
EDUS391004-N
Installation
Installation of Outdoor Units
57
7-3 Leading wire Procedure
•
The power wiring and ground wiring are passed out from the power
wiring hole on the front (knock hole).
•
The transmission wiring is passed out from the wiring hole (knock
hole) on the front of the unit.
(Refer to figure 18-1)
1.
Electric wiring diagram
Printed on the back of the electrical components box lid.
2.
Knockout hole
3.
Power line
4.
Transmission line
(Refer to figure 18-2)
1.
Electrical components box lid
2.
Service lid
3.
[Service precautions] Label location
NOTE
•
Open the knock holes with a hammer or the like.
•
After knocking out the holes, we recommend you remove any burrs
and paint them using the repair paint to prevent rusting.
(Refer to figure 18-1, 2)
•
When passing wiring through the knock holes, remove burrs
around the knock holes and protect the wiring with protective tape.
(Refer to figure 18-1, 2)
•
If small animals might enter the unit, block off any gaps (hatching
parts in figure 18-1, 2) with material (field supply).
7-4 Transmission Wiring Connection Procedure
•
Referring to figure 19, connect the transmission wiring between
outdoor unit and indoor unit, outdoor unit and outdoor unit of other
system, outdoor unit and outdoor unit of same system.
(Refer to figure 19)
1.
Master unit (*)
2.
Sub unit (*)
3.
Outdoor unit A
4.
Outdoor unit B
5.
Electrical components box (1)
6.
(Only RXYQ~PBYD)
Electrical components box (2)
7.
(Only RXYQ144PBTJ)
Do not open the electrical components box (2) lid.
(There is no work when installation)
8.
Never connect the power wire.
9.
To outdoor unit of other system
10.
Use duplex wires (No polarity)
11.
Indoor unit
(*) : The Outdoor unit that connects the transmission wiring to
an indoor unit is Master unit of the multi system.
And the other units are Sub unit. (In this figure, Outdoor
unit A is the Master unit.)
Check operation in installation work, Onsite settings and
so on are done by operating the PC-board (A1P) of Master
unit.
NOTE
•
Do not connect the power wiring to terminals for the transmission
wiring. Doing so would destroy the entire system.
•
When connecting wires to the terminal block on the PC-board, too
much heat or tightening could damage the PC-board. Attach with
care.
See the table below for the tightening torque of the transmission
wiring terminals.
•
Transmission wiring (About the symbol
~
,
see figure 19
)
should be done within the following limitations.
If they are exceeded, transmission problems may occur.
Between outdoor unit and indoor unit
Between outdoor unit and outdoor unit of other systems
Max. wiring length
: 3280 ft
Max. total wiring length
: 6560 ft
Max. no. of branches
: 16
[Note]
No branch is allowed after branch (
See figure 20
)
Max. no. of outdoor units of other system
that can be connected
: 10
(Refer to figure 20)
1.
Branch
2.
Branch after branch
Between outdoor unit and outdoor unit of same system
Max. wiring length
: 100 ft
•
The transmission wiring inside the electrical components box
should be secured using the clamp (1) as shown in figure 21.
(Refer to figure 21)
1.
In the electrical components box
2.
Retain to the electrical components box with the accessory
clamp (1).
3.
Vinyl tube (accessory)
•
Outside the units, the transmission wiring must be finished
simultaneously with the local refrigerant piping, and wound with
tape (field supply) as shown in figure 22.
(Refer to figure 22)
1.
Liquid pipe
2.
Gas pipe
3.
Transmission wiring
4.
Insulation material
5.
Finishing tape
•
For multi system:
1. Transmission wiring between outdoor units in the same piping
system must be connected to terminals Q1 and Q2 (TO MULTI
UNIT).
Connecting the wires to the F1, F2 (TO OUT/D UNIT) terminals
results in system malfunction.
2. Wiring to other systems should be connected to terminals F1
and F2 (TO OUT/D UNIT) on the PC-board of the master unit.
The outdoor unit that connects transmission wiring to indoor
unit is the master unit. The others are sub unit.
7-5 Power Wiring Connection Procedure
•
Be sure to connect the power supply wiring to the power supply
terminal block and hold it in place using the included clamp as
shown in the figure 23.
•
The L1, L2 and L3 phases of the power wiring should be secured
separately to the hook using the included clamp (1).
•
The ground wiring should be bound to the power wiring using the
included clamp (1) to prevent outside force from being applied to
the terminal area.
(Refer to figure 23)
1.
Power supply
(MODEL PBYD : 3 ~ 460V 60Hz)
(MODEL PBTJ : 3 ~ 208/230V 60Hz)
2.
Ground leakage circuit breaker
3.
Branch switch, Overcurrent breaker
4.
Ground wire
5.
Electrical components box (1)
6.
(Only RXYQ~PBYD and RXYQ144PBTJ)
Electrical components box (2)
7.
(Only RXYQ~PBYD and RXYQ144PBTJ)
Do not open the electrical components box (2) lid.
(There are no work when installation.)
8.
Attach insulation sleeves
9.
Power supply terminal block
10.
Ground terminal
11.
Clamp (1) (accessory)
12.
Vinyl tube (accessory)
Screw size
Tightening torque (ft · lbf)
M3.5 (A1P)
0.59 ~ 0.71
1
2
1
2
3P215731-10R
Summary of Contents for VRV III REMQ72PBYD
Page 1: ...EDUS 391004 N AMERICAS AMERICAS Installation...
Page 24: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 23 1P218719...
Page 25: ...REFNET Pipe System EDUS391004 N 24 Installation of Outdoor Units 1P218720...
Page 26: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 25 1P218720...
Page 28: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 27 1P280278A...
Page 29: ...REFNET Pipe System EDUS391004 N 28 Installation of Outdoor Units 1P280278A...
Page 30: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 29 1P280279...
Page 33: ...REFNET Pipe System EDUS391004 N 32 Installation of Outdoor Units 1P218714...
Page 34: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 33 1P218714...
Page 35: ...REFNET Pipe System EDUS391004 N 34 Installation of Outdoor Units 1P218715...
Page 36: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 35 1P218715...
Page 38: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 37 3D071080...
Page 39: ...REFNET Pipe System EDUS391004 N 38 Installation of Outdoor Units 1P280510A...
Page 40: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 39 1P280510A...
Page 41: ...REFNET Pipe System EDUS391004 N 40 Installation of Outdoor Units 1P280511A...
Page 42: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 41 1P280511A...
Page 113: ...EDUS391004 N Field Setting Installation of Outdoor Units 113 2P281604A...
Page 114: ...Field Setting EDUS391004 N 114 Installation of Outdoor Units 2P281604A...
Page 115: ...EDUS391004 N Field Setting Installation of Outdoor Units 115 2P281604A...
Page 116: ...Field Setting EDUS391004 N 116 Installation of Outdoor Units 2P281604A...
Page 121: ...EDUS391004 N Field Setting Installation of Outdoor Units 121 2P281605A...
Page 122: ...Field Setting EDUS391004 N 122 Installation of Outdoor Units 2P281605A...
Page 124: ...Field Setting EDUS391004 N 124 Installation of Outdoor Units 2P281605A...
Page 129: ......