19 Commissioning
Installation and operation manual
37
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600329-1E – 2023.02
18.1.7
Mode 1: monitoring settings
[1‑1]
Shows the status of low noise operation.
[1‑1]
Description
0
Unit is currently not operating under low noise
restrictions.
1
Unit is currently operating under low noise
restrictions.
[1‑2]
Shows the status of power consumption limitation operation.
[1‑2]
Description
0
Unit is currently not operating under power
consumption limitations.
1
Unit is currently operating under power
consumption limitation.
[1‑5] [1‑6]
Code
Shows ...
[1‑5]
The current T
e
target parameter position
[1‑6]
The current T
c
target parameter position
[1‑10]
Shows the total number of connected indoor units.
[1‑17] [1‑18] [1‑19]
Code
Shows ...
[1‑17]
The latest malfunction code
[1‑18]
The 2nd last malfunction code
[1‑19]
The 3rd last malfunction code
[1‑40] [1‑41]
Code
Shows ...
[1‑40]
The current cooling comfort setting
[1‑41]
The current heating comfort setting
18.1.8
Mode 2: field settings
[2‑8]
T
e
target temperature during cooling operation.
[2‑8]
T
e
target [°C]
0 (default)
Auto
2
6
3
7
4
8
5
9
6
10
7
11
[2‑9]
T
c
target temperature during heating operation.
[2‑9]
T
c
target (°C)
0 (default)
Auto
1
41
3
43
6
46
[2‑18]
Fan high static pressure setting.
If the static pressure of the outdoor unit fan increases, the airflow
decreases and the fan motor power input increases. The unit can
estimate the ESP via measurements.
Via this setting, the installer can set the ESP to a fixed level or
change the moment of ESP evaluation.
Note:
For an ESP level higher than 45 Pa, level 0 is kept for
reliability of the fan motor.
[2‑18]
Description
0 (default)
Auto setting at commissioning mode and
stand-by mode
1
Auto setting at commissioning mode only
2
Level 0 (ESP between 0-20 Pa)
3
Level 1 (ESP between 20-35 Pa)
4
Level 2 (ESP between 35-45 Pa)
[2‑20]
Manual additional refrigerant charge.
[2‑20]
Description
0 (default)
Deactivated.
1
Activated.
To stop the manual additional refrigerant
charge operation (when the required additional
refrigerant amount is charged), push BS3. If
this function was not aborted by pushing BS3,
the unit will stop its operation after 30 minutes.
If 30 minutes was not sufficient to add the
needed refrigerant amount, the function can be
reactivated by changing the field setting again.
[2‑60]
Supervisor remote controller setting. A power reset is required to
save this setting.
For details about the supervisor remote controller, see
17] or refer to the remote controller
installation and user reference guide.
[2‑60]
Description
0 (default)
No supervisor remote controller connected to
the system
1
Supervisor remote controller connected to
system
19
Commissioning
NOTICE
General
commissioning
checklist.
Next
to
the
commissioning instructions in this chapter, a general
commissioning checklist is also available on the Daikin
Business Portal (authentication required).
The general commissioning checklist is complementary to
the instructions in this chapter and can be used as a
guideline and reporting template during commissioning and
hand-over to the user.
NOTICE
ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.