background image

17 Configuration

Installation and operation manual

36

RXYSA4~6A7V/Y1B

VRV 5-S system air conditioner

4P600329-1A – 2020.01

17.1.4

To access mode 1 or 2

Initialisation: default situation

NOTICE

Be  sure  to  turn  on  the  power  6  hours  before  operation  in
order  to  have  power  running  to  the  crankcase  heater  and
to protect the compressor.

Turn  on  the  power  supply  of  the  outdoor  unit  and  all  indoor  units.
When the communication between indoor units and outdoor unit(s) is
established  and  normal,  the  7‑segment  display  indication  state  will
be as below (default situation when shipped from factory).

Stage

Display

When turning on the power supply: flashing as
indicated. First checks on power supply are
executed (1~2 min).

When no trouble occurs: lighted as indicated
(8~10 min).

Ready for operation: blank display indication as
indicated.

7‑segment display indications:

Off
Blinking
On

In  case  of  malfunction,  the  malfunction  code  is  displayed  on  the
indoor  unit  user  interface  and  the  outdoor  unit  7‑segment  display.
Solve  the  malfunction  code  accordingly.  The  communication  wiring
should be checked at first.

Access

BS1  is  used  to  switch  between  the  default  situation,  mode  1  and
mode 2.

Access

Action

Default situation

Mode 1

Push BS1 one time.

7‑segment display indication changes to:

.

Push BS1 one more time to return to the
default situation.

Mode 2

Push BS1 for at least 5 seconds.

7‑segment display indication changes to:

Push BS1 one more time (shortly) to return to
the default situation.

INFORMATION

If you get confused in the middle of the process, push BS1
to  return  to  the  default  situation  (no  indication  on
7‑segment  displays:  blank,  refer  to 

"17.1.4  To  access

mode 1 or 2" 

[

4

 36].

17.1.5

To use mode 1

Mode 1 is used to set basic settings and to monitor the status of the
unit.

What

How

Changing and accessing
the setting in mode 1

Once mode 1 is selected (push BS1
one time), you can select the wanted
setting. It is done by pushing BS2.

Accessing the selected setting's value is
done by pushing BS3 one time.

What

How

To quit and return to the
initial status

Press BS1.

17.1.6

To use mode 2

The  master  unit  should  be  used  to  input  field  settings  in
mode 2.

Mode 2 is used to set field settings of the outdoor unit and system.

What

How

Changing and accessing
the setting in mode 2

Once mode 2 is selected (push BS1 for
more than 5 seconds), you can select
the wanted setting. It is done by pushing
BS2.

Accessing the selected setting's value is
done by pushing BS3 1 time.

To quit and return to the
initial status

Press BS1.

Changing the value of the
selected setting in mode 2

▪ Once  mode  2  is  selected  (push  BS1

for  more  than  5  seconds)  you  can
select  the  wanted  setting.  It  is  done
by pushing BS2.

▪ Accessing the selected setting's value

is done by pushing BS3 1 time.

▪ Now  BS2  is  used  to  select  the

required value of the selected setting.

▪ When  the  required  value  is  selected,

you  can  define  the  change  of  value
by pushing BS3 1 time.

▪ Press  BS3  again  to  start  operation

according to the chosen value.

17.1.7

Mode 1: Monitoring settings

[1‑1]

Shows the status of low noise operation.

[1‑1]

Description

0

Unit is currently not operating under low noise
restrictions.

1

Unit is currently operating under low noise
restrictions.

[1‑2]

Shows the status of power consumption limitation operation.

[1‑2]

Description

0

Unit is currently not operating under power
consumption limitations.

1

Unit is currently operating under power
consumption limitation.

[1‑5] [1‑6]

Shows:

▪ [1‑5]: The current T

e

 target parameter position.

▪ [1‑6]: The current T

c

 target parameter position.

[1‑10]

Shows the total number of connected indoor units.

[1‑17] [1‑18] [1‑19]

Shows:

▪ [1‑17]: The latest malfunction code.

▪ [1‑18]: The 2nd last malfunction code.

▪ [1‑19]: The 3rd last malfunction code.

Summary of Contents for VRV 5-S Series

Page 1: ...llation and operation manual VRV 5 S system air conditioner English Installation and operation manual VRV 5 S system air conditioner RXYSA4A7V1B RXYSA5A7V1B RXYSA6A7V1B RXYSA4A7Y1B RXYSA5A7Y1B RXYSA6A...

