HXY48TAVJU EDUS392021-F18
9. Electric Characteristics
HXY48TAVJU
Model
Power supply
Pump
Hz
Volts
Voltage range
MCA
MOP
Input (W)
HXY48TAVJU
60
208/230 V
Max. 253 V
Min. 187 V
2.5
15
135
Symbol:
MCA: Min. Circuit Amps (A)
MOP: Max. Overcurrent Protective Device (A)
Note:
1. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit is not below or above listed range limits.
2. Maximum allowable voltage unbalance between phases is 2%.
3. Select wire size based on the MCA.
4. Instead of fuse, use circuit breaker.
C: 4D129499