base/T Ethernet
Operation
Keyboard, mouse, sound & speaker
SOFTWARE
Windows XP (Professional SP2 or later), Windows 2000 (Professional SP4 or later),
Internet explorer 7.0
CRT
SVGA
800 x 600, 1,024 x 768, 1,280 x 1,024
PRINTER
A4 page printer
NETWORK EQUIPMENT
Multi Port HUB (4 or more) ports
IPU (INTELLIGENT PROCESSING UNIT)
DAM602B51
256 indoor units per iPU
DAM602B52
128 indoor units per iPU
Back-up for power failure
Data are file into non volatile memory
Transmission
DIII-NET std: 1 line; Max. 4 lines / 1iPU
Power supply
AC100-240V,
±
10%, 50/60Hz, Max. 20W
Ambient temperature
-10 ~ +50
°
C
Ambient humidity
0~98% (condensation is not acceptable)
Dimensions
HxWxD
mm
281 x 260 x 78.5
Weight
kg
4
UPS (EG. APC SMART UPS 1,000)
Capacity
200~250W / 20min
Voltage
As required on the field
Control signals
Power failure signal (from UPS), UPS shut down signal (to iPU)/Power failure signal from UPS to both
iPU and PC
Relay
I/0 module (AP9610)