
EDUS391004-N
Installation
Installation of Outdoor Units
109
[Automatic refrigerant charging operation procedure]
NOTE
•
The marks of LED mean as follows.
h
: OFF
i
: ON
j
: Blinking
: OFF, ON or Blinking
(1) Open the liquid pipe, suction gas pipe and HP/LP gas pipe shutoff
valves. (The valve A~C must be closed. See figure 31.)
(2)
Close the electrical components box (1) lid and all front panel
except on the electrical components box (1) side. (*1) And turn
the power to the outdoor unit and all connected BS, indoor units.
(*2)
•
After H2P stop blinking (about 12 minutes after turning on the
power), check H2P is OFF.
If H2P is ON, check the malfunction code in the remote controller
of indoor unit and correct the malfunction in accordance with
[Remote controller display malfunction code] in chapter 11-2-2.
(3) Check the LED. And push the MODE button (BS1) once if the LED
displays is not as below.
(4) Push the TEST button (BS4) once. (The LED displays will change
as below.)
(5) Hold the TEST button (BS4) down for 5 seconds or more.
(The LED displays will change as below and fan of outdoor unit will
start rotation.)
(6) When the compressor start working and the LED displays change
any state in below (*3), go to “In case of cooling mode” or “In case
of heating mode” in accordance with the LED displays.
In case of cooling mode
(7) Push the TEST button (BS4) once within 5 minutes after
procedure (5) (*4) and close the all front panels (*5).
After that, open the valve A immediately (See figure 31) (*6) and
watch the remote controller display of indoor unit.
(8) If the remote controller display shows “PE” code (*7), ready to
close the valve A.
And go to procedure (9).
If the remote controller display shows other code, close the valve A
immediately and refer to [Remote controller cooling mode
malfunction code]
Beware the fan running when open the front panel.
The fan may continue rotation after the system stop the
operation.
(9) When the compressor stop working (the fan may continue
rotation.), close the valve A immediately (*8).
And check the LED displays are as below and the remote
controller display shows “P9” code.
After checking, push the MODE button (BS1) once and the
charging is complete.
In case of heating mode
(7) Push the TEST button (BS4) once within 5 minutes after
procedure (5) (*4) and close the all front panels.
After that, open the valve A immediately (See figure 31) (*6) and
check the charged amount by measuring device.
During operation, if the remote controller display shows “P2” or
“P8” code, close the valve A immediately and refer to [Remote
controller heating mode malfunction code].
Beware the fan running when open the front panel.
The fan may continue rotation after the system stop the
operation.
(8) When the required amount of refrigerant is charged, close the
valve A (See figure 31) (*8) and push the RETURN button (BS3)
once. And then go to procedure (9).
(9) Push the MODE button (BS1) once, and the charging is complete.
Notes (*1)~(*8)
(*1) Lead the refrigerant charge hose etc from the pipe intake.
All front panels must be closed at the procedure (7).
(*2)
If you perform the refrigerant charging operation within the
refrigerant system that have the power off unit, the operation
cannot finish properly.
Check the number of outdoor and indoor units that is powered.
For checking, see [How to check how many units are connected]
in chapter 11-1.
•
To energize the crankcase heater, make sure to turn on for
6 hours before starting operation.
(*3) It takes about 2~10 minutes for getting stability of refrigerant
state.
If the additional refrigerant is little and operation is started before
getting stability, the system can not judge the charging amount
precisely and it cause over charge.
(*4) If the TEST button (BS4) is not pushed within 5 minutes, “P2”
code will displayed in the remote controller. In this case, refer
[Remote controller cooling (or heating) mode malfunction code].
(*5) If the front panel is opened during the operation, the system
cannot operate properly.
(*6) If you leave the system without connecting the refrigerant tank or
opening the valve A for 30 minutes or more, the system stop
operation and “P2” code are displayed in remote controller.
In this case, refer [Remote controller cooling (or heating) mode
malfunction code].
