21
|
Configuration
Installer and user reference guide
80
FXHA-A
VRV system air conditioner
4P673749-1A – 2022.11
F2
T1
OFF
FORCED
T2
Input A
b
a
a
Forced OFF
b
Input A
Wiring requirements
Wiring specification
Only use harmonized wire providing
double insulation and suitable for
applicable voltage
2-core cable
Wiring size
Minimum 0.75 mm
2
Wiring length
Maximum 100 m
External contact specification
Contact that can make and break the
min. load of DC15 V · 1 mA
This setting must correspond with the needs of the user.
If you want to change increments to…
Then
(1)
M
SW
—
Forced OFF
12 (22)
1
01
ON/OFF Operation
02
Emergency (recommended for alarm operation)
03
Forced OFF - multi tenant
04
Interlocking setting A
05
Interlocking setting B
06
(1)
Field settings are defined as follows:
•
M
: Mode number –
First number
: for group of units –
Number between brackets
: for individual unit
•
SW
: Setting number
•
—: Value number
•
: Default