4
HXY48TAVJU EDUS392021-F18
3. System Layout
3.1 System Layout
Refrigerant piping
VRV
indoor unit
Total capacity of connected
VRV
indoor unit
requires at least
50%
of outdoor unit capacity.
Cold water / Hot water
Heat exchange
between refrigerant
and water
Underfloor heating
Radiator
Ceiling radiator
Low-temperature
hydrobox
The following table indicates the connectable number and capacity range of the low-temperature hydrobox and indoor units.
Please refer the dedicated Engineering Data Book for the specification of respective indoor units.
ton
6
8
10
12
14
Minimum
VRV
indoor unit number
1
Minimum
VRV
indoor unit capacity ratio
50% or more
Max hydrobox number
1
1
2
2
2
Total indoor capacity ratio range
50-130%
3.2 Connection Ratio
When connecting the low-temperature hydrobox, connect
VRV
indoor units of its total capacity at least 50% of the outdoor unit capability to prevent
the secondary side water temperature from dropping or freezing during defrosting or ON/OFF of the indoor unit.
Summary of Contents for VRV HXY48TAVJU
Page 1: ...Low temperature hydrobox HXY48TAVJU EDUS392021 F18 202009 Engineering Data 60 Hz...
Page 2: ......
Page 9: ...7 HXY48TAVJU EDUS392021 F18 6 Dimensions HXY48TAVJU 3D128656 Unit in mm...
Page 11: ...9 HXY48TAVJU EDUS392021 F18 8 Wiring Diagrams HXY48TAVJU C 3D128650...
Page 15: ...13 HXY48TAVJU EDUS392021 F18 11 Capacity...
Page 16: ...14 HXY48TAVJU EDUS392021 F18 12 Center of Gravity HXY48TAVJU 4D129458...
Page 25: ......
Page 26: ......
Page 27: ......