(*7) Depending on the situation of operation such as the charging
amount is little, the “PE” code may not be displayed and the “P9”
code may be displayed.
(*8) Always close the valve A and take the tank off.
The refrigerant charge port of this unit have electric expansion
valve and the valve are closed when charging is finished.
However, the valve will opened when other operation (Check
operation, normal operation, etc.). If you leave the tank
connected, the refrigerant will charged and it cause over charge.
[Remote controller cooling mode malfunction code]
H1P H2P H3P H4P H5P H6P H7P
h
h
i
h
h
h
h
H1P H2P H3P H4P H5P H6P H7P
i
i
i
i
i
i
i
H1P H2P H3P H4P H5P H6P H7P
h
j
h
h
h
H1P H2P H3P H4P H5P H6P H7P
j
j
j
h
i
h
i
Go to “In case of
cooling mode”
j
j
h
h
i
h
i
Go to “In case of
heating mode”
H1P H2P H3P H4P H5P H6P H7P
i
j
j
i
i
i
i
Code
The work contents
PE
Charging is almost finished. Ready to close the valve A.
PA
PH
The refrigerant tank is empty. Close the valve A and replace
empty tank to the new tank. After changing the tank, open
the valve A again.
Beware the fan running. The outdoor unit does not
stop operation.
P8
Close the valve A immediately, and restart the operation
from procedure (3).
P2
Operation is interrupted. Close the
valve A immediately and check the
below items.
•
Check if HP/LP gas pipe, suction
gas pipe or liquid pipe shutoff
valve is opened.
•
Check the refrigerant tank is
connected and the valve A was
opened.
•
Check if the air inlet and outlet of
the indoor unit are not closed by
an obstruction.
After correcting the
abnormality, restart
the operation from
procedure (3).
*
Operation is stopped abnormally. Close
the valve A immediately. Confirm the
malfunction code and correct the
abnormality following the [Remote
controller displays malfunction code] in
chapter 11-2-2.
P9
Charging is finished. Close the valve A and take the
refrigerant tank off.
3P215731-11R
Summary of Contents for VRV III REMQ72PBYD
Page 1: ...EDUS 391004 N AMERICAS AMERICAS Installation...
Page 24: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 23 1P218719...
Page 25: ...REFNET Pipe System EDUS391004 N 24 Installation of Outdoor Units 1P218720...
Page 26: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 25 1P218720...
Page 28: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 27 1P280278A...
Page 29: ...REFNET Pipe System EDUS391004 N 28 Installation of Outdoor Units 1P280278A...
Page 30: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 29 1P280279...
Page 33: ...REFNET Pipe System EDUS391004 N 32 Installation of Outdoor Units 1P218714...
Page 34: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 33 1P218714...
Page 35: ...REFNET Pipe System EDUS391004 N 34 Installation of Outdoor Units 1P218715...
Page 36: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 35 1P218715...
Page 38: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 37 3D071080...
Page 39: ...REFNET Pipe System EDUS391004 N 38 Installation of Outdoor Units 1P280510A...
Page 40: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 39 1P280510A...
Page 41: ...REFNET Pipe System EDUS391004 N 40 Installation of Outdoor Units 1P280511A...
Page 42: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 41 1P280511A...
Page 113: ...EDUS391004 N Field Setting Installation of Outdoor Units 113 2P281604A...
Page 114: ...Field Setting EDUS391004 N 114 Installation of Outdoor Units 2P281604A...
Page 115: ...EDUS391004 N Field Setting Installation of Outdoor Units 115 2P281604A...
Page 116: ...Field Setting EDUS391004 N 116 Installation of Outdoor Units 2P281604A...
Page 121: ...EDUS391004 N Field Setting Installation of Outdoor Units 121 2P281605A...
Page 122: ...Field Setting EDUS391004 N 122 Installation of Outdoor Units 2P281605A...
Page 124: ...Field Setting EDUS391004 N 124 Installation of Outdoor Units 2P281605A...
Page 129: ......