Installation
EDUS391004-N
94
Installation of Outdoor Units
•
The Branch Selector units that combined with REYQ-P system for
changing the refrigerant flow to indoor units are BSVQ36 · 60 · 96P
type only. To combine with other type Branch Selector units will
cause malfunction.
•
The indoor units that combined with REYQ-P system for air
conditioning are Daikin VRV series indoor units that compatible
with R410A. To learn which indoor units are compatible with
R410A, refer to the product catalogs. To combine with other
refrigerant indoor unit will cause malfunction.
2-1 Combination
The system name and that independent units are as follows.
The system name
Independent units
REYQ144PBYD..................REMQ72PBYD
REMQ72PBYD
REYQ168PBYD/PBTJ........REMQ72PBYD/PBTJ
REMQ96PBYD/PBTJ
REYQ192PBYD/PBTJ........REMQ72PBYD/PBTJ
REMQ120PBYD/PBTJ
REYQ216PBYD/PBTJ........REMQ96PBYD/PBTJ
REMQ120PBYD/PBTJ
REYQ240PBYD/PBTJ........REMQ120PBYD/PBTJ
REMQ120PBYD/PBTJ
REYQ264PBYD/PBTJ........REMQ72PBYD/PBTJ
REMQ96PBYD/PBTJ
REMQ96PBYD/PBTJ
REYQ288PBYD/PBTJ........REMQ72PBYD/PBTJ
REMQ96PBYD/PBTJ
REMQ120PBYD/PBTJ
REYQ312PBYD/PBTJ........REMQ96PBYD/PBTJ
REMQ96PBYD/PBTJ
REMQ120PBYD/PBTJ
REYQ336PBYD/PBTJ........REMQ96PBYD/PBTJ
REMQ120PBYD/PBTJ
REMQ120PBYD/PBTJ
The indoor units can be installed in the following range.
Outdoor unit
Total capacity index of indoor units
REYQ144PBYD
72 ~ 187
REYQ168PBYD/PBTJ
84 ~ 218
REYQ192PBYD/PBTJ
96 ~ 249
REYQ216PBYD/PBTJ
108 ~ 280
REYQ240PBYD/PBTJ
120 ~ 312
REYQ264PBYD/PBTJ
132 ~ 343
REYQ288PBYD/PBTJ
144 ~ 374
REYQ312PBYD/PBTJ
156 ~ 405
REYQ336PBYD/PBTJ
168 ~ 436
•
For installing the 2 or 3 units multi system, Outdoor unit multi
connection piping kit is required. See “2-3 Option accessory”.
•
If the total capacity of the connected indoor units exceeds the
capacity of the outdoor unit, cooling and heating performance may
drop when running the indoor units. See the capacity table in the
Engineering Data Book for details.
2-2 Standard supplied accessories
Confirm the following accessories are included. The storage location
of the accessories is shown in figure 1.
NOTE
Do not throw away any of the accessories until installation is
complete. They are needed for installation work.
(Refer to figure 1)
1.
Clamps, Manuals, etc.
2.
Accessory pipes
2 pcs.
1 pc.
Clamp(1)
(Large)
8 pcs.
Clamp(2)
4 pcs.
Vinyl tube
(Small)
Quantity
Clamp(3)
Name
Shape
2 pcs.
1 pc. each
Conduit mounting plate
2 pcs.
Quantity
Manuals, etc.
Name
Shape
•
Operation manual
•
Installation manual
•
“REQUEST FOR THE INDICATION”
label (Installation records)
HP / LP gas
side accessory
pipe (1)
HP / LP gas
side accessory
pipe (2)
1 pc.
2 pcs.
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
2 pcs.
2 pcs.
φ
7/8
φ
1-1/8
φ
7/8
φ
1-1/8
φ
3/4
φ
7/8
φ
7/8
φ
3/4
φ
1
φ
3/4
Liquid side
accessory
pipe (1)
Liquid side
accessory
pipe (2)
Suction gas
side accessory
pipe (1)
Suction gas
side accessory
pipe (2)
Equalizer side
accessory pipe
(1)
L type
accessory
joint (1)
L type
accessory
joint (2)
Equalizer side
accessory pipe
(2)
1 pc.
1 pc.
Quantity
Shape
Name
72 · 96P type
120P type
Shape
72 · 96P type
Name
120P type
Quantity
3P215731-11R
Summary of Contents for VRV III REMQ72PBYD
Page 1: ...EDUS 391004 N AMERICAS AMERICAS Installation...
Page 24: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 23 1P218719...
Page 25: ...REFNET Pipe System EDUS391004 N 24 Installation of Outdoor Units 1P218720...
Page 26: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 25 1P218720...
Page 28: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 27 1P280278A...
Page 29: ...REFNET Pipe System EDUS391004 N 28 Installation of Outdoor Units 1P280278A...
Page 30: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 29 1P280279...
Page 33: ...REFNET Pipe System EDUS391004 N 32 Installation of Outdoor Units 1P218714...
Page 34: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 33 1P218714...
Page 35: ...REFNET Pipe System EDUS391004 N 34 Installation of Outdoor Units 1P218715...
Page 36: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 35 1P218715...
Page 38: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 37 3D071080...
Page 39: ...REFNET Pipe System EDUS391004 N 38 Installation of Outdoor Units 1P280510A...
Page 40: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 39 1P280510A...
Page 41: ...REFNET Pipe System EDUS391004 N 40 Installation of Outdoor Units 1P280511A...
Page 42: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 41 1P280511A...
Page 113: ...EDUS391004 N Field Setting Installation of Outdoor Units 113 2P281604A...
Page 114: ...Field Setting EDUS391004 N 114 Installation of Outdoor Units 2P281604A...
Page 115: ...EDUS391004 N Field Setting Installation of Outdoor Units 115 2P281604A...
Page 116: ...Field Setting EDUS391004 N 116 Installation of Outdoor Units 2P281604A...
Page 121: ...EDUS391004 N Field Setting Installation of Outdoor Units 121 2P281605A...
Page 122: ...Field Setting EDUS391004 N 122 Installation of Outdoor Units 2P281605A...
Page 124: ...Field Setting EDUS391004 N 124 Installation of Outdoor Units 2P281605A...
Page 129: ......