Page 2: ...HD HU 200 1000 1000 500 HD HU A B C 200 1 300 1000 A B C E 200 1 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 250 1500 300 1500 B D E HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 50...

Page 3: ...30 7 d 92 36 0 c 31 0 d 93 36 4 c 31 4 d 94 36 7 c 31 7 d 95 37 0 c 32 0 d 96 37 4 c 32 4 d 97 37 7 c 32 7 d 98 38 0 c 33 0 d 99 38 4 c 33 4 d 100 38 7 c 33 7 d 63 26 2 c 21 2 d 64 26 6 c 21 6 d 65 26...

Page 4: ...1 12 13 14 15 16 17 Direktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je i...

Page 5: ...vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota...

Page 6: ...ioners Indoor unit outdoor unit 21 8 2 11 Symptom Noise of air conditioners Outdoor unit 21 8 2 12 Symptom Dust comes out of the unit 21 8 2 13 Symptom The units can give off odours 21 8 2 14 Symptom...

Page 7: ...rope com support and manuals product information Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer The original documentation is written...

Page 8: ...nce with the instructions from this manual See 15 Electrical installation 431 WARNING ALWAYS use multicore cable for power supply cables WARNING If the power supply has a missing or wrong N phase equi...

Page 9: ...se potential sources of ignition in searching for or detection of refrigerant leaks NOTICE Do NOT re use joints which have been used already Joints made in installation between parts of refrigerant sy...

Page 10: ...ecautions it is mandatory to install one of the following devices at a location with 24 hour monitoring a supervisor remote controller or an iTM with external alarm via WAGO module Note The remote con...

Page 11: ...or room 2 1 3 To determine the charge limitations 1 Determine the area of the smallest room in order to derive the total refrigerant charge limit in the system The room area can be determined by proje...

Page 12: ...for room with the smallest area on the lowest underground floor The maximum allowable charge has to be assessed for the room with the smallest room area in both the lowest underground floor and the o...

Page 13: ...h c to check the maximum allowed charge for a room of 16 m with a ceiling mounted unit 10 4 kg Use graph d to check the maximum allowed charge for the smallest room 28 m of the lowest underground floo...

Page 14: ...must be done by an authorized installer and must comply with applicable legislation Units must be treated at a specialized treatment facility for reuse recycling and recovery By ensuring this product...

Page 15: ...4 About the system The VRV 5 S uses R32 refrigerant which is rated as A2L and is mildly flammable For compliance with the requirements for enhanced tightness refrigerating systems and IEC60335 2 40 th...

Page 16: ...may stop immediately This is not a malfunction 6 2 3 About the heating operation It may take longer to reach the set temperature for general heating operation than for cooling operation The following...

Page 17: ...g NOTICE Do not turn off power immediately after the unit stops but wait for at least 5 minutes 6 3 3 To use the dry program WITH cool heat changeover remote control switch To start 1 Select cooling o...

Page 18: ...e displays of other user interfaces show change over under centralised control 7 Maintenance and service NOTICE Never inspect or service the unit by yourself Ask a qualified service person to perform...

Page 19: ...leshooting If one of the following malfunctions occur take the measures shown below and contact your dealer WARNING Stop operation and shut off the power if anything unusual occurs burning smells etc...

Page 20: ...r malfunction Discharge temperature sensor malfunction outdoor Suction temperature sensor malfunction outdoor De icing temperature sensor malfunction outdoor Liquid temperature sensor after subcool HE...

Page 21: ...tween the units causing them to stop Operation automatically restarts when the noise ceases 8 2 9 Symptom Noise of air conditioners Indoor unit A zeen sound is heard immediately after the power supply...

Page 22: ...ecycling and recovery For the installer 11 About the box 11 1 Outdoor unit 11 1 1 To unpack the outdoor unit 2 1 11 1 2 To handle the outdoor unit CAUTION To avoid injury do NOT touch the air inlet or...

Page 23: ...sound pressure level is less than 70 dBA CAUTION Appliance NOT accessible to the general public install it in a secured area protected from easy access This unit is suitable for installation in a comm...

Page 24: ...l the outdoor unit 4 M12 12 3 3 To provide drainage INFORMATION If necessary you can use a drain pan field supply to prevent drain water from dripping NOTICE If the unit CANNOT be installed fully leve...

