Troubleshooting by Indication on the Remote Controller
Si37-701
256
Troubleshooting
Troubleshooting
Ensure correct connection.
Ensure correct connection.
Replace the compressor.
Conclude the work
There is a possibility of defect
of pressure equalizing.
Check the refrigerant circuit.
Defect of pressure equalizing
Check the refrigerant circuit.
Replace the connecting wires and
ensure right connection of the
connector.
Local factor
Open the stop valve.
NO
NO
NO
NO
YES
NO
YES
NO
YES
NO
NO
NO
YES
YES
YES
YES
Check if
the stop valve is
open.
Power OFF
Power ON
Check if
the relay wires to the
compressor are
correct.
Check if the
connection of UVW
phase order is
correct.
Check if
the wiring is the
same as in the electric
wiring diagram.
The compressor
coil has disconnection
of wires.
Restart and
check the operation.
Check if the condition
occurs again.
Check if
the start mode is in
the high differential pressure
(not less than
0.5 MPa).
Check
if the inverter
output voltage between 3
phases is within
± 5V.
The insulation
resistance of the compressor
is low (not more than
100k
Ω
).
YES
YES
U
V
W
Check if the wiring has
any error in mistake for
inverter compressor.
Remove the connection between
the compressor and inverter. Set
the power transistor check mode
ON using “Setting mode 2” of the
outdoor unit PC board.
Measure the inverter output voltage
(
∗
2).
Note: Measurement should be made
while the frequency is stable.
Replace the inverter PC board.
Replace the inverter compressor.
∗
1: Pressure difference between high pressure and low pressure before starting.
∗
2: The quality of power transistors/ diode modules can be judged by executing
Check 4
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for VRV III REYQ10PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701 ...
Page 59: ...Specifications Si37 701 48 Specifications ...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit ...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219 ...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH ...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743 ...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742 ...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741 ...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A ...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C ...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E ...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E ...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E ...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A ...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359 ...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C ...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1 ...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B ...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D ...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C ...
Page 423: ...Piping Installation Point Si37 701 412 Appendix ...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix ...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix ...
Page 447: ...Si37 701 iv Index ...