Page 25: ...the piping size Determine the proper size using the following tables and reference figure only for indication A B 1 B 2 C 1 C 2 C 3 C 4 1 3 1 3 2 3 3 3 4 VRV DX 2 2 2 1 Outdoor unit 2 Refrigerant bra...

Page 26: ...ollowing table in accordance with the total capacity of all the indoor units connected below the refnet header Indoor unit capacity index Refrigerant branch kit 182 KHRQ22M29H INFORMATION Maximum 8 br...

Page 27: ...sing electrical wiring through the knockout holes wrap the wiring with protective tape to prevent damage 3 Do the following Connect the accessory liquid pipe a to the liquid stop valve brazing Connect...

Page 28: ...test solution from your wholesaler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping gets cold and or le...

Page 29: ...re shall be taken not to overfill the refrigerating system NOTICE Prior to charging the system it shall be pressure tested with the appropriate purging gas The system shall be leak tested on completio...

Page 30: ...s 437 Result The unit will start operation INFORMATION The manual refrigerant charge operation will automatically stop within 30 minutes If charging is not completed after 30 minutes perform the addit...

Page 31: ...iring regulations WARNING ALWAYS use multicore cable for power supply cables 15 1 About electrical compliance Equipment complying with EN IEC 61000 3 12 provided that the short circuit power Ssc is gr...

Page 32: ...th leakage circuit breaker b Fuse c Power supply cable 4 Fix the cables power supply and interconnection cable with a cable tie to the stop valve attachment plate and route the wiring according to the...

Page 33: ...to SVS output device Specifications of the SVS output Maximum voltage 40 VDC Maximum current 0 025 A Polarity of terminal 1 Polarity of terminal 2 It is mandatory to use a surge killer to protect the...

Page 34: ...ed above the indoor unit cover the stop valves f see above with sealing material to prevent condensed water on the stop valves from moving to the indoor unit NOTICE Any exposed piping might cause cond...

Page 35: ...e also 17 1 4 To access mode 1 or 2 436 17 1 5 To use mode 1 436 17 1 6 To use mode 2 436 17 1 7 Mode 1 Monitoring settings 436 17 1 8 Mode 2 Field settings 437 17 1 2 To access the field setting comp...

Page 36: ...atus of the unit What How Changing and accessing the setting in mode 1 Once mode 1 is selected push BS1 one time you can select the wanted setting It is done by pushing BS2 Accessing the selected sett...

Page 37: ...remote controller connected to the system 1 Supervisor remote controller connected to system 18 Commissioning NOTICE General commissioning checklist Next to the commissioning instructions in this cha...

Page 38: ...ctions for equipment using R32 refrigerant 49 Field settings Make sure all field settings you want are set See 17 1 Making field settings 434 Installation date and field setting Be sure to keep a reco...

Page 39: ...display and on the user interface of the indoor unit 19 1 1 Error codes Overview In case other error codes appear contact your dealer Main code Cause Solution SVEO a SVS b The R32 sensor in one of the...

Page 40: ...ly voltage Check if power supply is within range Insufficient supply voltage Check if the supply voltage is supplied properly Malfunction code System test run not yet executed system operation not pos...

Page 41: ...0 11 and audible alarm and red warning signal is generated from this remote controller The unit number is displayed on this remote controller k Error code U9 02 is displayed on this remote controller...

Page 42: ...s walls baffle plates E Obstacle roof a b c d e Minimum service space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction of o...

Page 43: ...rheat g One way valve R7T Thermistor heat exchanger h Pressure relief valve R10T Thermistor fin i PCB cooling R21T Thermistor discharge j Double tube heat exchanger k Distributor Refrigerant flow l He...

Page 44: ...PTC thermistor S1NPH High pressure sensor S1NPL Low pressure sensor S1PH High pressure switch S1S Air control switch option S2S Cool heat selector switch option SEG A1P 7 segment display SFB Mechanic...

Page 45: ...itch option SEG A1P 7 segment display SFB Mechanical ventilation error input field supply V D Diode module V1R V2R A1P IGBT power module V3R A1P Diode module X A PCB connector X M Terminal strip X Y C...

Page 46: ......

Page 47: ......

Page 48: ...4P600329 1A 2020 01 Copyright 2020 Daikin 4P600329 1 A 0000000X Verantwortung f r Energie und Umwelt...

Reviews: